HomeMy WebLinkAboutWQCSD0512_20180405_Compliance Evaluation Inspection (2) ROY COOPER Governor MICHAEL S. REGAN Sect etas y LINDA CULPEPPER Interim Dn ector April 5, 2018 Sharon Myers University of North Carolina at Chapel Hill Department of Environment, Health & Safety 1120 Estes Drive, CB# 1650 Chapel Hill,NC 27599-1650 Subject Compliance Evaluation Inspection UNC Collection System RECEIVED/DENR/DWR Deemed Collection System Permit WQCSD0512 Orange County APR m 2018 Dear Ms Myers: ater Resources ermitting Section On Tuesday, March 20, 2018, Vanessa Manuel from the Raleigh Regional Office conducted an inspection of the university's wastewater collection system to evaluate compliance with North Carolina Administrative Code Section 15A NCAC 02T .0403 (Permitting by Regulation). Your cooperation and assistance during the inspection, as well as that of Doug Horner and Janet Clarke were greatly appreciated. Our records indicate the wastewater collection system consists of one duplex pump station and a gravity sewer line to the Mason Farm Wastewater Treatment Plant. There are no high-priority sewer lines associated with this deemed permitted collection system. The items below show what conditions were noted during the inspection. 1 Reported Sanitary Sewer Overflows. During the two-year period ending December 2017,there was one reported SSO from the university's collection system with a combined estimated volume of 1,100 gallons, none of which reached surface water. 2 Grease Control Program. Because the research lab associated with the subject collection system does not have a dining hall/cafeteria on site, the requirement for a grease control program does not apply 3. Pump Stations Inspected. The UNC Collection System has 1 duplex pump station located at the Francis Owens Blood Research Lab (FOBRL) The inspector's observations noted in the next 5 items below refer to the FOBRL pump station inspected 4. Pump Station Signage. Although North Carolina Administrative Code Title 15A Subchapter 02T Section .0403 does not require a peiniittee to post signage that identifies the pump station and provides an emergency 24-hour contact telephone number(s) with instructions for notification if the visual alarm illuminates and/or the audible alarm sounds,there is a benefit to having such signage posted in the event of an emergency. Please consider installing a sign at the pump station with instructions for notification and 24-contact numbers in the event the visual alarm illuminates or if an emergency is apparent 5. Pump Station Restricted Access. The pump station, equipment and components were observed to have restricted access. State of North Carolina I Environmental Quality I Water Resources I Raleigh Regional Office 1628 Mail service Center I Raleigh,North Carolina 27699-1628 919 791-4200 UNC-CH Dept. of Environment, Health &Safety (WQCSD0512) c April 5, 2018 6 Pump Stations Automatic Polling Feature. The pump station is connected to a telemetry system (i.e , remote alarm system) that allows the UNC Collection System operators routine contact with the pump station from a central location to check the operational status of the communication system. 7 Pump Station High Water Alarms. The pump station is equipped with a visual high-water alarm During the inspection, the visual alarm did not function when the high-water float was triggered. The operator evaluated of the alarm during the inspection and determined the alarm's light bulb needed to be replaced. Please ensure the light bulb is replaced and the visual alarm is tested during the pump station inspections. The telemetry system was activated during the high-water alarm test, and the operator received notification of the event on his mobile phone. 8 Pump Station Inspection Program. The UNC-CH Department of Environment, Health& Safety has developed and implements a routine inspection of the pump station that includes the following maintenance activities cleaning and removing debris from the pump station area and wet well; inspecting all valves; inspecting pumps and other mechamcal equipment; and verifying the proper operation of the alarms, telemetry system and auxiliary equipment. The inspection logs are maintained electronically and was not available to inspect during the state inspection. In the future, please ensure logs are available at the time of the inspection 9 Overflow Response Plan. The UNC-CH Department of Environment, Health& Safety has developed an Overflow Response Plan that includes 24-hour contact numbers, response time, equipment list and spare parts inventory, site sanitation and cleanup materials, and post-SSO assessment. Please ensure the Plan is reviewed periodically and updated as needed 10. Sewer Collection System Map. The UNC-CH Department of Environment, Health& Safety has developed and maintains an up-to-date comprehensive map of its sewer collection system. The map includes pipe location, flow direction, and the pump station location. 