HomeMy WebLinkAboutWQCSD0244_Compliance Evaluation Inspection_20180503 tirq, `a j. et. V ROY COOPER eAt 3 24 Governor � '� MICHAEL S.REGAN p .e Seel Clark Water Resources LINDA CULPEPPER Envnoumental Quality Interim Director May 3, 2018 Mr. Steve Harrell Area Manager,Utilities Inc. 315 B Hwy. 70 East Gamer,NC 27529 Subject: Compliance Evaluation Inspection Ashley Hills Collection System Collection System Permit Number WQCSD0244 Wake County Dear Mr. Harrell, Jeremiah Dow of the Raleigh Regional Office conducted a compliance evaluation inspection on May 3, 2018. The assistance of Mr. Wayne Leary and Mr. Brandon Baldwin was greatly appreciated. Please find the attached Basin Wide Information Management System(BIMS) inspection checklist summarizing the inspection. During the inspection, the following items were noted: 1. Carolina Water Service, Inc. of North Carolina operates a deemed collection system pursuant to 15 NCAC .02T .0403 that collects wastewater from six (6) nearby subdivisions for treatment at the Ashley Hills WWTP. 2. The system includes five (5) duplex pump stations, approximately ten(10) miles of gravity collection line, approximately three (3)miles of force main, high priority lines, and 337 manholes. All pump stations had telemetry, and four(4) of five(5)pump stations had standby emergency generators. 3. Pump station weekly inspections and logbooks are being maintained as required. The Amber Acres, Amber Ridge, Bishop Point#1, and Bishop Point#2 pump stations were observed during the inspection. The system appeared to be well maintained. The visual alarm at the Amber Ridge pump station did not work, and should be repaired as soon as possible. A significant amount of grease was observed in all wet wells observed. Mr. Leary stated that they clean the pump stations every quarter with additional cleaning as needed. `� ' t�lotllin Compares .__ State of North Carolina I Environmental Quality I Water Resouices I Raleigh Regional Office 1628 Mail service Center I Raleigh,North Carolina 27699-1628 9 1` 1 9 7 - - - o-Y „s.,,r�-t-a;a- n "a � �n`�'s, i .. __ 4. The aerial line at Amber Ridge was observed. The right of way was adequately maintained and there were no visible signs of damage. The aerial line is only used in cases of emergency. Flow to the Amber Ridge pump station can be diverted through the aerial line to the Amber Acres station. 5. Manhole#AR1 was inspected. No blockages or significant grease accumulation was observed. 6. A review of the records indicates the following: a) A map of the system is actively maintained depicting manholes, pump station locations,right of ways, high priority lines, line size, and tracking for line cleaning. b) Records are maintained for the facility's spare parts inventory, annual system observation,high priority line inspections, and cleaning. Mr. Leary stated that they clean ten(10) percent of the line per subdivision per year. An overflow response plan is kept on site and readily available for viewing. c) Grease control educational materials are distributed bi-annually as required with utility bills. Mr. Leary stated that the grease control educational information is posted to their website as well. If you have any questions about this inspection or this letter, please contact Jeremiah Dow at