HomeMy WebLinkAboutWQ0040011_Application_20180518E May 15, 2018 Technical Memorandum To: Review Officer NCDEQ — Division of Water Resources — Asheville Regional Office 2090 US Highway 70 Swannanoa, NC 28778 From: Jeffrey T. Brown, PE President �r Cc: Josh Nickol General Manager RE: Hwy. 209 — I-40 Sewer Fast -Track Application (Pump Station) Haywood County, NC Attached please find the following documents: WQ0040011 1. Fast -Track Application (FTA 04-16) for a pumps at Richland Creek Pump Station 2. Flow tracking/Acceptance for Sewer Extension Application (FTSE 04-16) 3. An application fee Check in the amount of $480. Payable to NCDEQ 4. Site Map Purpose for Gravity Sewer Replacement: The purpose of the proposed project is to eliminate a confined space entry into a dry well by replacing the existing pumps with Gorman -Rupp suction lift pumps. The existing pump station serves businesses in the downtown Lake Junaluska area in the Junaluska Sanitary District. The project will not increase capacity at the existing pump station. Should you have any questions, please advise. 30 Ben Lippen School Road, Asheville, NC 28806 X828.350.7683 (office], 828.350.7684 [fax] , www, brown pa.net State of North Carolina `> WQ0040011 Department of Environmental Quality DWR w„ Division of Water Resources 15A NCAC 02T.0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION Division of Water Resources INSTRUCTIONS FOR FORM: FTA 04-16 & SUPPORTING DOCUMENTATION This application is for sewer extensions involving gravity sewers, pump stations and force mains, or any combination that has been certified by a professional engineer and the applicant that the project meets the requirements of 15A NCAC 02T and the Division's Minimum Design Criteria and that plans, specifications and supporting documents have been prepared in accordance with, 15A NCAC 02T, 15A NCAC 02T.0300, Division policies and Hood engineering practices. While no upfront engineering design documents are required for submittal, in accordance with 15A NCAC 02T .0305(b), design documents must be prepared prior to submittal of a fast track permit application to the Division. This would include plans, design calculations, and project specifications referenced in 15A NCAC 02T .0305 and the applicable minimum design criteria. These documents shall be available upon request by the Division. Projects that are deemed permitted (do not require a permit from the Division) are explained in 1 A NC 0303. nk,ry Projects not eligible for review via the fast track process (must be submitted for full technical r iew): /hn 'C R�® ➢ Projects that require an environmental assessment in accordance with 15A NCAC 1C 0100; °sovmr ➢ Projects that do not meet any part of the minimum design criteria (MDC) document; ➢ Projects that involve a variance from the requirements of 15A NCAC 2T; M�y % ➢ Pressure sewer systems utilizing septic tank -effluent pumps (STEPS) or simplex grdevs mps; ➢ STEP or simplex grinder pumps connecting to pressurized systems (e.g. force mai 01,0111, ➢ Vacuum sewer systems. Ashovift�oP10 General — When submitting an application, please use the following instructions as a checklist in order to ensure aller quired items are submitted. Adherence to these instructions and checking the provided boxes will help produce a quicker review time and reduce the amount of requested additional information. Failure to submit all required items will necessitate additional processing and review time, and may result in return of the application. Unless otherwise noted, the Applicant shall submit one original and one copy of the application and supporting documentation. A. One Original and One Copy of Application and Supporting Documents ® Required unless otherwise noted B. Cover Letter (Required for All Application Packages): M List all items included in the application package, as well as a brief description of the requested permitting action. ➢ Be specific as to the system type, number of homes served, flow allocation required, etc. ➢ If necessary for clarity, include attachments to the application form. C. Application