11. Right-of-ways and Easements. As required by 15A NCAC 02T 0403(a)(9), right-of-ways and easements are maintained in the full easement width for personnel and equipment accessibility surrounding the sewer collection system. If you have questions or comments about this inspection or the requirements to take corrective action if applicable,please contact Vanessa Manuel at 919-791-4255 ,/7 Sincerely, C '7" . -'7l/ ------------- .5----;121/2,- S. Daniel Smith, Supervisor Water Quality Regional Supervisor Raleigh Regional Office Attachment(s). Collection System Inspection Report Cc RRO/SWP Files PERCS Unit Central Files I Compliance Inspection Report Permit WQCSD0512 Effective 02/22/10 Expiration Owner UNC-CH Department of Environment Health &Safety SOC• Effective- Expiration Facility UNC Collection System County Orange Region Raleigh Contact Person Sharon Myers Title Phone 919-962-9752 Directions to Facility. System Classifications. Primary ORC Certification Phone. Secondary ORC(s): On-Site Representative(s) Related Permits Inspection Date 03/20/2018 Entry Time• 09 51AM Exit Time 11 30A Primary Inspector. Vanessa E Manuel - 2 -,9,1i'./ - / , Phone e�8e.7-6392 Secondary Inspector(s). / 14//r 9'71 1/2 s� Reason for Inspection Routine Inspection Type Collection System Inspect Non Sampling Permit Inspection Type. Deemed permitted collection system management and operation Facility Status' • Compliant 0 Not Compliant Question Areas. II Miscellaneous Questions j Performance Standards ® Operation&Maint Reqmts II Records ® Inspections • Pump Station (See attachment summary) Page 1 Permit WQCSD0512 Owner-Facility UNC-CH Department of Environment Health&Safety Inspection Date 03/20/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine Inspection Summary See attached Inspection report Page 2 Permit WQCSD0512 Owner-Facility UNC-CH Department of Environment Health&Safety Inspection Date 03/20/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine Performance Standards Yes No NA NE Is Public Education Program for grease established and documented? 00110 What educational tools are used? The deemed collection system serves a research lab it does not serve the public Is Sewer Use Ordinance/Legal Authonty available? 00M1=1 Does it appear that the Sewer Use Ordinance is enforced? 00 • O Is Grease Trap Ordinance available? ❑ ❑ E ❑ Is Septic Tank Ordinance available(as applicable,i e annexation) ❑ ❑ E ❑ List enforcement actions by permittee,if any,in the last 12 months Has an acceptable Capital Improvement Plan(CIP)been implemented? 00 • 0 Does CIP address short term needs and long term\"master plan\"concepts9 ❑ ❑ E ❑ Does CIP cover three to five year period? 00 • O Does CIP include Goal Statement? 1=10 • 0 Does CIP include description of project area? 00 • 0 Does CIP include description of existing facilities? 00 • O Does CIP include known deficiencies? 00 • 0 Does CIP include forecasted future needs? 00 • 0 Is CIP designated only for wastewater collection and treatment? 001. 0 Approximate capital improvement budget for collection system? Total annual revenue for wastewater collection and treatment? CIP Comments Is system free of known points of bypass? • 000 If no,describe type of bypass and location Is a 24-hour notification sign posted at ALL pump stations? 00 • 0 #Does the sign include Instructions for notification? ❑ ❑ e ❑ Pump station identifier? 00110 24-hour contact numbers 00 • 0 If no,list deficient pump stations Although the deemed collection system is not required to have a 24-hour sign posted,it is recommended A sign with instructions for notification and 24-hour contact phone numbers would be helpful in the event of a sewer overflow #Do ALL pump stations have an"auto polling"feature/SCADA9 111000 Number of pump stations 1 Number of pump stations that have SCADA 0 Number of pump stations that have simple telemetry 1 Number of pump stations that have only audible and visual alarms a Page 3 Permit WQCSD0512 Owner-Facility UNC-CH Department of Environment Health&Safety Inspection Date 03/20/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine Number of pump stations that do not meet permit requirements 0 #Does the permittee have a root control program? El El • ❑ #If yes,date implemented? Describe Comment Inspections Yes No NA NE Are maintenance records for sewer lines available? • El ❑ El Are records available that document pump station inspections? • 0 ❑ ❑ Are SCADA or telemetry equipped pump stations inspected at least once a week? ■ ❑ ❑ El Are non-SCADA/telemetry equipped pump stations inspected every day? El El • ❑ Are records available that document citizen complaints? El El • ❑ #Do you have a system to conduct an annual observation of entire system? • El El El #Has there been an observation of remote areas in the last year? ❑ El • 0 Are records available that document inspections of high-priority lines? El El ■ ❑ Has there been visual inspections of high-priority lines in last six months? El El • El Comment Operation&Maintenance Requirements Yes No NA NE Are all log books available? • ❑ El ❑ Does supervisor review all log books on a regular basis? ■ El El El Does the supervisor have plans to address documented short-term problem areas? ❑ ❑ I El What is the schedule for reviewing inspection,maintenance,&operations logs and problem areas? Are maintenance records for equipment available? • El El El Is a schedule maintained for testing emergency/standby equipment? ® ❑ ❑ ❑ What is the schedule for testing emergency/standby equipment? Monthly Do pump station logs include Inside and outside cleaning and debris removal? 