jeremiah.dow@ncdenr.gov or 919-791-4248. f i S•ferely, Danny Smith Water Quality Regional Operations Raleigh Regional Office cc: Central Files RRO File Bryce Mendenhall,Vice President, Carolina Water Service Inc. of NC,PO Box 240908, Charlotte NC 28224 Compliance Inspection Report Permit. WQCSD0244 Effective: 01/23/07 Expiration: Owner• Carolina Water Service Inc of North Carolina SOC: Effective: Expiration. Facility. Ashley Hills WWTP County:Wake 320 Woods Run Rd Region. Raleigh Knightdale NC 27545 Contact Person: Matthew Klein Title. President Phone. 704-525-7990 Directions to Facility. System Classifications: Primary ORC. Certification. Phone: Secondary ORC(s). On-Site Representative(s): Related Permits. Inspection Date• 05/03/2018 Entry TiTi//me 09 5 AM Exit Time: 11.16AM Primary Inspector Jeremiah J Dow r t....."----- 5/3/f$' Phone: 919-791-4248 Secondary Inspector(s)• Reason for Inspection Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: Compliant 0 Not Compliant Question Areas: J Miscellaneous Questions El Performance Standards El Operation&Maint Reqmts El Records El Monitoring&Rpting Reqmts FE Inspections Pump Station ® Manhole kti Lines (See attachment summary) Page. 1 Permit WQCSD0244 Owner-Facili?y•Carolina Water Service Inc of North Carolina Inspection Date. 05/03/2018 Inspection Type:Collection System Inspect Non Sampling Reason for Visit. Routine Inspection Summary Page• 2 Permit. WQCSD0244 Owner-Facility.Carolina Water Service Inc of North Carolina Inspection Date 05/03/2018 Inspection Type:Collection System Inspect Non Sampling Reason for Visit. Routine Performance Standards Yes No NA NE Is Public Education Program for grease established and documented'? )( 000 What educational tools are used'? Grease education materials are sent out twice per year with customers'sewer bills The grease education materials are also posted to the company's website Is Sewer Use Ordinance/Legal Authority available'? 000 Does it appear that the Sewer Use Ordinance is enforced? Is Grease Trap Ordinance available? 0 0 0 Is Septic Tank Ordinance available(as applicable,i.e.annexation) 000 List enforcement actions by permittee,if any,in the last 12 months Has an acceptable Capital Improvement Plan(CIP)been implemented? 00 0 Does CIP address short term needs and long term\"master plan\"concepts'? 00 ' 0 Does CIP cover three to five year period? 0 0 ' # 0 Does CIP include Goal Statement'? 0 0 ¢ 0 Does CIP include description of project area? 0 ❑ 0 Does CIP include description of existing facilities'? 0 ❑ 0 Does CIP include known deficiencies'? 00 0 Does CIP include forecasted future needs? 00 0 Is CIP designated only for wastewater collection and treatment'? 00 0 Approximate capital improvement budget for collection system'? Total annual revenue for wastewater collection and treatment'? CIP Comments Deemed system so CIP is not required Is system free of known points of bypass'? 000 r If no,describe type of bypass and location Is a 24-hour notification sign posted at ALL pump stations'? El 000 #Does the sign include Instructions for notification'? 000 Pump station identifier? ti000 24-hour contact numbers 000 If no,list deficient pump stations #Do ALL pump stations have an"auto polling"feature/SCADA? 