Loading...
HomeMy WebLinkAboutNC0022098_Compliance Evaluation Inspection_20180529r is C1. Water Resources Environmental Quality May 29, 2018 Mr. Derek Hinds NC Land Lease, LLC P.O. Box 2533 Christiansburg, VA 24068-2533 SUBJECT: Compliance Evaluation Inspection Cranbrook Village WWTP NPDES Permit No. NCO022098 Guilford County Dear Mr. Hinds: ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER Interim Director On May 23, 2018, Jenny Graznak of this office met with Paul Smith vg®j�Mpliance Evaluation Inspection of the wastewater treatment system serving Cranbryc N '�idafejfhe inspection findings are detailed below and an inspection checklist is attached. Water Resources L Permit Permitting Section The current permit became effective October 1, 2016 and will expire on June 30, 2021. A copy of the permit was. not available during the inspection. Please make sure that the operator has a copy of the most recent permit with his records. 2. Self -Monitoring Program' The Discharge Monitoring Reports (DMRs) were reviewed for the period February 2017 through March 2018. There were limit violations April, May, and October 2017, and they are summarized in an attached list. These violations were addressed in separate correspondence from this office. All sampling during this time appears to have been performed per the frequencies specified in the permit. A 3. Flow Measurement The permit requires weekly instantaneous flow monitoring. The effluent flow is manually measured using the v -notch weir in the contact chamber. 4. Sludge Handling and Disposal Solids are removed approximately every 6 weeks from the in -ground digester by Carolina Septic Tank Company. The owner maintains the receipts from these services. **5. Operations and Maintenance This treatment system is showing significant signs of age and wear. The ladder to climb on top of the treatment system is severely rusted and potentially unsafe for the operator and inspector. The walkway is also severely rusted. The in -ground digester appears to be caving in to some degree. The bar screen fell off the system at some point and has not been replaced, so the operator manually removes solids. These issues should be addressed soon before they impact treatment. ­��'"Nothing Compares;r-._.,.v State of North Carolina i Environmental Quality 450 W. Hanes Mill Road, Suite 300, Winston-Salem, North Carolina 27105 Phone: 336-776-98001 FAX: 336-776-9797 6. Facilitv Site Review The existing wastewater treatment system consists of the following: a single -train aboveground package plant with flow splitter box (split between aeration basin and influent pump station to control the flow), aeration basin, secondary clarifier, tablet chlorinator box (no tubes), contact chamber, tablet dechlorination tubes and effluent discharge pipe. The old in -ground package plant is used for sludge holding and is not aerated. 6. Records/Reports A review of the operator's logs indicated that records are being maintained according to the permit. A comparison of the September 2017 DMR with the corresponding operator records and certified laboratory data sheets from Pace Analytical showed that all values were properly transcribed onto the DMR. 7. Effluent/Receiving Waters The system discharges into Little Alamance Creek, classified WS -IV NSW waters in the Cape Fear River Basin. The effluent was observed to be clear during the inspection. Should you have any questions concerning this report, please contact Jenny Graznak or me at (336) 776-9800. Sincerely, Id >10­r%Z4,v� �_ 14t? Sherri V. Knight, P.E. Regional Supervisor Water Quality Regional Operations Section Division of Water Resources cc: Paul Smith (smithindustriegbellsouth.net) Central Files 019M. ,;WE WSRO Attachments: Inspection Checklist Monitoring Report Violations list United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 I 3 I NCO022098 I11 12 18/05/23 17 181,•1 19I G I 201 211 1 1111I11111IIIIIIIIIIIIIIIIIIIIIIIIIIIIII�6 Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA Reserved 67 70 LJ 7 I 72 .ti 73 I 174 751 I I I I I 180 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 11:00AM 18/05/23 16/10/01 Cranbrook Village Community 4309 Liberty Rd Exit Time/Date Permit Expiration Date Greensboro NC 27406 12:OOPM 18/05/23 21/06/30 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data /// Paul Matthew Smith/ORC/336-932-9347/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Paul Smith,4309 Old Liberty PI Greensboro NC 27407//336-932-9347/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit N Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program E Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date / Jennifer F Graznak , / WSRO WQ//336-771-5000/ S/ •Za/Z�� Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date 1, EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type (Cont.) 31 NCo022098 111 121 18/05/23 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) 1. Permit The current permit became effective October 1, 2016 and will expire on June 30, 2021. A copy of the permit was not available during the inspection. Please make sure that the operator has a copy of the most recent permit with his records. 2. Self -Monitoring Program The Discharge Monitoring Reports (DMRs) were reviewed for the period February 2017 through March 2018. There were limit violations April, May, and October 2017, and they are summarized in an attached list. These violations were addressed in separate correspondence from this office. All sampling during this time appears to have been performed per the frequencies specified in the permit. 3. Flow Measurement The permit requires weekly instantaneous flow monitoring. The effluent flow is manually measured using the v -notch weir in the contact chamber. 4. Sludge Handling and Disposal Solids are removed approximately every 6 weeks from the in -ground digester by Carolina Septic Tank Company. The owner maintains the receipts from these services. **5. Operations and Maintenance This treatment system is showing significant signs of age and wear. The ladder to climb on top of the treatment system is severely rusted and potentially unsafe for the operator and inspector. The walkway is also severely rusted. The in -ground digester appears to be caving in to some degree. The bar screen fell off the system at some point and has not been replaced, so the operator manually removes solids. These issues should be addressed soon before they impact treatment. 6. Facility Site Review The existing wastewater treatment system consists of the following: a single -train aboveground package plant with flow splitter box (split between aeration basin and influent pump station to control the flow), aeration basin, secondary clarifier, tablet chlorinator box (no tubes), contact chamber, tablet dechlorination tubes and effluent discharge pipe. The old in -ground package plant is used for sludge holding and is not aerated. 6. Records/Reports A review of the operator's logs indicated that records are being maintained according to the permit. A comparison of the September 2017 DMR with the corresponding operator records and certified laboratory data sheets from Pace Analytical showed that all values were properly transcribed onto the DMR. 7. Effluent/Receiving Waters The system discharges into Little Alamance Creek, classified WS -IV NSW waters in the Cape Fear River Basin, The effluent was observed to be clear during the inspection. Page# Permit: NCO022098 Inspection Date: 05123/2018 Owner - Facility: Cranbrook Village Community Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable M ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The treatment system and in -ground sludge holding tank are operational. However, please note that this entire system is severely deteriorated and needs repair. Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ E ❑ ❑ application? 0 ❑ ❑ ❑ Is the facility as described in the permit? M ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ E ❑ ❑ Is access to the plant site restricted to the general public? E ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? M ❑ ❑ ❑ Comment: A copy of the permit was not available during the inspection. Please make sure that the operator has a copy of the most recent permit with his records. Results of analysis and calibration Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? M ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? M ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? M ❑ ❑ ❑ Is the chain -of -custody complete? M ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ E ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? M ❑ ❑ ❑ Page# 3 Permit: NCO022098 Owner - Facility: Cranbrook Village Community Inspection Date: 05/23/2018 Inspection Type: Compliance Evaluation Record Keepina Yes No NA NE Is a copy of the current NPDES permit available on site? ❑ E ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: A comparison of the September 2017 DMR with the corresponding operator records and Yes No NA NE Is the clarifier free of black and odorous wastewater? certified laboratory data sheets from Pace Analytical showed that all values were properly ❑ ❑ transcribed onto the DMR. ❑ ❑ 0 Aeration Basins Yes No NA NE Mode of operation Ext. Air ❑ ❑ Type of aeration system Diffused ❑ ❑ Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Are the diffusers operational? E ❑ ❑ ❑ Is the foam the proper color for the treatment process? E ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? N ❑ ❑ ❑ Is the DO level acceptable? ❑ ❑ ❑ N Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑ 0 Comment: Two blowers Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? N ❑ ❑ ❑ Is the site free of weir blockage? E ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? ■ ❑ ❑ ❑ Is the site free of excessive floating sludge? N ❑ ❑ ❑ Is the drive unit operational? E ❑ ❑ ❑ Is the return rate acceptable (low turbulence)? N ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? N ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately Y, of the sidewall depth) ❑ ❑ ❑ 0 Comment: Single clarifier with one weir trough Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? ❑ 0 ❑ ❑ Page# 4 Permit: NCO022098 Inspection Date: 05/23/2018 Owner - Facility: Cranbrook Village Community Inspection Type: Compliance Evaluation Disinfection -Tablet Yes No NA NE Are the tablets the proper size and type? 0 ❑ ❑ ❑ Number of tubes in use? 0 Is the level of chlorine residual acceptable? E ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ 0 ❑ Comment: There are no chlorinator tubes Tablets are placed in the clarifier weir trough and in the bottom of the chlorinator box. De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ N ❑ Is storage appropriate for cylinders? ❑ ❑ 0 ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ N ❑ Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? S ❑ ❑ ❑ Number of tubes in use? 2 Comment: The dechlorination unit is attached to the outside of the package plant. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? E ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? N ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ N ❑ Comment: The plant discharges into Little Alamance Creek. Page# 5 MONITORING REPORT(MR) VIOLATIONS for: Report Date: 05/21/18 Page: 1 of 1 PERMIT: NCO022098 FACILITY: NC Land Lease LLC - Cranbrook Village Community COUNTY: Guilford REGION: Winston-Salem Limit Violation MONITORING OUTFALL/ VIOLATION UNIT OF CALCULATED REPORT PPI LOCATION PARAMETER DATE FREQUENCY MEASURE LIMIT VALUE Over VIOLATION TYPE VIOLATION ACTION 04-2017 001 Effluent Coliform, Fecal MF, MFC 04/04/17 Weekly #/100ml 400 1,410 252.5 Daily Maximum Proceed to NOV Broth, 44.5 C Exceeded 04-2017 001 Effluent Nitrogen, Ammonia Total (as 04/12/17 Weekly mg/I 19 24.1 26.8 Daily Maximum Proceed to NOV N) - Concentration Exceeded 04-2017 001 Effluent Nitrogen, Ammonia Total (as 04/19/17 Weekly mg/I 19 31.6 66.3 Daily Maximum Proceed to NOV N) - Concentration Exceeded 04-2017 001 Effluent Nitrogen, Ammonia Total (as 04/30/17 Weekly mg/I 3.8 9.8 158.0 Monthly Average Proceed to NOV N) - Concentration Exceeded 05-2017 001 Effluent Nitrogen, Ammonia Total (as 05/17/17 Weekly mg/I 19 25.4 33.7 Daily Maximum Proceed to NOV N) - Concentration Exceeded 05-2017 001 Effluent Nitrogen, Ammonia Total (as 05/23/17 Weekly mg/I 19 30.4 60 Daily Maximum Proceed to NOV N) - Concentration Exceeded 05-2017 001 Effluent Nitrogen, Ammonia Total (as 05/31/17 Weekly mg/I 3.8 4.5 18.4 Monthly Average Proceed to NOV N) - Concentration Exceeded 10-2017 001 Effluent Nitrogen, Ammonia Total (as 10/02/17 Weekly mg/I 19 19.5 2.6 Daily Maximum Proceed to NOD N) - Concentration Exceeded Monitoring Violation MONITORING OUTFALL/ PARAMETER VIOLATION FREQUENCY UNIT OF LIMIT CALCULATED % VIOLATION TYPE VIOLATION ACTION PrPnPT PPI .LOCATION DATE MEASURE VALUE Over 03-2018 001 Effluent Chlorine, Total Residual 03/31/18 2 X week ug/I Frequency Violation None