HomeMy WebLinkAboutNC0022098_Compliance Evaluation Inspection_20180529r
is C1.
Water Resources
Environmental Quality
May 29, 2018
Mr. Derek Hinds
NC Land Lease, LLC
P.O. Box 2533
Christiansburg, VA 24068-2533
SUBJECT: Compliance Evaluation Inspection
Cranbrook Village WWTP
NPDES Permit No. NCO022098
Guilford County
Dear Mr. Hinds:
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Interim Director
On May 23, 2018, Jenny Graznak of this office met with Paul Smith vg®j�Mpliance
Evaluation Inspection of the wastewater treatment system serving Cranbryc N '�idafejfhe inspection
findings are detailed below and an inspection checklist is attached.
Water Resources
L Permit
Permitting Section
The current permit became effective October 1, 2016 and will expire on June 30, 2021. A copy of the
permit was. not available during the inspection. Please make sure that the operator has a copy of the
most recent permit with his records.
2. Self -Monitoring Program'
The Discharge Monitoring Reports (DMRs) were reviewed for the period February 2017 through
March 2018. There were limit violations April, May, and October 2017, and they are summarized in
an attached list. These violations were addressed in separate correspondence from this office. All
sampling during this time appears to have been performed per the frequencies specified in the permit.
A
3. Flow Measurement
The permit requires weekly instantaneous flow monitoring. The effluent flow is manually measured
using the v -notch weir in the contact chamber.
4. Sludge Handling and Disposal
Solids are removed approximately every 6 weeks from the in -ground digester by Carolina Septic Tank
Company. The owner maintains the receipts from these services.
**5. Operations and Maintenance
This treatment system is showing significant signs of age and wear. The ladder to climb on top
of the treatment system is severely rusted and potentially unsafe for the operator and inspector.
The walkway is also severely rusted. The in -ground digester appears to be caving in to some
degree. The bar screen fell off the system at some point and has not been replaced, so the operator
manually removes solids. These issues should be addressed soon before they impact treatment.
��'"Nothing Compares;r-._.,.v
State of North Carolina i Environmental Quality
450 W. Hanes Mill Road, Suite 300, Winston-Salem, North Carolina 27105
Phone: 336-776-98001 FAX: 336-776-9797
6. Facilitv Site Review
The existing wastewater treatment system consists of the following: a single -train aboveground
package plant with flow splitter box (split between aeration basin and influent pump station to control
the flow), aeration basin, secondary clarifier, tablet chlorinator box (no tubes), contact chamber, tablet
dechlorination tubes and effluent discharge pipe. The old in -ground package plant is used for sludge
holding and is not aerated.
6. Records/Reports
A review of the operator's logs indicated that records are being maintained according to the permit. A
comparison of the September 2017 DMR with the corresponding operator records and certified
laboratory data sheets from Pace Analytical showed that all values were properly transcribed onto the
DMR.
7. Effluent/Receiving Waters
The system discharges into Little Alamance Creek, classified WS -IV NSW waters in the Cape Fear
River Basin. The effluent was observed to be clear during the inspection.
Should you have any questions concerning this report, please contact Jenny Graznak or me at (336)
776-9800.
Sincerely,
Id
>10r%Z4,v� �_ 14t?
Sherri V. Knight, P.E.
Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources
cc: Paul Smith (smithindustriegbellsouth.net)
Central Files
019M. ,;WE
WSRO
Attachments: Inspection Checklist
Monitoring Report Violations list
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO022098 I11 12 18/05/23 17 181,•1 19I G I 201
211 1 1111I11111IIIIIIIIIIIIIIIIIIIIIIIIIIIIII�6
Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA Reserved
67 70 LJ 7 I 72 .ti 73 I 174 751 I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
11:00AM 18/05/23
16/10/01
Cranbrook Village Community
4309 Liberty Rd
Exit Time/Date
Permit Expiration Date
Greensboro NC 27406
12:OOPM 18/05/23
21/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
Paul Matthew Smith/ORC/336-932-9347/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Paul Smith,4309 Old Liberty PI Greensboro NC 27407//336-932-9347/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit N Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program E Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
/
Jennifer F Graznak , / WSRO WQ//336-771-5000/ S/ •Za/Z��
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
1,
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
31 NCo022098 111 121 18/05/23 117 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
1. Permit
The current permit became effective October 1, 2016 and will expire on June 30, 2021. A copy of the
permit was not available during the inspection. Please make sure that the operator has a copy of the
most recent permit with his records.
