HomeMy WebLinkAboutWQ0002052_CEI_20180627
State of North Carolina | Environmental Quality | Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
June 27, 2018
Lee Slusher
Milliken & Company
PO Box 1926
M-482
Spartanburg, SC 29304
SUBJECT: Compliance Inspection Report
Golden Valley Plant
Non-discharge Permit No. WQ0002052
Rutherford County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Golden Valley
Plant on 6/21/2018. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non-discharge Permit No.
WQ0002052. The findings and comments noted during this inspection are provided in the
enclosed copy of the inspection report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a
response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact me at 828-296-4500 or
via email at bev.price@ncdenr.gov.
Sincerely,
Beverly Price, Environmental Senior Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Greg Marana
WQS ARO Server
Laserfiche
Compliance Inspection Report
Permit:WQ0002052 Effective:04/01/17 Expiration:03/31/22 Owner :Milliken & Company
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Rutherford
Asheville
Lee Slusher
Effective:Expiration:Facility:Golden Valley Plant
2080 NC Hwy 226
Bostic NC 28018
Title:Phone:864-503-1844Sr. Environmental Engineer
From Asheville: Take I-40 East to Exit 86 ( Hwy. 226). Travel approximately 18 miles on Hwy. 226 south to Milliken-Golden Valley
Plant located on the left.
Barbara Jean Warlick 1003683 828-247-4300
Secondary ORC(s):
828-247-4300Phone:27004Certification:Michael D FortenberryPrimary ORC:
SI,System Classifications:
24 hour contact name Greg Marana 828-247-4313
On-site representative Greg Marana 828-247-4313
On-site representative Michael D Fortenberry 828-247-4300
On-site representative Barbara Warlick 828-247-4300
On-Site Representative(s):
Related Permits:
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
06/21/2018 09:30AM 11:50AM
Beverly Price 828-296-4500
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Wastewater Irrigation
Compliance Evaluation
Question Areas:
Treatment Flow Measurement-Effluent Treatment Flow Measurement-Influent Miscellaneous Questions
Treatment Flow Measurement-Water
Use Records
Treatment Record Keeping
Treatment Lagoons End Use-Irrigation Treatment Flow Measurement
(See attachment summary)
Page:1
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0002052
06/21/2018 Compliance Evaluation
Milliken & Company
Routine
Inspection Summary:
The inspection was conducted by Beverly Price of the Asheville Regional Office. Greg Marana, Mike Fortenberry and
Barbara Warlick assisted with the inspection.
Our database shows Mike Fortenberry as the primary spray irrigation Operator in Responsible Charge (ORC). The database
shows Barbara Warlick maintains a spray irrigation certification. Please submit an ORC Designation Form for Ms. Warlick.
Please contact Jenee Williamston at 919-707-9089 or Beth Buffington at 919-707-9105 with the Operator Certification
Section if you have questions.
The influent meters were calibrated on 11/21/17 by Clearwater, Inc. The Ultrasonic 4210 had a 1% error; the Bubbler 4230
had a 0% error.
The effluent meter was calibrated by Venture Measurement on 5/25/17 (placed in service 3/21/18). The meter was within
tolerance limits: 700 gal - 100.2%; 600 gal – 100.8%;100 gal – 99.9%.
The March & April 2018 NDMR/NDAR’s were reviewed for accuracy. The April 2018 GW-59 was reviewed for accuracy.
Soils Analysis: 07/11/17; pH = 6.3
Spray heads were calibrated 12/20/17.
The spray field is to be scheduled for cutting within the month.
There are a few moist/soft spots at the toe of the dam. This area also contains vegetation that is indicative of consistent
moisture. This issue has been noted in past inspections and the permittee had an engineer investigate in 2007. This area
should be inspected frequently. Any increase in moisture should be documented and investigated further to ensure the
integrity of the dam.
The facility is well maintained and operated. Records appeared to be complete.
Page:2
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0002052
06/21/2018 Compliance Evaluation
Milliken & Company
Routine
Type Yes No NA NE
Activated Sludge Spray, LR
Reuse (Quality)
Single Family Spray, LR
Activated Sludge Spray, HR
Recycle/Reuse
Single Family Drip
Infiltration System
Activated Sludge Drip, LR
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
Comment:
Treatment Flow Measurement-Influent Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment:
Treatment Flow Measurement-Water Use Records Yes No NA NE
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement-Effluent Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
The effleunt meter is an in-line meter from the irrigation pond to the sprayfield. The meter does
not record flow (i.e. there is no tape or chart recorder).
Comment:
Record Keeping Yes No NA NE
Page:3
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0002052
06/21/2018 Compliance Evaluation
Milliken & Company
Routine
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
Effluent sampling does not require volatile organic compound analysis.
Effluent monitoring results for March 2018 that exceed the 2L Groundwater (GW) Standards:
fecal coliform and ammonia nitrogen. The permit does not require fecal coliform monitoring for
GW. The April GW monitoring event did not show exceedances for ammonia nitrogen.
PAN records are not required.
The soils analysis did not indicate the need for lime application; soil pH = 6.3.
Comment:
End Use-Irrigation Yes No NA NE
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Page:4
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0002052
06/21/2018 Compliance Evaluation
Milliken & Company
Routine
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
The crop type is not specified in the permit. The crop type is fescue.
The permitted acreage is approximately 12.25 acres. Only 5.97 acres are irrigated due to the
proximity of a mobile home park to the spray field. 5.97 acres are used in th calculations on
Form NDAR-1.
There are no water supply wells within the Compliance Boundary.
Comment:
001 -
Treatment Lagoons Yes No NA NE
Lagoon Type None
Primary/Secondary Primary
Influent structure
Banks/berms (seepage and erosion)
Vegetation (excessive vegetation on banks/berms)
Liner
Liner Type Unknown
Baffles/curtains
Freeboard Marker
Required freeboard 2
Feet
Actual freeboard 3.1
Feet
Are increments clearly marked on gauge at adequate intervals?
Has the water level gauge been surveyed w/ respect to lowest point on dike? wall?
No Evidence of overflow
Page:5
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0002052
06/21/2018 Compliance Evaluation
Milliken & Company
Routine
Acceptable color
Floating mats
Excessive solids buildup
Aerators/mixers
Effluent structure
Lagoon cover
Page:6