00 10 Number of pump stations 5 Number of pump stations that have SCADA 0 Number of pump stations that have simple telemetry 5 Number of pump stations that have only audible and visual alarms 0 Page' 3 ® W ❑ ❑ ❑ ❑ .• 0000 W ❑ ❑ ❑ ❑ 000000000 0 Z ❑ ❑ ❑ 00000 a ❑ ❑ ❑ DO 0000 ❑ 0CO z ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ . 000 ❑ ❑ , 000000000 cc 0 CD >- 0 . N_ w C 0 0 a) 0 EL I C S O OCDN 0 C_ 'j U aj -o I r o o in I m to Z c a) `o Z co a i> E x a) a) II x cri a) c- 0 o y c n l0 O N L O O @ U U CO -0 N u) . C1 -.S r- N r. > • O U o. co w o m r c E E o_ a) a. a a, a) >o m = x 0 E E r ° O C !!! C @ a) O T 2 N O '6,- E y o E c N d U a) i O -a N @ N U a) a C �, a> @ C 0 E o m N o (° a C C,. N >. 7 a) c C E J, O c ca `cr I o. m c rNm CO " 0 -s° a) n- E g r @ @ N r C C N -� a) E C Q @ C r Y6 L @ °- '5 -_ r @ C C a N Q7 N 0 °- @ 0 @ a) 'U E t _o 0 c o o @ N -_>. cc 0 E > ° a) a 0 > c c v E m m 4 c"o o `o_ ;n °o c `—° c t Z > @ m 0 -o 0- co > N @ N c c0a 3 U U d a) N O > m U N ° @ a N yL--, _° C (0 a @ 0_ o a N C a) -c a) @ N o @ N c r '0 X U N ,C a) C as C E o c a E. @ E0 of °) as a -`o a c E 2, o aa) a c 0 0 a) al — �' c • E a 0 c 2 E -° a) ° o - > N -0 ° a) -0 a) • c E a) = n D @ c 0 = Y as c E m E c m a c o o N @ cu 0 0 C 0 a) a) •Q 0_ a) 0 O a) N °O O 0) a a) a) > E @ a L Co@ a m C C N o0 0 3 E n a E ° o E o _a N o- N an m m a Z E °) CC m a.) a c 00 �_ E N v o 5 m o a) o @ > o o N °o S 0) _0) E 0- 0 0 -No E , c ° U M w @ r �O o N O . 0 - a a) O a) 0 N N @ N N co T 0 E m@ of N N > N -- co N @ N Cr) 0 @ 1] @ > LO "NOL U i (� °) Q -O m J, V E o c @ C -° .L-. a) _c E L .c N @ N a O C .N a) X L vi co N N d CO O L0 m o io N E 0 a) E c a D c > ,. a) ' e .R o 4 -0 -0 E c _� ° o `° >, y N N @ O N N co @ > '(6 y N N a) N -6 0 a C @ 0 a) N C o N c N N a 0- o +a) @ CO a) @ 2 Y o 2 L U E L o O c6 @ @ N 0 N N O N O m a a° E a) a > o 0 >@ > -0 > a, . ao o N o- u°) _ a) v) 0 -o c) 2 E' aa)) c 3 " N w >, Ti a aa„-- -;--: 1E .. I c C N Q 0 N t N N Q C C .o N N d @ N @ o 0 0 .0. O E @ @ N L a 0 CO C I a) -O 0 cn 12 a`) -O a) a) O SD 0- N Y c 0 a 0 a) m a) @ C N ru E •0 c ° L-. '0 a) a) ., C O 0 C 00 o -c OU a) E +. O N .c N .F U N 5 N a 0. a N c6 L >, @ @ , U a) N N EV @ U U O > L @ 0 C c C C a) E N a o > t, E 0 E 2 to c m o @ ° N E a) ° m a) >� ° @ @cL O. 2 ) >L a a> E 0 w a) 0 N 2 2 2 2 N 0 2 N @ ° > < N > N < ¢ < = > Q N z it t 0 0 ¢ ¢ ¢ ¢ ¢ It ¢ I 0 0 < 4k D D g, n * 3 C �, m o > > 73 C7 m F 0 (7' ^ m m CD o a ° o ° ° m m o ° m v o ° m m Z D -n m m o a m o D m cn m cn CO > D mn 0 O' '00 O 3 O 3 `C S 3 3 _° O N N N- a' °' n N Q. D N "O O O O O .L] Cl) coN -O m c c' C' c CD s 7 m CD �- _° co -0 0• o '0 0 to (D v — n m N -o -o ° N =7- ,7 y c 7 NO ., 7 (D -0 30 .0 N (� X Q' 0 0 N 0 ° W n Q CD CD ( O< 7 O N N 7 'O • 'O O_ O w O 7 N m m o m CD 0 ° v o m 0 m m 0 3 7-- o o m o n a m ° o o ° • P» n (D 3 N c7 C' O O O 0' O N N d O O N O O — 7 O • v Mt m c a —I 3 n o. 7 m - -0 7 7 in ? N v 7 cn o m _ ° m N m m m N v m FD.- _ 7 v ° ° ° 5 a' 0 m 7 a' c m m 3 0- °- Cl S ° a ° a m m c3 ° m 0 m o m m 7. (DO' ❑' 01 O. 3 7 0 7 0 CO '0 -0 0 C1I ° N 7 O O N c0 0 j" (D (D o ° O a n ° O O N 3 O o O a0i 57 N ° Q '30 "00 -t°ii co v �. N 0' co ° 7 (n ,. `G 7 _p 0 S 7 "' IJ < o v c m o _° N h O O X (D o N O co N Cn 0' -0 0 7 o O -0 (p N W Cn ° m 0 30 m J CO ° c cn m a 3 ° 0 CD m Fo- iv o coittC fD r ; i 2 J * N CD _ O O J O N d S_ 0 o co -a7 co O d ° O ,z 0 07 ' cn - 3 d N v O 0' m 7• n' 6' = O Q• 3 0' O 0' C S O CD "O 7 CD 0 o CD 0- 3 a CD 0. .v 7 Q O O 3 07 O O 3 — CD CO O a iir5 a N cn Q NCD a S N co 'o f Cn < CD O_ N O. CO CCD .O. ° 3 < a' co o1' .p 0 • O 0' u N -I m w 0- CD 7 m .