Subject: Compliance Evaluation Inspection
TJ Ellison WTP
NPDES Permit No. NCO079740
Cleveland County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on April 4, 2018, by Ori Tuvia. Newt Henson's cooperation during the site
visit was much appreciated. Please advise the staff involved with this NPDES Permit by
forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori. tuvia(a),ncdenr. gov.
Sincerely,
EF161DocuSigned by:
FB69A2D84A3...
"ww H P44-ftfor
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
Cc: NPDES Unit, MRO Files (Laserfiche)
Mooresville Regional Office
Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115
Phone: (704) 663-16991 Fax: (704) 663-60401 Customer Service: 1-877-623-6748
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCO079740 111 12 I 18/04/05 I17 18 I S i 19 LG] i 201 I
211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
67 1.0 70 Id I 71 In, I 72 I n, I 73I I I74 751 1 1 1 1 1 1 180
I—I I� I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
11:45AM 18/04/05
14/02/01
Ellison WTP
1432 Oak Grove Rd
Exit Time/Date
Permit Expiration Date
Kings Mountain NC 28086
12:45PM 18/04/05
18/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Newt E. Henson/ORC/704-482-7131/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Newt E. Henson,PO Box 429 Kings Mountain NC
280860429/Supervisor/704-482-7131/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Ori A Tuvia .-F MRO WQ//704-663-1699/ 4/6/2018
EBB057A2DE017498...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax NuerS�ocuSigned by: Date
Andrew Pitner MRO WQ//704-663-1699 Ext.21 A H pZt#44 4/6/18
AgnsAAi
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO079740 111 121 18/04/05 1 17 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO079740 Owner - Facility: Ellison WTP
Inspection Date: 04/05/2018 Inspection Type: Compliance Evaluation
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
❑
❑
❑
0
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The subject permit expires on 8/31/2018.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
0
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
❑
0
❑
❑
Dates, times and location of sampling
CDCs, ORC logs, and Calibration logs were reviewed for the period October 2017 through
December 2017. COC's for Toxcity sampling, should be complete including
Name of individual performing the sampling
from Water Tech Labs to R&A Labs.
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: The records reviewed during the inspection were organized and well maintained. DMRs,
CDCs, ORC logs, and Calibration logs were reviewed for the period October 2017 through
December 2017. COC's for Toxcity sampling, should be complete including
the sending
from Water Tech Labs to R&A Labs.
Page# 3
Permit: NCO079740 Owner - Facility: Ellison WTP
Inspection Date: 04/05/2018 Inspection Type: Compliance Evaluation
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Field analvses (DH and total residual chlorine) are Derformed under the on-site laborator
certification #5597. Water Tech Labs (total suspended solids, trubidity , total nitrogen and
total phosphorus) and R&A Laboratories, Inc. (metals, toxicity) have also been contracted to
provide analytical support. The laboratory instrumentation used for field analyses appeared
to be properly
calibrated/verified and documented.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: The subject permit requires effluent grab sampling.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and 0 ❑ ❑ ❑
sampling location)?
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Page# 4
Permit: NCO079740
Inspection Date: 04/05/2018
Operations & Maintenance
Owner - Facility: Ellison WTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The NPDES treatment system includes a dechlorination unit. primary settlina tank. overflow
tank, and sludge dewatering system. A polymer is added to the influent of the settling tank to
enhance settling. The NPDES facilities appeared to be properly operated and well
maintained. The facility has been recently upgraded adding dechlornartion contact chamber,
SCADA system and flow meter.
De -chlorination
Yes No NA NE
Type of system ?
Liquid
❑
❑
❑
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑
❑
0
❑
Is storage appropriate for cylinders?
❑
❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑
❑
0
❑
Are the tablets the proper size and type?
❑
❑
0
❑
Comment: Liquid sodium thiosulfate is added (via dosage pump) for dechlorination prior to the settling
tank. The dechlorination pump system is only activated during discharge events.
Are tablet de -chlorinators operational? ❑ ❑ 0 ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Flow meter was installed last year, did not need to be calibrated vet.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: No discharge at the time of the inspection.
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Page# 5
Permit: NC0079740
Inspection Date: 04/05/2018
Owner - Facility: Ellison WTP
Inspection Type: Compliance Evaluation
Solids Handling Equipment
Yes No NA NE
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
❑
❑
❑
0
Is the site free of sludge buildup on belts and/or rollers of filter press?
0
❑
❑
❑
Is the site free of excessive moisture in belt filter press sludge cake?
0
❑
❑
❑
The facility has an approved sludge management plan?
0
❑
❑
❑
Comment: dewatering was occurring at the time of the inspection. Dewatered alum sludge is
transported (by facility staff) to the County Landfill for final disposal.
Page# 6