HomeMy WebLinkAboutNC0004375_Inspection_20180608s Water Resources Environmental Quality 8 June 2018 Mr. Bruce Hintzen, Facility Manager Clariant Corporation 4000 Monroe Road Charlotte, North Carolina 28205 Subject: Compliance Evaluation Inspection Clariant Corp./Mt. Holly East WWTP NPDES Permit No. NC0004375 Mecklenburg County Dear Mr. Hintzen: ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER Interim Director Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on June 5, 2018, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible Charge (ORC) of our findings by forwarding a copy of the enclosed report. Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192, or via email at wes.bellgncdenr.gov. Sincerely, DocuSigned by: �PiY 'B C& A61696D90CC3437... for W. Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ Enclosure: Inspection Report cc: Rusty Rozzelle, MCWQP (via email) State of North Carolina I Environmental Quality) Water Resources I Water Quality Regional Operations Mooresville Regional Office 1610 East Center Avenue, Suite 310 1 Mooresville, North Carolina 28115 704-663-1699 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 15 I 3 I NC0004375 111 12 I 18/06/05 I17 18 I S J 19 LG] 201 I 211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved------------------- 67 2.0 70 Id I 71 I.. I 72 I �, I 73 �74 751 I I I 1 1 1 I80 I—I u Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 09:05AM 18/06/05 18/01/01 Mount Holly East Facility 11701 Mount Holly Rd Exit Time/Date Permit Expiration Date Charlotte NC 28214 01:00PM 18/06/05 22/12/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Dwayne R Wallace/ORC/704-307-3870/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Ken Golder,4000 Monroe Rd Charlotte NC 28205/CEO CFO/704-331-7000/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date EDocuSigned by: 6/7/2018 Wes Bell MRO WQ//704-663-1699 Ext.2192/ s� �PiY Be A:,, e.D90CC3437... Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NC0004375 111 121 18/06/05 1 17 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# Permit: NC0004375 Owner - Facility: Mount Holly East Facility Inspection Date: 06/05/2018 Inspection Type: Compliance Evaluation Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? 0 ❑ ❑ ❑ Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The industrial site (Reventure Park) currently has eight tenants that mainly discharge domestic wastewater to the WWTP. One of these tenants also discharges approximately 5,000 qpd of process wastewater (soap/tap water) resulting from the washing of concrete forms. The last compliance evaluation inspection was performed at the facility on 8/25/16 by DWR staff. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported CM Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ Page# 3 Permit: NC0004375 Inspection Date: 06/05/2018 Record Keeping Owner - Facility: Mount Holly East Facility Inspection Type: Compliance Evaluation Yes No NA NE Comment: The records reviewed durina the inspection were oraanized and well maintained. Discharae Monitoring Reports (eDMRs) were reviewed for the period April 2017 through March 2018. No effluent limit violations were reported and all monitoring frequencies were correct. A revised February 2018 edmr will be submitted to correct the effluent and upstream hardness results (change results to mg/L). Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: On-site field analyses (dissolved oxygen, pH, temperature, conductivity) are being performed under Clariant's field laboratory certification #5603. Pace Analytical Services (all effluent parameters except field and toxicity), Shealy Environmental Services (downstream sampling parameters and TRC analyses for pollutant scan), and ETT (toxicity). Effluent Sampling Yes No NA NE Is composite sampling flow proportional? 0 ❑ ❑ ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: The subiect Dermit reauires comDosite and arab effluent samDles. The samDler temDerature was four degrees Celsius and collecting 130 ml. aliquots at the time of the inspection. The facility staff perform and document weekly aliquot verifications. The ORC must ensure that effluent oil & grease samples are collected directly into the container (no intermediate sampling devices/containers) Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, and ❑ ❑ ❑ sampling location)? Comment: The CIRC performs all upstream sampling and the contracted lab personnel (Shealy Environmental Services) performs all downstream sampling. Page# 4 Permit: NC0004375 Inspection Date: 06/05/2018 Owner - Facility: Mount Holly East Facility Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The treatment units currently in service appeared to be properly operated and well maintained. Several treatment units have been removed from the treatment process including primary clarifiers, pH adjustment facilities, aeration basins, etc. Process control measurements were being properly documented and maintained on-site. Pump Station - Influent Yes No NA NE Is the pump wet well free of bypass lines or structures? ❑ 0 ❑ ❑ Is the wet well free of excessive grease? ❑ ❑ ❑ Are all pumps present? 