< 2. i O O S OF-DJ J 3 3 O A K co lo -0 OF J C) C) O m J ❑. I N o m va m m O N 7 3 o J j N CD0 CD O 7 O Z O O 7 Z 0 o o a. 3 a- -o C) m CD o . a' . c m m co O O N o 9.3 CC ❑ ❑ ❑ Z 0 ❑ ❑ ❑ ❑ ❑ ❑ ❑ CI CI ^'a+ CI ElZ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ CD CD EN ❑ ❑ z 0 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ •f ❑ ❑ ❑ Z ❑❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ® ❑ m 0 0 0 0 0 0 0 0 ❑ ❑ ❑ ❑ ❑ m 0 0 0 0 0 0 0 0 0 0 , , Permit WQCSD0244 Owner-Facility.Carolina Water Service Inc of North Carolina Inspection Date. 05/03/2018 Inspection Type:Collection System Inspect Non Sampling Reason for Visit. Routine #Is permittee compliant with all compliance schedules in the permits? 0 0 'i 0 If no,which one(s)? Comment* AMBER ACRES LIFT ST. - Pump Station Yes No NA NE Pump station type —, '--_ ..._-. _______.___�_�_____.___�_�A—__—__._._..__.—Duplex --- Are pump station logs available? 0 0 0 Is it accessible in all weather conditions? 0 ❑ ❑ #Is general housekeeping acceptable? 0 0 0 Are all pumps present? 0 0 0 Are all pumps operable? El 0 0 0 Are wet wells free of excessive debris? 0 0 0 Are upstream manholes free of excessive debris/signs of overflow? 0 0 0 Are floats/controls for pumps/alarms operable? A. 0 ❑ 0 Is"auto polling"feature/SCADA present? 0 0 0 0 Is"auto polling"feature/SCADA operational? 0 0 0 Is simple telemetry present? 0 0 0 Is simple telemetry operational? ) 0 0 0 Are audio and visual alarms present? ta 0 0 0 Are audio and visual alarms operable? V 0 0 0 Is the Pump station inspected as required? 0 0 0 Are backflow devices in place? 0 0 0 Are backflow devices operable? 0 0 0 Are air relief valves in place? 0 0 0 Are air relief valves operable? 0 0 0 # Is an emergency generator available? 0 0 0 Can the emergency generator run the pumps? ag 0 0 0 Is the pump station equipped for quick hook-up? ❑ 0 a 0 Is the generator operable? ® 0 0 0 #Is fuel in tank and sufficient? au 0 0 ❑ Is the generator inspected according to their schedule? Ell 0 0 0 Is a 24-hour notification sign posted? ® 0 0 ❑ Does it include' Instructions for notification? El 0 ❑ 0 Pump station identifier? ® 0 0 0 Emergency phone number EZ 0 0 0 Page 6 000 • W DDDDDDDDDDDDDDDDDDDDD 000 z 000000000 000000001:1000E1111 ❑ ❑ G 000 0 x 00000E10000000 — ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ as o FA CD N -1:3 a3 w Y N O o K • a) 0 E U 0 m c O c_ O U a o to Z c O O Z 7 U COC U U N E C • CO a E N• Tu) a) PL O cco O • o m o 2 U 0 c N a, N • � C7 m 3 ao LL c Cfl `C O CD (3) ; o c 0 • 3 H4 CO o O c L c c N co N 0) a -o .c N c, 3 a) d- -- N cs Q Y U 0 U) o C E 0 N C- C 0" � (6 � -(:),„ m �• � a L _3 O E N C a N a) Y .0 `c 7 L N C > o w 0 a) .O .L.. U 0) > a) C a) U) v)) 0 a) a) N C cr O C O a O U O O a) C - o > an c ✓ s 0' p .' fn a 0 X E a O N 0 ` O O -- a) CV CO a N ) C` C 0- •O a) N &) N u) �O a N 0 0 `+- o o U) a) "- , < < (` 2 n a a` c- o a) a) 0 0 cO N 0 a E •E o I-: 8 > 0 � 0 0 a) a 0 v a) . c C- 2 a 2 a U c`" E m 2O c o N ca ca 0 a Q Q . O W co O U a) Q) O `a) C c a3 c C! o i m L w 0 0 c — E E 