HomeMy WebLinkAboutNCG590017_Compliance Evaluation Inspection_20180629 ROY COOPER
Governor
MICHAEL S.REGAN
Secretary
LINDA CULPEPPER
Water Resources
Interim Director
• Environmental Quality
June 29, 2018
Mr. Steven Drew,Director
Water Resources Department
City of Greensboro
P.O.Box 3136
Greensboro,NC 27402-3136 RECEIVED/DENR/DWR
SUBJECT: Compliance Evaluation Inspection JUL 10 2018
Lake Townsend Water Treatment Plant
General Permit No.NCG590017 Water Resources
Guilford County Permitting Section
Dear Mr. Drew:
On June 25,2018,Jenny Graznak and Kelli Park of this office met with Earl Green,Dell Harney,Larry
Nance, and Ali Khan to perform a Compliance Evaluation Inspection on the permitted wastewater
discharge from the Lake Townsend Water Treatment Plant(WTP).The inspection findings are detailed
below and an inspection checklist is attached.
1.Permit
The individual permit for this facility(NC0081671)was rescinded in July 2017 and replaced with the
general permit for water treatment plants (NCG590017). Please note that the general permit requires
annual Whole Effluent Toxicity testing,using an effluent concentration of 90%.
2. Self-Monitoring Program
The Discharge Monitoring Reports (DMRs)were reviewed for the period of May 2017 through April
2018. It was noted that all sampling was performed per the frequencies specified in the permit. There
were multiple violations during this period, which were addressed in separate correspondence from
this office. A comparison of the July 2017 DMR with the facility's laboratory data for temperature,
pH, total residual chlorine, turbidity, and TSS showed that these parameters were transcribed
accurately. •Meritech handles the Whole Effluent Toxicity, metals, fluoride, total nitrogen, and
ammonia testing for the facility.
3. Flow Measurement
The permit requires continuous effluent flow recording and annual calibration of the flow measuring
device. The daily effluent flow values reported on the DMRs are measured using an ultrasonic meter
and rectangular weir at the discharge structure. The meter is calibrated every six months by City of
Greensboro staff. The meter was last calibrated on April 6, 2018.
4. Sludge Handling and Disposal
Solids were removed from the settling lagoon October 2017 through March 2018 by a private
contractor(Synagro) using a portable centrifuge. This removal event caused the elevated TSS levels
s""1J'catl�ir�g Compares 2r,.1._
State of North Carolina Environmental Quality
450 W.Hanes Mill Road,Suite 300,Winston-Salem,North Carolina 27105
Phone:336-776-98001 FAX:336-776-9797
•
r e
that led to the violations that are listed in one of the attachments. Greensboro will construct a second
settling lagoon to address this recurring noncompliance issue.
5. Operations and Maintenance
The Operator in Responsible Charge(ORC)for this facility is Earl Green.The facility was competently
operated and maintained. No problems or concerns were noted.
6.Facility Site Review
Wastewater from this plant is generated from filter backwash,which is clarified in the settling lagoon,
and then discharged. The wastewater handling system consists of the following: mixing basin for
dechlorination addition, settling lagoon, ultrasonic flow meter, and effluent outfall. Construction is
ongoing at this facility for upgrades.
7.Effluent/Receiving Waters
The system discharges into Reedy Fork,classified as WS-V;NSW waters in the Cape Fear River Basin.
The effluent was observed to be clear on the day of inspection.
Should you have any questions concerning this report, please contact Jenny Graznak or me at (336)
776-9800.
Sincerely,
Sherri V.Knight,P.E.
Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources
Attachments: Inspection Report
Monitoring Report Violations
fr
cc: Earl Green<earl.green@greensboro-nc.gov>
NPDES Unit
Central Files
WSRO
y.