Fee (All New and Major Modification Application Packages): ® Submit a check or money order in the amount of $480.00 dated within 90 days of application submittal. ➢ Payable to North Carolina Department of Environmental Quality (NCDEQ) D. Fast Track (Form: FTA 04-16) Application (Required for All Application Packages): ® Submit the completed and appropriately executed application. ➢ If necessary for clarity or due to space restrictions, attachments to the application may be made. ❑ If the Applicant Type in Item I.2 is a corporation or company, provide documentation it is registered for business with the North Carolina Secretary of State. ❑ If the Applicant Type in Item I.2 is a partnership or d/b/a, enclose a copy of the certificate filed with the Register of Deeds in the county of business. ® The Project Name in Item II.1 shall be consistent with the project name on the flow acceptance letters, agreements, etc. ® The Professional Engineer's Certification on Page 5 of the application shall be signed, sealed and dated by a North Carolina licensed Professional Engineer. ® The Applicant's Certification on Page 5 of the application shall be signed in accordance with 15A NCAC 02T .0106(b). Per 15A NCAC 02T .0106(c), an alternate person may be designated as the signing official if a delegation letter is provided from a person who meets the criteria in 15A NCAC 02T .0106(b). INSTRUCTIONS FOR FORM: FTA 04-16 & SUPPORTING DOCUMENTATION Pagel of 3 E. Flow Tracking/Acceptance Form (Form: FTSE 04-16) (If Applicable): ® Submit the completed and executed FTSE form from the owners of the downstream sewers and treatment facility. ➢ Multiple forms maybe required where the downstream sewer owner and wastewater treatment facility are different. ➢ The flow acceptance indicated in form FTSE must not expire prior to permit issuance and must be dated less than one year prior to the application date. ➢ Submittal of this application and form FTSE indicates that owner has adequate capacity and will not violate GS. 11419- 215.67(a). ➢ Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific FTSE. F. Site Maps (All Application Packages): ® Submit an 8.5 -inch x 11 -inch color copy of a USGS Topographic Map of sufficient scale to identify the entire project area and closest surface waters. ➢ Location of the project (gravity sewer, pump stations & force main) ➢ Downstream connection points and permit number (if known) for the receiving sewer N Include a street level map (aerial) showing general project area so that Division staff can easily locate it in the field. G. Existing Permit (All Modification Packages): ❑ Submit the most recently issued existing permit. ❑ Provide a list of any items within the permit the Applicant would like the Division to address during the permit modification (i.e., permit description, flow allocation, treatment facility, etc.). H. Power Reliability Plan (Required if portable reliability option utilized for Pump Station): ® Per 15A NCAC 02T .0305(h)(1), submit documentation of power reliability for pumping stations. ➢ This alternative is only available for average daily flows less than 15,000 gallons per day ➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant and is compatible with the station. The Division will accept a letter signed by the applicant (see 15A NCAC 02T .0106(b)) or proposed contractor, stating that "the portable power generation unit or portable, independently -powered pumping units, associated appurtenances and personnel are available for distribution and operation of this pump station." ➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided in the case of a multiple station power outage. (Required at time of certification) L Certificate of Public Convenience and Necessity (All Application Packages for Privately -Owned Public Utilities): ❑ Per 15A NCAC 02T .0115(a)(1) provide the Certificate of Public Convenience and Necessity from theNinitlhCluallma Utilities Commission demonstrating the Applicant is authorized to hold the utility franchise for the area to be served by the sewer extension, or ❑ Provide a letter from the North Carolina Utilities Commission's Water and Scwvr WwRArsm Flifi fiic Slff stating an application for a franchise has been received and that the service area is contiguous to an existing franchised area or that franchise approval is expected. J. Operational Agreements (Applications from HOA/POA and Developers for lots to be sold): ❑ Home/Property Owners' Associations ❑ Per 15A NCAC 02T.01 15(c), submit the properly executed Orall ons (IlN11::11)). ❑ Per 15A NCAC 02T.01 15(c), submit a copy of the Articles of Incorporation, Declarations and By-laws. ❑ Developers of lots to be sold ❑ Per 15A NCAC 02T.01 15(b), submit the properly executed Opera inial B Mmzmnd (11'iX1t: M EM). information, visit the Division's collection systems niwdiwkre MAY 15 2018 waver Llualiiy Regional opemilms I ASFP.Vi!i@ I?.nn!grp,l O{{Irg INSTRUCTIONS FOR FORM: FTA 04-16 & SUPPORTING DOCUMENTATION Page 2 of 3 State of North Carolina Department of Environmental Quality DWR,, Division of Water Resources n. 15A NCAC 02T.0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION Division of Water Resources r 04-16 & SUPPORTING DOCUMENTATION ApplicationNW completed by DWR) I. APPLICANT INFORMATION: 1. Applicant's name: Junaluska Sanitary District (company, municipality, HOA, utility, etc.) 2. Applicant type: ❑ Individual ❑ Corporation ❑ General Partnership ❑ Privately -Owned Public Utility ❑ Federal ❑ State/County ❑ Municipal ® Other 3. Signature authority's name: Josh Nickol per 15A NCAC 02T .0106(b) Title: General Manager/ CFO �l~ nrvsfon � �,y P Bil�'Q 4. Applicant's mailing address: Po Box 35 pasourcps City: Lake Junaluska State: NC Zip: 28745- MAY 5. Applicant's contact information: 1 5 ZOlB Phone number: 828) 452-1178 Email Address: inickol@'sdwater.ore 11'nter pull/iv RrgbAe! Ae Il. PROJECT INFORMATION: -� �naiQt" 1. Project name: Hwv 209 Sewer 2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project If a modification, provide the existing permit number: W000 and issued date: If new construction but part of a master plan, provide the existing permit number: WQ00 3. County where project is located: Haywood 4. Approximate Coordinates (Decimal Degrees): Latitude: 35.55060 Longitude: -82.9449° 5. Parcel ID (if applicable): 8627-68-8521 (or Parcel ID to closest downstream sewer) III. CONSULTANT INFORMATION: 1. Professional Engineer: Jeffrey T. Brown License Number: 28289 Firm: Brown Consultants, PA Mailing address: 30 Ben Lippert School Road City: Asheville State: NC Zip: 28806 - Phone number: 828) 350-7683 Email Address: jtrown e brown IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION: 1. Facility Name: Waynesville WWTP Permit Number: NCO025321 Owner Name: Waynesville V. RECEIVING DOWNSTREAM SEWER INFORMATION (if different than WWTF): 1. Permit Number(s): WQ Downstream (Receiving) Sewer Size: inch System Wide Collection System Permit Number(s) (if applicable): WQCS00182 Owner Name(s): Junaluska Sanitary District FORM: FTA 04-16 Page 1 of 5 VI. GENERAL REQUIREMENTS 1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached? ❑ Yes [-]No ®N/A 2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached? ❑ Yes ❑No ®N/A 3. If the Applicant is a Home/Pro��ty Owners' Association, has an Operational Agreement (FORM: HOA) been attached? ❑ Yes ❑No ®N/A 4. Origin of wastewater: (check all that apply): ❑ Residential Owned ❑ Retail (stores, centers, malls) ❑ Car Wash ❑ Residential Leased ® Retail with food preparation/service ❑ Hotel and/or Motels ® School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool /Clubhouse ❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash ❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment) 5. Nature of wastewater: 100 % Domestic/Commercial % Commercial Industrial (See 15A NCAC 02T.0103(20 ) "Is there a Pretreatment Program in effect? ® Yes ❑ No 6. Hasa flow reduction been approved under 15A NCAC 02T.01 14(f)? ❑ Yes ❑ No ➢ If yes, provide a copy of flow reduction approval letter 7. Summarize wastewater generated by project: Establishment Type (see 02T.0114(fl) Daily Design Flow °'b