Loading...
HomeMy WebLinkAboutNCG590004_Inspection NOV2018PC0123_20180412ROY COOPER coverrwr ;na Water R esources ENVIRONMENTAL QUALITY MICHAEL S. REGAN Secretary LINDA CULPEPPER Interim Director April 12, 2018 CERTIFIED MAIL # 7016 1370 0000 2596 0221 RETURN RECEIPT REQUESTED Mr. Rondall Roper Cleveland County WTP P.O Box 788 Lawndale, NC 28090 Dear Mr. Roper: Subject: Notice of Violation Compliance Evaluation Inspection NOV-2018-PC-0123 Cleveland County WTP NPDES Permit No. NCG590004 Cleveland County Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at the subject facility on April 10, 2018 by Ori Tuvia. Your cooperation during the site visit was much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a copy of the enclosed report. The following areas of concern were observed during the inspection: 1) Facility has failed to conduct 24-hour flow based composite sampling as required by the permit. 2) Chain -of -Custody (COC) forms do not include the name of individual relinquishing the sample. Please be advised that this letter is a Notice of Violation. You are requested to respond to this Notice in writing within fifteen (15) days of receipt indicating your plan of action to ensure future compliance. Failure to respond and/or failure to resolve the violations could subject you to further action by the Division of Water Resources. Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-16991 Fax: (704) 663-60401 Customer Service: 1-877-623-6748 Internet: www.ncwaterquality.org The report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia(ancdenr.gov. Sincerely, DocuSigned by: A14CC681 AF27425... W. Corey Basinger Regional Supervisor Mooresville Regional Office Division of Water Resources cc: NPDES, MRO files (Laserfiche) United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 15 I 3 I NCG590004 111 12 I 18/04/10 I17 18 I S i 19 LG] i 201 I 211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----------------------Reserved------------------- 67 1.0 70Iq I 71 72n, 73I i74 751 1 1 1 1 80 u Int Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 11:05AM 18/04/10 15/02/01 Cleveland County WTP 435 Casar-Lawndale Rd Exit Time/Date Permit Expiration Date Lawndale NC 28090 12:20PM 18/04/10 19/07/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Rondall A Roper/ORC/704-538-9033/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Rondall A Roper,PO Box 327 Fallston INC 28042//704-538-9033/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date DocuSigned by: Ori A Tuvia MRO WQ//704-663-1699/ 4/12/2018 BB057A2DE017498... Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. DocuSigned by: 4/12/2018 �- Page# EA14CC681AF27425... NPDES yr/mo/day Inspection Type NCG590004 111 121 18/04/10 1 17 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# Permit: NCG590004 Owner - Facility: Cleveland County wTP Inspection Date: 04/10/2018 Inspection Type: Compliance Evaluation Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? ❑ ❑ ❑ 0 Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ 0 ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The permit expires on July 31, 2019. The facillity has been changed to a general permit. The old permit number was NC0051918. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? ❑ 0 ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ ❑ 0 Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling ❑ 2018 were reviewed for the inspection. At the time of the inspection it was determined that Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: DMRs, chain -of -custody's (CDCs), and calibration lops from June 2017 through February 2018 were reviewed for the inspection. At the time of the inspection it was determined that COCs do not include the name of individual relinquishing the samples. Laboratory Yes No NA NE Page# 3 Permit: NCG590004 Owner - Facility: Cleveland County WTP Yes No NA NE Is composite sampling flow proportional? ❑ ❑ Inspection Date: 04/10/2018 Inspection Type: Compliance Evaluation ❑ Is sample collected below all treatment units? 0 ❑ Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? ❑ 0 ❑ ❑ Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: The permittee performs on-site analysis of pH and total residual chlorine (TRC) under field laboratory certification #5381. Clear Water Laboratories has been contracted for any other sampling data. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type ❑ 0 ❑ ❑ representative)? Comment: The subiect Dermit reauires annual acute toxicitv 24-hour composite sample and arab samples. At the time of the inspection it was discovered the facility has failed to conduct composite sampling, and does not have the proper equipment to conduct such sampling. ORC was instructed on how to perform proper composite sampling. Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: At the time of the inspection the facility appeared to be well maintained Lagoons Yes No NA NE Type of lagoons? # Number of lagoons in operation at time of visit? 2 Are lagoons operated in? Parallel # Is a re -circulation line present? ❑ ❑ 0 ❑ Is lagoon free of excessive floating materials? 0 ❑ ❑ ❑ Page# 4 Permit: NCG590004 Owner - Facility: Cleveland County WTP Yes No NA NE Type of system ? Liquid Inspection Date: 04/10/2018 Inspection Type: Compliance Evaluation Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ Lagoons Yes No NA NE # Are baffles between ponds or effluent baffles adjustable? ❑ ❑ 0 ❑ Are dike slopes clear of woody vegetation? 0 ❑ ❑ ❑ Are weeds controlled around the edge of the lagoon? 0 ❑ ❑ ❑ Are dikes free of seepage? 0 ❑ ❑ ❑ Are dikes free of erosion? 0 ❑ ❑ ❑ Are dikes free of burrowing animals? 0 ❑ ❑ ❑ # Has the sludge blanket in the lagoon (s) been measured periodically in multiple ❑ ❑ 0 ❑ locations? # If excessive algae is present, has barley straw been used to help control the growth? ❑ ❑ 0 ❑ Is the lagoon surface free of weeds? 0 ❑ ❑ ❑ Is the lagoon free of short circuiting? 0 ❑ ❑ ❑ Comment: Sludge has been pumped for disposal in 2017. Sludge is pumped every 3 years. De -chlorination Yes No NA NE Type of system ? Liquid Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ 0 Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ ❑ 0 Are the tablets the proper size and type? ❑ ❑ 0 ❑ Comment: Permittee was using liquid sodium thiosulfite at the time of the inspection. Process control sampling is used to adjust dechlorination feed. Are tablet de -chlorinators operational? ❑ ❑ 0 ❑ Number of tubes in use? Comment: Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Yes No NA NE ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ Comment: Effluent Flow estimates are based on pump run time. Anew flow meter was recently Durchased and should be installed in the next couple of weeks. Effluent Pipe Yes No NA NE Page# 5 Permit: NCG590004 Inspection Date: 04/10/2018 Owner - Facility: Cleveland County WTP Inspection Type: Compliance Evaluation Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: At the time of the inspection the effluent was clear. Yes No NA NE ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Page# 6