United States Environmental Protection Agency Form Approved
EPA Washington,D C 20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 I5 I 3 NCG590017 111 12 I 18/06/25 117 18 I 19 Li 20I
21111111 1111111111111111111111111 11111111111 p6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved
67 I 701 Li
I 71 I—I 72 I N I 731 1 174 751 1 1 1 1 1 1 180
Section B.FacilityiData l�-J� 1
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 12.00PM 18/06/25 17/07/01
Lake Townsend VVTP
Exit Time/Date Permit Expiration Date
6268 Bryan Park Rd
01 30PM 18/06/25 19/07/31
Greensboro NC 27402
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Earl Clayton Green/ORC/336-383-9882/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Lewis Walker,2503 White St Greensboro NC 27405//336-373-7662/
No
Section C Areas Evaluated During Inspection(Check only those areas evaluated)
▪ Permit • Flow Measurement II Operations&Maintenance II Records/Reports
▪ Self-Monitoring Program II Sludge Handling Disposal • Facility Site Review NI Effluent/Receiving Waters
Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Jennifer Graznak c WSRO WQ//336-771-5000/ / 2-q
r01/ /G0t �1
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
&/24/12
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type (Cont.) 1
31 NCG590017 111 121 18/06/25 1 17 18 LI
I
Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
1. Permit
The individual permit for this facility(NC0081671)was rescinded in July 2017 and replaced with the
general permit for water treatment plants(NCG590017). Please note that the general permit requires
annual Whole Effluent Toxicity testing, using an effluent concentration of 90%.
2. Self-Monitoring Program
The Discharge Monitoring Reports (DMRs)were reviewed for the period of May 2017 through April
2018. It was noted that all sampling was performed per the frequencies specified in the permit. There
were multiple violations during this period,which were addressed in separate correspondence from
this office.A comparison of the July 2017 DMR with the facility's laboratory data for temperature, pH,
total residual chlorine,turbidity, and TSS showed that these parameters were transcribed accurately.
Meritech handles the Whole Effluent Toxicity, metals,fluoride, total nitrogen, and ammonia testing for
the facility.
3. Flow Measurement
The permit requires continuous effluent flow recording and annual calibration of the flow measuring
device.The daily effluent flow values reported on the DMRs are measured using an ultrasonic meter
and rectangular weir at the discharge structure. The meter is calibrated every six months by City of
Greensboro staff. The meter was last calibrated on April 6, 2018.
4. Sludge Handling and Disposal
Solids were removed from the settling lagoon October 2017 through March 2018 by a private
contractor(Synagro) using a portable centrifuge. This removal event caused the elevated TSS levels
that led to the violations that are listed in one of the attachments. Greensboro will construct a second
settling lagoon to address this recurring noncompliance issue.
5. Operations and Maintenance
The Operator in Responsible Charge (ORC) for this facility is Earl Green.The facility was competently
operated and maintained. No problems or concerns were noted.
6. Facility Site Review
Wastewater from this plant is generated from filter backwash,which is clarified in the settling lagoon.
The wastewater handling system consists of the following. mixing basin for dichlorination addition,
settling lagoon, ultrasonic flow meter, and effluent outfall. Construction is ongoing at this facility for
upgrades.
7. Effluent/Receiving Waters
The system discharges into Reddy Fork,classified as WS-V; NSW waters in the Cape Fear River
Basin. The effluent was observed to be clear on the day of inspection.
Page# 2
Permit: NCG590017 Owner-Facility: Lake Townsend WTP
Inspection Date: 06/25/2018 Inspection Type: Compliance Evaluation
Operations &Maintenance Yes No NA NE
• Is the plant generally clean with acceptable housekeeping? • 0 0 0
Does the facility analyze process control parameters,for ex: MLSS, MCRT, Settleable • 000
Solids, pH, DO, Sludge Judge,and other that are applicable?
Comment: The Operator in Responsible Charge(ORC)for this facility is Earl Green.The facility was
competently operated and maintained. No problems or concerns were noted.
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 001110
application?