0 ❑ El III Inspecting and exercising all valves? El ❑ El all Inspecting and lubricating pumps and other equipment? ❑ El ❑ 111 Inspecting alarms,telemetry and auxiliary equipment? El El El lill Is there at least one spare pump for each pump station w/o pump reliability? El ❑ ® El Are maintenance records for right-of-ways available? El ❑ ® ❑ Are right-of-ways currently accessible in the event of an emergency? ® ❑ ❑ El Are system cleaning records available? ❑ ❑ ® ❑ Has at least 10%of system been cleaned annually? ❑ El $ ❑ What areas are scheduled for cleaning in the next 12 months? Logs are maintatined electronically The electronic logs were not available on-site at the time of the inspection Page 4 ❑ 0000000000 W00000 ❑ 1 ❑ ❑ ❑ ❑ ❑ ❑ ■ • • • • • • 11111111 • 0 a) 7 ❑ ■ • N ❑ 0000 • • 0 ❑ } r - ❑ 0000000000 . 00000 ❑ ❑ ❑ ❑ ❑ ❑ ❑ 0 J § 7 ) 0 000000000N § ƒ •. ❑ ❑ ❑ ■ • 0 • 00 •■ ■ ƒ ƒ S2 0 o- k 12 Z• m C ® J p Cr) § § 2 •3 } S ( -F...,F \ ® ƒ 2 0 \ c • = O / | z co e 3 t 2 / \ / / G / E f 2 - 0 g / c ® * > c 5 0 ) . § � \ \ c. -0 $ .0 } Q. k • C. co C Ca k 2U. c § § m 2 G E E o • 2 / 2 f •{ ± ( k o I 6 \ { } § a) \ 2 £ p \ \ a) 7 $ -ca \ q o / a 7 k \ / E - - CO \ / / \ ® k ) § k % § 7 - £ § 5 / « / k - 0 ) 7 k 0 / 0 - k \ E § co\ ƒ @ / k k k § ƒ o 0 E CO/__ \ ) } k / ) k 0 / / § _ E A § ; / CO a) q ƒ 2 $ ) f / \ o co / \ § q f % rtai ] / . 2 k . # < § § . § \ ) § E \ co \ 3ct, -0 co \ CO ) 9 o \ c tj k \ / k § / \ o § C £ E § \ \ / / \ cn c b k 4 C o o / < c s at [ / : S § 3 { o 3 \ [ / o % 2 3 £ E a a ] § E ® a k d & ,, o. c a.co ) ) G E m S E G f £ Q * 2 ; co 2 - § Cl) ± £ $' o 7 - C - 0 0 § $ = A E ) \ ( & E E \ ® g { \ Q E Co \ \ § \ / < < / ¥ J / f § 0 \ ( » > coE 0 E o E E < J O. o ° E co„ E E 0 0 a £ O 1:1) L.. 0 2 \ \ { / O. a- Permit WQCSD0512 Owner-Facility UNC-CH Department of Environment Health&Safety Inspection Date 03/20/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine Are pump station logs available'? 0 0 0 El Is it accessible in all weather conditions? • 0 0 ❑ #Is general housekeeping acceptable? • El ❑ El Are all pumps present? • 00 ❑ Are all pumps operable'? • ❑ ❑ 0 --- - --- ------ -- --- T Are wet wells free of excessive debris? • El El 0 Are upstream manholes free of excessive debris/signs of overflow'? El ❑ U 0 Are floats/controls for pumps/alarms operable'? 1100 ❑ Is"auto polling"feature/SCADA present'? El 0 • 0 Is"auto polling"feature/SCADA operational'? El ❑ • ❑ Is simple telemetry present'? • El 0 0 Is simple telemetry operational'? • 0 El ❑ Are audio and visual alarms present'? ■ El ❑ El Are audio and visual alarms operable? 01100 Is the Pump station inspected as required'? I ❑ El El Are backflow devices in place'? ❑ El U 0 Are backflow devices operable'? El El ■ ❑ Are air relief valves in place? ❑ ❑ 11 El Are air relief valves operable'? 0 ❑ ■ El # Is an emergency generator available'? ❑ El ❑ U Can the emergency generator run the pumps? ❑ ❑ ❑ III Is the pump station equipped for quick hook-up'? El El El ■ Is the generator operable? El El El ■ #Is fuel in tank and sufficient'? ❑ ❑ El ■ Is the generator inspected according to their schedule'? ❑ El ❑ II Is a 24-hour notification sign posted'? El ❑ ■ ❑ Does it include Instructions for notification'? 0 ❑ ❑ El Pump station identifier'? ❑ El ❑ ❑ Emergency phone number ❑ ❑ El ❑ Is public access limited? U ❑ ❑ ❑ Is pump station free of overflow piping'? ® ❑ El ❑ Is the pump station free of signs of overflow'? ® ❑ El ❑ Are run times comparable for multiple pumps'? Page 6 Permit WQCSD0512 Owner-Facility UNC-CH Department of Environment Health&Safety Inspection Date 03/20/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine Comment While testing the high water alarm, the visual alarm did not function The operator inspected the alarm and determined the light bulb needed to be replaced The operator stated the pump station does not have an audible alarm During the testing, the operator received a message on his smart phone from the telemetry system regarding the alarm Although the deemed collection system is not required to have a 24-hour notification sign posted, it is recommended that one is posted in case of an emergency The information on the sign should provide contact information in the event of an overflow or other emergency at the pump station Page 7