0 m 0 .Q c a) F a` a) o) o C` > 0 .n • 0 m a)° o c 0 coco N az `m `m n a a 0) T °' 0 0 o 0 2 a3 _I :i V 3 0 N N a) n a) 2 O 0_ @ a3 m 0 a >, U C a7 c U O • a; o (9 E J cn _ a) c O O .2 w n O C N N C O U 2 O N a) )6 a) r--. n i O Y a) (0 p _C 0 0 m N C a) a a3 d o E W m c v0 aai Q o m �0 2 2 w w 0 >cT) > a) a) rn E' • oa a C U O a _ - > > as - Q) a o 0 o o 0 a - g a) 0 N- 0 ` E 0) o) E E ->0 > g -o a > o E 0- 0 0 0 ii o n O c ca _ t a n w E O c c a) a) c c 3 3 aE) 0 E ' R 0 0 c c, 0 0 m a E c cr w° o - E E a) 0 0 •o a) a) as as 0- 0 0 a) `U) 0 n m a`) J c c a 0 N y E a)) o a o 3 m a n °' m a 0-a ' o �) m o m c aci r = n c W c 0 aa)) — — m a o ° ° 0- a c c a m m N m n a) v aa) a a) 2 E m a 0- a a) a) m m 3 7 c m m E E m m a) _a 9 m m U 9 m ? 0 N 0 a n r 2 0 = c 2 '' N a) a a) a) a) _ = 0 0 2 2 S 2 2 2 2 w w S a) 0 N a 0 Q a a. a It a < a a a 9 9 9 N a < N a . . a` CO # 0) N E # > > > > z > > E — — E > > > > > # E > -0 -0 _ / > 7 — — E o / / § \ \ c - C } Ea - ( -0 j ] I ] } / m -u s CD - - \ m / - - o \ \ / ) [ 2 0 \ : 21 ) f ® j } - _ \ 0 _ { 0 0 ) § \ ED_ \ } \ \ o a 3 3 i % o ( -0 / g \1 \ ° - 15 } j 0 \ \ < } 3 / \ / - / ' / / ` ¥ = j / } / 2 m _ - » ® § CD / / \ 2 2 - ° f o 5 -0 3 o / / \ _ $ { \ § j \ \ E o = E / \ & ® / # ° % e ] 2 « r ,-0co - * f c j j ( g > > 5 { k § \ c k \ $ 2 a c o 7 Q ° 0 § ° ° \ 0 CL ° Q > \ - a » \ O o 2 e ) k ` ° j 2 ( / / ƒ CU ; +cr cu _ \ g Cl) 3 o� / a \ ° § 0 \ % % Cl) \ \ \ \ ° ° CD CD 0 \ / _ — _ & a \ § ° CD 0- 0 - » S . _ (a f ' / ? $ / 0 / \ \ / \ e m : E � f _ . I 0 0 SD 8 ( \ \ j q \ \ / 0 . 1 } 3 ƒ / i . cn \ ! co 5 CT i o & y R J ° } J o q \ / 5 o \ \ ! cu SD m 1 _ DJ ( c)ƒ \ 7 G \ . k - ® M O ❑ E3 4 ❑ ❑ ❑ EI 2 El El Et M A El % 2 \ / \ / ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ^ \ 1:100000 ; } CD ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ DD ❑ ❑ ❑ ❑ ❑ ❑ › U ❑ ❑ ❑ ❑ ❑ 011:11210E1 g. A g ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ El 0 ❑ ❑ ❑ ❑ Permit WQCSD0244 Owner-Facility.Carolina Water Service Inc of North Carolina Inspection Date. 05/03/2018 Inspection Type.Collection System Inspect Non Sampling Reason for Visit Routine Is the generator inspected according to their schedule'? 0 0 0 Is a 24-hour notification sign posted? •& 0 0 0 Does it include Instructions for notification? 0 ❑ ❑ Pump station identifier? • 000 Emergency phone number 0 0 0 Is public access limited? 0 0 0 Is pump station free of overflow piping? ® 0 U 0 Is the pump station free of signs of overflow? EN 0 0 0 Are run times comparable for multiple pumps? Yes Comment: Pump runtimes were 6,089 and 7,184. BISHOP POINT#1 - Pump Station Yes No NA NE Pump station type Duplex Are pump station logs available? 0 0 0 Is it accessible in all weather conditions? 0 0 0 #Is general housekeeping acceptable? LE 0 0 0 Are all pumps present? 0 0 0 Are all pumps operable? # ❑ 0 0 Are wet wells free of excessive debris? 0 0 0 Are upstream manholes free of excessive debris/signs of overflow? Are floats/controls for pumps/alarms operable? Efi 0 0 0 Is"auto polling"feature/SCADA present? 0 ❑ 0 Is"auto polling"feature/SCADA operational? 0 0 0 Is simple telemetry present? ® 0 El 0 Is simple telemetry operational? MOOD Are audio and visual alarms present? 1000 Are audio and visual alarms operable? ® 0 0 0 Is the Pump station Inspected as required? 