HomeMy WebLinkAboutNC0067288_Inspection_20180517DocuSign Envelope ID: 1302F4E4-9361-4B6A-B32B-76CD19491A3D
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NCO067288 111 12 I 18/05/15 I17 18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I 73 I I 174 751 I I I I I I I80
u I� I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:30AM 18/05/15
16/02/01
Hunter's Glen WWTP
US Hwy 64
Exit Time/Date
Permit Expiration Date
Etowah NC 28729
11:15AM 18/05/15
20/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Vincent L Edwards/ORC/828-697-3077/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Patty Carland,117 Kira Ln Hendersonville NC 28739//828-890-4810/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance 0 Self -Monitoring Program
Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DS
Daniel J Boss ARO WQ//828-296-4658/ 5/17/2018
Signature of Management Q A Reviewer Docusigned by: Agency/Office/Phone and Fax Numbers Date
5/17/2018
7E617A38285848C...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 1302F4E4-9361-4B6A-B32B-76CD19491A3D
NPDES yr/mo/day Inspection Type (Cont.)
NCO067288 I11 121 18/05/15 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 5/15/2018, 1 (Daniel Boss) conducted a compliance evaluation at Hunter's Glen WWTP. The ORC,
Vince Edwards was present for the inspection. Overall the plant appeared clean and well operated, but
there were a couple of violations noted.
One item of concern was that the flow meter was broken since 3/18/2018, and is still waiting to be
repaired. Equipment needed to meet permit requirements should always be repaired immediately.
Another problem discovered is that the composite sampler is drawing samples from the chlorine
contact chamber. The sampling locaion for the composite sampler needs to be changed so that it is
past all treatment units. Vince said that he adds dechlorination substance to the composite sample,
and he does grab the fecal sample post-dechlorination.
There was some algae build-up on the clarifier weirs and skimmer. Please try to keep these clear of
blockages as much as possible.
Page#
DocuSign Envelope ID: 1302F4E4-9361-4B6A-B32B-76CD19491A3D
Permit: NCO067288
Inspection Date: 05/15/2018
Owner - Facility: Hunter's Glen WWTP
Inspection Type: Compliance Evaluation
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
❑
❑
❑
Is the wet well free of excessive grease?
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment: Visual alarm was present and operational. Audio alarm was not present.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Vince tests settleable solids and D.O. about twice a month.
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment:
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
0 ❑
❑
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
❑ ❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑
❑
Page# 3
DocuSign Envelope ID: 1302F4E4-9361-4B6A-B32B-76CD19491A3D
Permit: NC0067288 Owner - Facility: Hunter's Glen WWTP
Inspection Date: 05/15/2018 Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Comment:
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
❑
0
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
❑
❑
❑
Comment: There was some algae build-up on the weirs.
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0❑
❑
❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment:
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑ ❑
0
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Page# 4
DocuSign Envelope ID: 1302F4E4-9361-4B6A-B32B-76CD19491A3D
Permit: NCO067288 Owner - Facility: Hunter's Glen WWTP
Inspection Date: 05/15/2018 Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Number of tubes in use? 2
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
❑
0
❑
❑
Is flow meter calibrated annually?
❑
❑
❑
Is the flow meter operational?
❑
0
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The flow meter is currently broken and has been since 3/18/18.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
❑
Comment: Did not check outfall.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
0
❑
❑
Is sample collected below all treatment units?
❑
0
❑
❑
Is proper volume collected?
❑
❑
❑
Is the tubing clean?
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: Composite samples are being drawn from the chlorine contact chamber. Sampling needs
to be post dechlorination.
Page# 5