No. of Units Flow Riverbend School 1,200 gal/ 1 1200 GPD Sams Mart 2880 gal/ 1 2880 GPD Pilot Travel Center 5,400 gal/ 1 5400 GPD gal/ GPD gal/ GPD gal/ GPD To 9480 PD a See 15A NCAC 02T .0114(b), (d), (e)(1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas; and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined in G.S. 42A-4). b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01 141 shall be determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data. 8. Wastewater generated by project: 9480, PD (per 15A NCAC 02T.0114) ➢ Do not include future flows or previously permitted allocations If permitted flow is zero, indicate why: ❑ Pump Station or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line ❑ Flow has already been allocated in Permit Number: ❑ Rehabilitation or replacement of existing sewer with no new flow expected ❑ Other (Explain): FORM: FTA 04-16 MAY , r' 2018 Water QualityRegfonetOperaAfons I ASfev�'�x P^oional ('Kine Page 2 of 5 VII. GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T.030 & MDC (Gravity Sewers): 1. Summarize gravity sewer to be permitted: Size (inches) Length (feet) Material ➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria ➢ Section III contains information related to minimum slopes for gravity sewer(s) ➢ Oversizing lines to meet minimum slope requirement is not allowed and a violation of the MDC VIII. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains): COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT 1. Pump station number or name: Richland Creek Pump Station 2. Approximate Coordinates (Decimal Degrees): Latitude: 35.5506° Longitude: -82.9449° 3. Design flow of the pump station: .864 MGD millions gallons per day (firm capacity) 4. Operational point(s) of the pump(s): 10 gallons per minute at 81.1 feet total dynamic head (TDH) 5. Summarize the force main to be permitted (for this Pump Station): Size (inches) Length (feet) Material n/a 6. Power reliability in accordance with 15A NCAC 02T .0305(h)(1): ® Standby power source or pump with automatic activation and telemetry - 15A NCAC 02T .0305(h)(1)(B); ➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day ➢ Must be permanent to facility Or if the pump station has an average daily flow less than 15,000 gallons per day: ❑ Portable power source with manual activation, quick -connection receptacle and telemetry - 15A NCAC 02T .0305(h)(1)(C) or ❑ Portable pumping unit with plugged emergency pump connection and telemetry - 15A NCAC 02T .0305(h)(1)(C): ➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant (draft agreement) and is compatible with the station. ➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided in the case of a multiple station power outage. FORM: FTA 04-16 Page 3 of 5 IX. SETBACKS & SEPARATIONS — (02B.0200 & 15A NCAC 02T.0305(f)): 1. Does the project comply with all separations found in 15A NCAC 02T.0305(f) & (g) ® Yes ❑ No ➢ 15A NCAC 02T.0305(f) contains minimum separations that shall be provided for sewer systems: Setback Parameter* Separation Required Storm sewers and other utilities not listed below (vertical) 24 inches Water mains (vertical -water over sewer including in benched trenches) 18 inches Water mains (horizontal) 10 feet Reclaimed water lines (vertical - reclaimed over sewer) 18 inches Reclaimed water lines (horizontal - reclaimed over sewer) 2 feet **Any private or public water supply source, including any wells, WS -I waters of Class I or Class II impounded reservoirs used as a source of drinking water 100 feet **Waters classified WS (except WS -I or WS -V), B, SA, ORW, HQW, or SB from normal high water (or tide elevation) and wetlands (see item IX.2) 50 feet **Any other stream, lake, impoundment, or ground water lowering and ce drainage ditches 10 feet Any building foundation g�*36/nches t Any basement Katerqt Top slope of embankment or cuts of 2 feet or more vertical height t Drainages stems and interceptor drains St Any swimmingpools t Final earth grade (vertical) Any ➢ 15A NCAC 02T.0305(g) conta ns alternatives here separations in 02T.0305 f��� V�iev�d. p **Stream