2. Self -Monitoring Program
The Discharge Monitoring Reports (DMRs) were reviewed for the period February 2017 through March
2018. There were limit violations April, May, and October 2017, and they are summarized in an
attached list. These violations were addressed in separate correspondence from this office. All
sampling during this time appears to have been performed per the frequencies specified in the permit.
3. Flow Measurement
The permit requires weekly instantaneous flow monitoring. The effluent flow is manually measured
using the v -notch weir in the contact chamber.
4. Sludge Handling and Disposal
Solids are removed approximately every 6 weeks from the in -ground digester by Carolina Septic Tank
Company. The owner maintains the receipts from these services.
**5. Operations and Maintenance
This treatment system is showing significant signs of age and wear. The ladder to climb on top of the
treatment system is severely rusted and potentially unsafe for the operator and inspector. The walkway
is also severely rusted. The in -ground digester appears to be caving in to some degree. The bar
screen fell off the system at some point and has not been replaced, so the operator manually removes
solids. These issues should be addressed soon before they impact treatment.
6. Facility Site Review
The existing wastewater treatment system consists of the following: a single -train aboveground
package plant with flow splitter box (split between aeration basin and influent pump station to control
the flow), aeration basin, secondary clarifier, tablet chlorinator box (no tubes), contact chamber, tablet
dechlorination tubes and effluent discharge pipe. The old in -ground package plant is used for sludge
holding and is not aerated.
6. Records/Reports
A review of the operator's logs indicated that records are being maintained according to the permit. A
comparison of the September 2017 DMR with the corresponding operator records and certified
laboratory data sheets from Pace Analytical showed that all values were properly transcribed onto the
DMR.
7. Effluent/Receiving Waters
The system discharges into Little Alamance Creek, classified WS -IV NSW waters in the Cape Fear
River Basin, The effluent was observed to be clear during the inspection.
Page#
Permit: NCO022098
Inspection Date: 05123/2018
Owner - Facility: Cranbrook Village Community
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable M ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The treatment system and in -ground sludge holding tank are operational. However, please
note that this entire system is severely deteriorated and needs repair.
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
E
❑
❑
application?
0
❑
❑
❑
Is the facility as described in the permit?
M
❑
❑
❑
# Are there any special conditions for the permit?
❑
E
❑
❑
Is access to the plant site restricted to the general public?
E
❑
❑
❑
Is the inspector granted access to all areas for inspection?
M
❑
❑
❑
Comment: A copy of the permit was not available during the inspection. Please make sure that the
operator has a copy of the most recent permit with his records.
Results of analysis and calibration
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
M
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
M
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
M
❑
❑
❑
Is the chain -of -custody complete?
M
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
E
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
0
❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
M
❑
❑
❑
Page# 3
Permit: NCO022098 Owner - Facility: Cranbrook Village Community
Inspection Date: 05/23/2018 Inspection Type: Compliance Evaluation
Record Keepina Yes No NA NE
Is a copy of the current NPDES permit available on site? ❑ E ❑ ❑
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑
Comment: A comparison of the September 2017 DMR with the corresponding operator records and
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
certified laboratory data sheets from Pace Analytical showed that all values were
properly
❑
❑
transcribed onto the DMR.
❑
❑
0
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
❑
❑
Type of aeration system
Diffused
❑
❑
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
E ❑
❑
❑
Is the foam the proper color for the treatment process?
E ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
N ❑
❑
❑
Is the DO level acceptable?