Is the facility as described in the permit? • 0 ❑ ❑
#Are there any special conditions for the permit? 011100
Is access to the plant site restricted to the general public'? • 000
Is the inspector granted access to all areas for inspection'? • 000
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit'? • ❑ ❑ ❑
Is all required information readily available, complete and current? • 000
Are all records maintained for 3 years(lab. reg. required 5 years)? • 000
Are analytical results consistent with data reported on DMRs? 1000
Is the chain-of-custody complete? U ❑ ❑ ❑
Dates,times and location of sampling
Name of individual performing the sampling •
Results of analysis and calibration U
Dates of analysis •
Name of person performing analyses U
Transported COCs •
Are DMRs complete.do they include all permit parameters'? U ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ U ❑
(If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with'a certified operator 00 • O
on each shift?
Is the ORC visitation log available and current'? • 000
Is the ORC certified at grade equal to or higher than the facility classification'? U 000
Is the backup operator certified at one grade less or greater than the facility classification? • 000
Is a copy of the current NPDES permit available on site'? • 000
Page# 3
Permit: NCG590017 Owner-Facility: Lake Townsend VVTP
Inspection Date: 06/25/2018 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? 0 0 • 0
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? • 0 0 0
Are the receiving water free of foam other than trace amounts and other debris'? • 0 0 0
If effluent (diffuser pipes are required) are they operating properly? 0 0 II ❑
Comment.
Flow Measurement-Effluent Yes No NA NE
#Is flow meter used for reporting? • 0 0 0
Is flow meter calibrated annually? • 0 0 0
Is the flow meter operational'? • 0 0 0
(If units are separated) Does the chart recorder match the flow meter? 0 0 • 0
Comment
De-chlorination Yes No NA NE
Type of system? Liquid
Is the feed ratio proportional to chlorine amount(1 to 1)? 0 • 0 0
Is storage appropriate for cylinders? 0 0 I 0
#Is de-chlorination substance stored away from chlorine containers? 0 0 MI 0
Comment:
Are the tablets the proper size and type? 0 0 U ❑
Are tablet de-chlorinators operational? 0 0 NI 0
Number of tubes in use?
Comment. Sodium thiosulfate is added for dechlorination, and caustic is used for pH adjustment.
Page# 4
h
''..i,
MONITORING REPORT(MR)VIOLATIONS for: Report Date' 06/29/18 Page 1 of 2
-
=•m a* :"a <"ar ,,�-�"-s, x.��"r., K�;'" ,"--�-;�,r_-, u,�K,,,,^ sE;.st �:two,"„�.,;;...s���:r:-.^,`„�:3'�e�.;-<«rm*yt�r";�'e�wse m,>�Yr;:._"�w,..ra.»«„v.."„.� ,�':�- 'W--�"y°,�rwt-.�. `x,
r,.w>4” `>s., *c'.'' ', 3" .,t,P" ';`,,,,, "g a''., „sya._sh_ fir.
'ra�a���;�.;�;w., �`:�xx ��,= 'ism*�"�� �'➢�„«,>,<_ r,,:i«��:,;-� ,�,.;,;�- E i3'�<>_ ,",ice,:,i`t`* ,�,:'��z, „�, ,�,. `� ;x�'- �`i;
moi" �� "r�}�"� =� .,.�'=u� �?�-_ �+ a�'�, x;�',,a};t ,},�.,.'`=�,w �'; ��.- .>1,. _w,«, �x"aa .�:,.
3. ,), F.ir>;'",. "r,,-,?' �a�r Wiz" '�..v�"��,.;. - ri,e''s - 'a,.'_.�}.-',.R'�,`t' 'I,-�",r,,,.}', "�?i,=te. ,,,.a a- riz•°r ,,EYE 'iia' +X?- �K txi-,v ,�.