classifications can be identified usingthe Division's NC Surface Water Classy atiQn�s Vt. age ➢ If noncompliance with 02T.0305(f) or ( see Section X of this application 2. Does the project comply with separation requirements for wetlands? (50 feet of separation) ❑ Yes ❑ No ® N/A ➢ See the Division's draft separation requirements for situations where separation cannot be meet ➢ No variance is required if the alternative design criteria specified is utilized in design and construction ➢ As built documents should reference the location of areas effected 3. Does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .02009 ® Yes ❑ No ❑ N/A ➢ This would include Trout Buffered Streams per 15A NCAC 2B.0202 4. Does the project require coverage/authorization under a 404 Nationwide or [-]Yes ® No individual permits or 401 Water Quality Certifications? ➢ Information can be obtained from the 401 & Buffer Permitting Branch 5. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permits/certifications)? ® Yes ❑ No Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications are being prepared, have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and sedimentation control plans, stormwater management plans, etc.). 6. Does this project include any sewer collection lines that are deemed "high-priority?" Per 15A NCAC 02T.0402, "high-priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer. ❑ Yes ® No ❑ N/A ➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location). High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System -Wide Collection permit. FORM: FTA 04-16 Page 4 of 5 X. CERTIFICATIONS: 1. Does the submitted system comply with 15A NCAC 02T, the Minimum Design Criteria for the Permitting of Pump Stations and Force Mains (latest version), and the Gravity Sewer Minimum Design Criteria (latest version) as applicable? ® Yes ❑ No If No, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for review. Approval of the request is required prior to submittal of the Fast Track Application and supporting documents. 2. Professional Engineer's Certification: name from Application Item 111. 1.) attest that this application for has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the proposed design. NOTE — In accordance with General Statutes 143-215.6A and 143-215.613, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. A I, ration for has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non - discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water Resources should a condition of this permit be violated. I also understand that if all required parts of this application package are not completed and that if all required supporting information and attachments are not included, this application package will be returned to me as incomplete. NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. Signature: y Date: .5/451ZD78 FORM: FTA 04-16 Page 5 of 5 Get Maps I topoView Page 1 of 1 n 1 LIA QIV WP r Y i 4 _ 1-IOlAR4 I 1 .l fi , l Ole , p 1 a e , i � � I rF i e � (�1t,est'4laenP ��SSbiile+�' I MA I r,e I(i1� %AAQAf, POI} - J P Old_ClOe i ) � ads 'J '�Bq dya, ' Hosl➢,le i :nt �4a 1pv \ l I ' � •' Cs. ci I C 11 l` m� a,,5 kY A P 60 I_ .Ir'a'q�l V / 1 ell,il A D , Divlswn Water ReseureM Q�I jag I I NOW MAY T5.-2018 is :AIOS�&neee,...Pa�saeyleal mmlan I '%� � � � Water Quality Regional Opernlbnt https://iigmdb.usgs.gov/topoview/viewer/ Ashev-Ne ReTonai Office 4/2018 PROJECT: OWNER: ENGINEER: CONTRACTOR: DESCR[PTIONJ Jtjnaluska Sanitary District Pump Station Improvements -Richland Pump Station, Retrofit and Highway 209 Pump Statioa Retrofit Clyde; NC McGill Associates Blytheco Construction TWG)i(2,)))FaIWban ks.Wors& modWW' B5442 T,20 t verticaF dry pit n, onrclbg, sewag.8 pum- P9,41111cast, iron vwluta; linpelfbran& bearing framej, 4""1'259-flbrngjad dikhergo;-4,pamilically., balkneedArnpeller,. 316 stainless;steel wear rimgt% high, striera&t Ilist0aEs 1418ft'r,bronZa shaft,slee-v%.stqndbrd]doubIe, mechanical.