❑ ❑
❑
N
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑
❑
0
Comment: Two blowers
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
N
❑
❑
❑
Is the site free of weir blockage?
E
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
■
❑
❑
❑
Is the site free of excessive floating sludge?
N
❑
❑
❑
Is the drive unit operational?
E
❑
❑
❑
Is the return rate acceptable (low turbulence)?
N
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
N
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately Y, of the sidewall depth)
❑
❑
❑
0
Comment: Single clarifier with one weir trough
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? ❑ 0 ❑ ❑
Page# 4
Permit: NCO022098
Inspection Date: 05/23/2018
Owner - Facility: Cranbrook Village Community
Inspection Type: Compliance Evaluation
Disinfection -Tablet
Yes No NA NE
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
0
Is the level of chlorine residual acceptable?
E
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
0
❑
Comment: There are no chlorinator tubes Tablets are
placed in the clarifier weir trough and in the
bottom of the chlorinator box.
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ N ❑
Is storage appropriate for cylinders? ❑ ❑ 0 ❑
# Is de -chlorination substance stored away from chlorine containers? ❑ ❑ N ❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? S ❑ ❑ ❑
Number of tubes in use? 2
Comment: The dechlorination unit is attached to the outside of the package plant.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? E ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? N ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ N ❑
Comment: The plant discharges into Little Alamance Creek.
Page# 5
MONITORING REPORT(MR) VIOLATIONS for: Report Date: 05/21/18 Page: 1 of 1
PERMIT: NCO022098 FACILITY: NC Land Lease LLC - Cranbrook Village Community COUNTY: Guilford REGION: Winston-Salem
Limit Violation
MONITORING OUTFALL/ VIOLATION UNIT OF CALCULATED
REPORT PPI LOCATION PARAMETER DATE FREQUENCY MEASURE LIMIT VALUE Over VIOLATION TYPE VIOLATION ACTION
04-2017
001
Effluent
Coliform, Fecal MF, MFC
04/04/17
Weekly
#/100ml
400
1,410
252.5
Daily Maximum
Proceed to NOV
Broth, 44.5 C
Exceeded
04-2017
001
Effluent
Nitrogen, Ammonia Total (as
04/12/17
Weekly
mg/I
19
24.1
26.8
Daily Maximum
Proceed to NOV
N) - Concentration
Exceeded
04-2017
001
Effluent
Nitrogen, Ammonia Total (as
04/19/17
Weekly
mg/I
19
31.6
66.3
Daily Maximum
Proceed to NOV
N) - Concentration
Exceeded
04-2017
001
Effluent
Nitrogen, Ammonia Total (as
04/30/17
Weekly
mg/I
3.8
9.8
158.0
Monthly Average
Proceed to NOV
N) - Concentration
Exceeded
05-2017
001
Effluent
Nitrogen, Ammonia Total (as
05/17/17
Weekly
mg/I
19
25.4
33.7
Daily Maximum
Proceed to NOV
N) - Concentration
Exceeded
05-2017
001
Effluent
Nitrogen, Ammonia Total (as
05/23/17
Weekly
mg/I
19
30.4
60
Daily Maximum
Proceed to NOV
N) - Concentration
Exceeded
05-2017
001
Effluent
Nitrogen, Ammonia Total (as
05/31/17
Weekly
mg/I
3.8
4.5
18.4
Monthly Average
Proceed to NOV
N) - Concentration
Exceeded
10-2017
001
Effluent
Nitrogen, Ammonia Total (as
10/02/17
Weekly
mg/I
19
19.5
2.6
Daily Maximum
Proceed to NOD
N) - Concentration
Exceeded
Monitoring Violation
MONITORING
OUTFALL/
PARAMETER
VIOLATION
FREQUENCY
UNIT OF
LIMIT
CALCULATED
%
VIOLATION TYPE
VIOLATION ACTION
PrPnPT
PPI
.LOCATION
DATE
MEASURE
VALUE
Over
03-2018 001 Effluent Chlorine, Total Residual 03/31/18 2 X week ug/I Frequency Violation None