-�.- -`"¢.➢�.• y '; <�r' s�i'rlia'a r i r e ���+,,.»„�3s: 'sa`�� "��n a.�� xo- r s,., ,<-,.,
«'«'�°� `.G`�^e%*ry ,.3. ��y�'�a�_, «.S, ",;�w-> '-�_' .;,�,,_r ,1>;f>�" ��u'«;.t:'�u7,x E. ,.sir s�. .�, �"u, �'«--s`.. �a�;'.-r
- =-_�` �- -_ ��, ;;:, �� ,i,�a�,�;y3r'_ x <,� �,.Pro ra :;�� _ :��r
-kz °_.�-:5�=7����7 it 4= !0�°S = •�'a�: i, '°a ��aatlQnp�i�f'�.a-.:I�i>s'tifVlr�i'�ti�'n �-�'� - k �/oma' •+� - »
'tPercnif-;^NQ=i;',,-,4:;.0,1,--4--4
894.0,1,-- �Mfts°f3etween, an -Re�yl ,n _ �-�°,r•'' n' ir, , ! _,, 9_. ! . ,; _.1. , : «ir 4r:4
_ _e. - a"- :�� °;';,a.r"°�'r" ,t?.>i.� '�,.-,a. �.��r',n �'v`.•� _ -,3;�T '.$.a..
*s_= ""4-.�-W'�� '-x �rss r�, ,�-r`.,,,�ia Y;.,°<ti"..�x,�,,a., qquui�- �-��,2 ,r�2x,. ,�:.t- �k �,��-��&.-" r�w-�^
�N"-3 ^'�� ➢'� ^'6iHz vii s' i v'z�x-'i�i-"7"�'v rf '.'Fa.+fr v
t 3
s f.,� -0-'3-'
F i 'zt-�.it _
>a,� y
F°j'➢ «S a' s-tai":..
�-�' �.t, - Q do lOh; _.�-
.m.r tJl1��9k3-r >;�.VI d rs"
;'c' - QUrit 'mow-�'�� �� �
-'P�ra
e ASC �' N-;'° v,
' i rtilV8ft1 ,} ir., rr�&��'x ''°.
�yFacli�� ii x�e,� ���,H ��.° rr, - ��� -�s.- �w
Y'M-�'} �- � �fir. r>;,�,,,, :+'�4''`x:�, �, `,i.'�! �, `�`'��,`v x�m,
- Te- °,i_- ,9""`f_, .'#`;j0i",.}'>"i'=` :e *f �' �`:tr v «j .,fG.z ..j,.0 ?�, tJf'�-.
,"u 13 ,a 4'e _x^',A, ,£e',a �Y ,�.� _-v�lYq'
�'" 4',Wa, mei.u,
- it-,a 'Yy,='..z ,C�,
S't".- a
:yrs.<, .,3 ^"S•rd-, '-S3
,,,E �x�=_,r. s:` ,,:;.,, ,>;,)i� �a
a.'ter � err , "^ate';
,; <`D.c o}, �=-B%,« } �7,,, 4utn bSxi v`�-.}, .i�k.n'�r 5P- �%:
s «a= .:�. _�', -`� '`-'rii'OA r i ray _-'"-.,,.,,,,
'a orIVIiW�Qr-/ob_ .,�,u >?_'� �,i--=,�r` >� _�> �,r-y-s_`s��t r t ,_
<°M 1 n `,-�=�_,�, ,a.��:«� R�' "� �°�,- ,�,� - ,,,x"� or Mme: «-,a �°.