* seal' (kwithi dead ifteaTdL-diftlitiarsystem)}.RL-xlb]L---,coupling i guard i drlVen)byr,25,,HFI,,1176SRPM' 2-8'4',VPZ'firam,e, stand8rdr�of,ftcit)nt:.motorwithWpliencibsur.eand Clas&F Insulation, � T!wo(R),.,:cefk,ff,led�n.on,Withess,pump hydrostatic tests Two ,,(,2).,oas,tiir,oniior,,stoetpump.,bases with separate suction elbow„ 4"'x:6!' swetio-welbaw andlelt-anout Spare parts4o.be one (1) o-ring/gasket kit. Four (',4),S5E)N0 5W, 'mercury float switches One, (1!) stainless steel float bracket MAY 15 2018 Water OtIRIM/ "99bnal C)peFWjc)rjs Regional I _qLlllLal (Iffce SHEET OF PROJECT: SUBJECT: 1'' c®1'7' BROWN CONSULTANTS, PA 30 Ben Lippen School Rd. Asheville, NC 28806 o: 828.350.7683 f: 828.350.7684 WORK BY: CHK'D BY: PROJECT #: DATE: 41t 6AM&I—fy 6)56) r-UTV?�g- &®o �®�^1 /45- Z� y pm C APAI, s f lo,5) 0 7v !d #5s 7 MAY 15 2018 Water oualitY Regional NC DENR-DIVISON OF WATER RESOURCES .0304 FRENCH BROAD RIVER BASIN 2B .0300 Name of Stream Description Class Class Date Index No. Pisgah Creek From source to East Fork Pigeon WS-III;Tr 08/03/92 5-3-11 River Reed Creek From source to Pisgah Creek WS-III;Tr 08/03/92 5-3-11-1 Chinquapin Creek From source to Pisgah Creek WS-III;Tr 08/03/92 5-3-11-2 Cold Creek From source to East Fork Pigeon WS-III;Tr 08/03/92 5-3-12 River Long Branch From source to East Fork Pigeon WS-III;Tr 08/03/92 5-3-13 River Harley Branch From source to East Fork Pigeon WS -III 08/03/92 5-3-14 River Burnett Creek From source to East Fork Pigeon WS-III;Tr 08/03/92 5-3-15 River Anderson Creek From source to Burnett Creek WS-III;Tr 08/03/92 5-3-15-1 Henderson Branch From source to Burnett Creek WS -III 08/03/92 5-3-15-2 Lenoir Creek From source to East Fork Pigeon WS-III;Tr 08/03/92 5-3-16 River Dix Creek From source to East Fork Pigeon WS-III;Tr 08/03/92 5-3-17 River Smoky Cove Branch From source to Dix Creek WS -III 08/03/92 5-3-17-1 Poison Cove Branch From source to Pigeon River WS -III 08/03/92 5-4 Stamey Cove Branch From source to Pigeon River WS -III 08/03/92 5-5 Garden Creek From source to Pigeon River WS -III 08/03/92 5-6 Henson Cove Branch From source to Garden Creek WS -III 08/03/92 5-6-1 Coffee Branch From source to Garden Creek WS -III 08/03/92 5-6-2 PIGEON RIVER From Garden Creek to Canton Water WS-III;Tr,CA 08/03/92 5-(6.5) Intake PISEGN a e From Canton Water Supply Intake to C 09/01/74 5-(7) below elevation 2258) North Carolina -Tennessee State Line Beaverdam ree From source to Pigeon River C 07/01/73 5-8 Long Branch From source to Beaverdam Creek B 04/01/58 5-8-1 West Cove Branch From source to Beaverdam Creek C 09/01/74 5-8-2 Wilson Cove Branch From source to Beaverdam Creek C 09/01/74 5-8-3 Rough Creek From source to dam at Canton WS-I;Tr,ORW 08/01/00 5-8-4-(1) Reservoir Rough Creek From dam at Canton Reservoir to C;HQW 08/03/92 5-8-4-(2) Beaverdam Creek Rice Cove Creek From source to Beaverdam Creek C 09/01/74 5-8-5 Murray Branch From source to Pigeon River C 09/01/74 5-9 Thickety Creek From source to Pigeon River C 09/01/74 5-10 Bowen Branch From source to Pigeon River C 09/01/74 5-10.5 Patton Branch From source to Pigeon River C 09/01/74 5-11 Sally Haynes Branch From source to Pigeon River C 09/01/74 5-12 Medford Cove Branch From source to Pigeon River C 09/01/74 5-13 Conner Mill Branch From source to Pigeon River C 08/03/92 5-14 Chambers Branch From source to Pigeon River C 09/01/74 5-15 3 111. Certification Statement: ' ` ��� _ certify to the best ofmy knowledge that the addition of the volume of wastewatc�e permitted in this project has been evaluated along the route to the receiving wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving treatment plant under normal circumstances, given the implementation of the planned improvements identified in the planning assessment where applicable. This analysis has been performed is accordance with local established policies and procedures using the best available data. This certification applies to those items listed above in Sections I and II plus all attached planning assessment addendums for which I am the responsible party. Signature of this form indicates acceptance of this wastewater Pl.ow. ,Wgning Of/irinl Signufan e ��-- ___._...____ Dcrle Page 2 of G FTSE 04-1G