0 ❑ ❑ ❑ Are all pumps operable? 0 ❑ ❑ ❑ Are float controls operable? 0 ❑ ❑ ❑ Is SCADA telemetry available and operational? ❑ ❑ 0 ❑ Is audible and visual alarm available and operational? ❑ ❑ 0 ❑ Comment: The influent pump station is equipped with a bypass conveyance system (gravity flow) to stormwater equalization basin Z03B if flows exceed the capacity of the influent pumps. Equalization Basins Is the basin aerated? Is the basin free of bypass lines or structures to the natural environment? Is the basin free of excessive grease? Are all pumps present? Are all pumps operable? Are float controls operable? Are audible and visual alarms operable? # Is basin size/volume adequate? ❑ ❑ ■ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ Comment: The facility is equipped with multiple stormwater equalization basins (alkaline and non -alkaline drainage areas) that have to be manually pumped back into the influent waste stream. Aeration Basins Mode of operation Type of aeration system Is the basin free of dead spots? Yes No NA NE Diffused ■ ❑ ❑ ❑ Page# 5 Permit: NC0004375 Inspection Date: 06/05/2018 Owner - Facility: Mount Holly East Facility Inspection Type: Compliance Evaluation Is the clarifier free of black and odorous wastewater? 0 ❑ Aeration Basins Yes No NA NE Are surface aerators and mixers operational? 0 ❑ ❑ ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? 0 ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) 0 ❑ ❑ ❑ Comment: The facility is equipped with a circular aeration basin (former secondary clarifier). A low biomass population is maintained due to the low organic influent loading. Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? Are pumps in place? ❑ ❑ ❑ Are weirs level? ❑ 0 ❑ ❑ Is the site free of weir blockage? Are there adequate spare parts and supplies on site? ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? 0 ❑ ❑ ❑ Is the return rate acceptable (low turbulence)? E ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) 0 ❑ ❑ ❑ Comment: The clarifier weirs were not sianificantly unlevel. The weirs should be DrODerly adiusted if operational problems (including short-circuiting) are observed. Pumps -RAS -WAS Yes No NA NE Are pumps in place? 0 ❑ ❑ ❑ Are pumps operational? 0 ❑ ❑ ❑ Are there adequate spare parts and supplies on site? ❑ ❑ ❑ 0 Comment: Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page# 6 Permit: NC0004375 Inspection Date: 06/05/2018 Flow Measurement - Effluent Owner - Facility: Mount Holly East Facility Inspection Type: Compliance Evaluation (If units are separated) Does the chart recorder match the flow meter? Yes No NA NE ❑ ❑ ■ ❑ Comment: The ORC verifies the flow meter's accuracv twice Der month and calibrates the flow meter as -needed during the bi-monthly verifications. The flow meter was last verified on 5/23/18. • ❑ ❑ Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ 0 If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: The effluent appeared clear with no floatable solids or foam. Solids Handling Equipment Is the equipment operational? Is the chemical feed equipment operational? Is storage adequate? Is the site free of high level of solids in filtrate from filter presses or vacuum filters? Is the site free of sludge buildup on belts and/or rollers of filter press? Is the site free of excessive moisture in belt filter press sludge cake? The facility has an approved sludge management plan? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ■ ❑ ❑ ❑ Comment: The facilitv is eauiDDed with two sludae storaae tanks (eauiDDed with mixers) and two belt presses. One of the belt presses was not operational. Dewatered sludge is transported to the on-site landfill (Cell #3) for disposal under the authority of Permit No. WQ0000537. No sludge dewatering has occurred since October 2016 due to the low influent flow/loading to the WWTP. All decant and filtrate are returned to the influent pump station. Page# 7