^�;,.a _.fir_ -„_,` �,.�a>^-- _� -"- '� W �'� w' r � ,:,:�3 �3
r 1 -•a=�A �:"t' `i. ;ars bw`;i'F.r,.t-' ;'�__
,•:fir' i== a � _'� Imo_ •''�'�,- '"w' =.a'>r
'3 E '£ii�r^
'..--,',,,4,-e';-' i. r 4r.- .'$ , Y C" S,-a" ,'4`°,3,r «,'rc` n.f It 3p
,N2x, '�r„ v�
�- "y4"x` `x."vr,"�. ,4 '"a..,;t'.",r`r.°s` 'e'er '�m"�,`�s .k�,`"".:
t Yi,,� -,„� `�a” �'� �,. `aa. „ >r, � .-moi `��>i;:�,,;i��,.>:.' «;�w�,�}�>.;,,r�,.Nsw;`,'A',;;;��::,,s,,.f <...An :�,;_,,°xx .�,",.�H`, .:a:',,�
wr>�i;.. ,«,w„»x"..,° fin .-,.�,”,,� ": ';tr,z:�A.,T,,. �,'s��.w,".�.....�a.�y .��,'vF,�,.,�ua,s� �ax °,,ia«<�,r �„� �»-�,>�:"'��>«,�,,,.,,, _,-_ �n
PERMIT: NCG590017 FACILITY: City of Greensboro-Lake Townsend WTP COUNTY:Guilford REGION: Winston-Salem
Limit Violation
MONITORING OUTFALU VIOLATION UNIT OF CALCULATED
REPORT PPI LOCATION PARAMETER DATE FREQUENCY MEASURE LIMIT VALUE Over VIOLATION TYPE VIOLATION ACTION
10_2017 001 Effluent Chlorine,Total Residual 10/09/17 2 X month ug/I 17 24 41.2 Daily Maximum No Action,BPJ
Exceeded
02_2018 001 Effluent Chlorine,Total Residual 02/07/18 2 X month ug/I 17 23 35 3 Daily Maximum No Action,BPJ
Exceeded
03_2018 001 Effluent pH 03/14/18 Monthly su 9 9 1 1.1 Daily Maximum No Action,BPJ -Exceeded
03_2018 001 Effluent pH 03/15/18 Monthly su 9 9.4 4 4 Daily Maximum No Action,BPJ
Exceeded
10_2017 001 Effluent Solids,Total Suspended- 10/04/17 2 X month mg/I 45 205.4 356 4 Daily Maximum Proceed to NOV
Concentration Exceeded
10_2017 001 Effluent Solids,Total Suspended- 10/23/17 2 X month mg/I 45 78.7 74.9 Daily Maximum Proceed to NOV
Concentration Exceeded
10_2017 001 Effluent Solids,Total Suspended.. 10/31/17 2 X month mg/I 30 77.6 158.7 Monthly Average Proceed to NOV
Concentration Exceeded
11-2017 001 Effluent Solids,Total Suspended- 11/06/17 2 X month mg/I 45 146 224.4 Daily Maximum Proceed to NOV
Concentration Exceeded
11-2017 001 Effluent Solids,Total Suspended- 11/20/17 2 X month mg/I 45 57.2 27.1 Daily Maximum Proceed to NOV
Concentration Exceeded
11_2017 001 Effluent Solids,Total Suspended- 11/30/17 2 X month mg/I 30 101 6 238 7 Monthly Average Proceed to NOV .
Concentration Exceeded
02_2018 001 Effluent Solids,Total Suspended- 02/07/18 2 X month mg/I 45 -510 1,033.3 Daily Maximum Proceed to NOV
Concentration Exceeded
02_2018 001 Effluent Solids,Total Suspended- 02/28/18 2 X month mg/I 30 274.85 816 2 Monthly Average Proceed to NOV
Concentration Exceeded
10_2017 001 Effluent Turbidity 10/23/17 Monthly ntu 50 52 4 Daily Maximum Proceed to NOV
Exceeded
11_2017 001 Effluent Turbidity 11/06/17 Monthly ntu 50 63.7 27.4 Daily Maximum Proceed to NOV
Exceeded
02-2018 001 Effluent Turbidity 02/07/18 Monthly ntu 50 118 136 Daily Maximum Proceed to NOV
Exceeded
MONITORING REPORT(MR) VIOLATIONS for: Report Date: 06/29/18 Page 2 of 2
PERMIT: NCG590017 FACILITY: City of Greensboro -Lake Townsend WTP COUNTY: Guilford REGION: Winston-Salem
Limit Violation
MONITORING OUTFALL/ VIOLATION UNIT OF CALCULATED % VIOLATION TYPE VIOLATION ACTION
REPORT PPI LOCATION PARAMETER DATE FREQUENCY MEASURE LIMIT VALUE Over
02 _ 2018 001 Effluent Turbidity 02/19/18 Monthly ntu 50 65.5 31 Daily Maximum Proceed to NOV
Exceeded