0 0 0 Are backflow devices in place? U 0 0 Are backflow devices operable? 0 0 0 ;l Are air relief valves in place? 0 0 0 Are air relief valves operable? 0 0 0 # Is an emergency generator available? MOOD Can the emergency generator run the pumps? ri 0 0 0 Is the pump station equipped for quick hook-up? E U U Page. 9 Permit WQCSD0244 Owner-Facility Carolina Water Service Inc of North Carolina Inspection Date 05/03/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit. Routine Is the generator operable? ❑ ❑ 0 #Is fuel in tank and sufficient? 0 ❑ ❑ Is the generator inspected according to their schedule? ❑ ❑ ❑ El Is a 24-hour notification sign posted? . ❑ 0 0 Does it include Instructions for notification? -0-D-0------ Pump station identifier? EU El ❑ ❑ Emergency phone number El El El Is public access limited? El ❑ ❑ Is pump station free of overflow piping? • ❑ ❑ ❑ Is the pump station free of signs of overflow? El 0 ❑ Are run times comparable for multiple pumps? Yes Comment. Pump runtimes were 140117 and 202209. This is the smallest pump station and the only pump station without a permanent on site emergency generator The station is equipped for quick hookup. Significant grease accumulation observed in wet well AMBER RIDGE LINE - Lines/Right-of-Ways/Aerie) Lines Yes No NA NE Is right-of-way accessible for emergency? 12 ❑ 0 ❑ Is right-of-way free of sinkholes or depressions? Ef2 ❑ ❑ ❑ Is line/nght-of-way free of evidence of leakage? El ❑ ❑ #Are there areas of exposed line? El ❑ 0 #Is any exposed line constructed of ductile iron or other approved material? ❑ El ❑ Are water crossing and supports in good condition? m ❑ ❑ ❑ #Is right-of-way free of non-utility motorized traffic? ❑ ❑ ❑ Is line free of visible damage? El ❑ El ❑ #Are there siphons in this system? ❑ ❑ ❑ If yes,are they maintained and documented? Comment. High priority line at Amber Ridge is largest hich priority line in the system The aerial line is 10'to 12'off the ground and crosses a stream The line is no longer used regularly, but is maintained as an emergency bypass of the Amber Ridge Lift Station Flow can be diverted from Amber Ridge to the Amber Acres station. MANHOLE#AR1 - Manhole Yes No NA NE Is manhole accessible? e ❑ I=1- # #Is manhole cover/vent above grade? El ❑ El ❑ Is the manhole free of visible signs of overflow? El 0 ❑ ❑ Is the manhole free of sinkholes and depressions? E2 ❑ El El Page: 10 Permit WQCSD0244 Owner-Facility:Carolina Water Service Inc of North Carolina Inspection Date. 05/03/2018 Inspection Type•Collection System Inspect Non Sampling Reason for Visit. Routine Is manhole cover present? 0 0 0 #Is manhole properly seated'? ❑ 0 0 #Is manhole in good condition? 0 ❑ 0 #Is invert in good condition? I 0 0 0 Is line free-flowing and unrestricted in manhole? 0 0 0 Is manhole free of excessive amounts of grease'? 1, 0 ❑ 0 Is manhole free of excessive roots? s 0 0 ❑ Is manhole free of excessive sand'? 2.1 0 0 0 Is manhole's extended vent screened? 0 0 ❑ Are vents free of submergence'? ❑ ❑ ❑ Are manholes free of bypass structures or pipes? ' ❑ ❑ ❑ Comment: Invert was free of obstructions and relatively free of grease. Manhole is the junction for a bypass of Amber Ridge lift station through high priority line to Amber Acres in the event of an emergency. Page' 11