Loading...
HomeMy WebLinkAboutWQCS00111_NOV-2018-PC-0117_20180406DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E WarerResources ENVLG0KME4rAi QUAL ITY Certified Mail #7009 1680 0000 7515 6135 Return Receipt Requested April 06, 2018 Zack 011is, Town Manager Town of Tryon 301 N Trade St Tryon, NC 28782 SUBJECT: NOTICE OF VIOLATION Tracking Number: NOV-2018-PC-0117 Permit No. WQCS00111 Tryon Collection System Polk County Dear Mr. 011is: ROY COOPER Grn m -,r MICHAEL S. REGAIN Secret LT -NMA CUL PEPPER -Inlerem Dlrecia? The North Carolina Division of Water Resources conducted an inspection of the Tryon Collection System on March 8, 2018. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Collection System Permit No. WQCS00111. A summary of the findings and comments noted during the inspection are provided in the enclosed copy of the inspection report. The Collection System Inspection was conducted by Division of Water Resources staff from the Asheville Regional Office. The following violation(s) were noted during the inspection: Inspection Area Description of Violation Inspections Citizen complaints are logged at Town Hall and relayed to the collection system personnel. Permit Condition 11.2 requires the Permittee to develop and adhere to a schedule for reviewing complaint logs. Permit Condition 111.2. requires the Permittee to maintain adequate records pertaining to complaints for a minimum of three years. Inspections Inspections of high priority lines are not documented. Permit Condition VA. requires inspections of all high priority lines at least once per every 6 months. Permit Condition III. 1. requires records to document compliance with Condition VA. State of North Carolina I Environmental Quality I Water Resources 2090 U.S. 70 Highway, Swannanoa, NC 28778 828-296-4500 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E Performance Standards The CIP covers the next twenty years and projects are listed in order of priority, it does not include a 3-5 year period. This was noted in the last inspection. Permit Condition I.6. the Permittee shall adopt and implement a Capital Improvement Plan (CIP) to designate funding for reinvestment into the wastewater collection system infrastructure. The CIP should address short-term needs and long-term "master plan" concepts. The CIP should typically cover a 3-5 year period and include a description of the project area, description of the existing facilities, known deficiencies and forecasted future needs. Records The systemwide map does not include pipe size, pipe material, approximate age and number of service taps. This was noted in the last inspection. Permit Condition III.3. requires the permittee to maintain an up-to-date map, accurate, comprehensive map of its wastewater collection system that also notes the locations where other wastewater collection systems become tributary. The map shall include: pipe size, pipe material, pipe location flow direction, approximate pipe age, number of service taps. Operation & Maintenance The Spill Control Plan does not include response time. This was noted in the last inspection. Permit Condition II.9.b. requires adequate measures be taken to contain and properly dispose of materials associated with SSOs. The permittee shall maintain a Response Action Plan that addresses the following minimum items: a. contact phone numbers for 24-hour response; b. response time; c. equipment list and spare parts inventory; d. access to cleaning equipment; e. access to construction crews, contractors or engineers; f. sources of emergency funds; site sanitation and cleanup materials; h. post-SSO assessment. In addition, the issues below must also be addressed: Compliance Issue(s): 1. Gary Walker is listed as the Backup ORC but the Division database shows that his certification is invalid. Please determine if the certification is valid and if not, a certified Backup ORC should be designated. 2. There were three SSO's at the manholes on Braewick Road and Melrose Ave. Ext. between December 5, 2017 and February 19, 2018. All three SSO's reached surface waters. According to facility staff, the problem is associated with the Town's Water Treatment Plant alum pond. The pond appears to be close to capacity. The pond discharge contains debris that causes clogged lines and ultimately SSO's. The Town should make resolving this issue a high priority. Remedial actions should have already been taken to correct this problem and prevent further occurrences in the future. The Division of Water Resources may pursue enforcement action for this and any additional violations of State law. To prevent further action, please respond in writing to this office within 30 days upon your receipt of this Notice of Violation regarding your plans or measures to be taken to address the indicated violations and other identified issues, if applicable. State of North Carolina I Environmental Quality I Water Resources 2090 U.S. 70 Highway, Swannanoa, NC 28778 828-296-4500 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E If you should have any questions, please do not hesitate to contact Beverly Price with the Water Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500. Sincerely, DocuSigned by: 1 -r(KA f�6KA 082131105A3CA418... On behalf of G. Landon Davidson, P.G., Regional Supervisor Water Quality Regional Operations Section Asheville Regional Office Division of Water Resources, NCDEQ ATTACHMENTS: Inspection Report EC: WQS ARO Server PERCS - LF 20180406_WQCS00111_NOV2018PC0117. rtf State of North Carolina I Environmental Quality I Water Resources 2090 U.S. 70 Highway, Swannanoa, NC 28778 828-296-4500 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E Compliance Inspection Report Permit: WQCS00111 Effective: 04/01/17 Expiration: 03/31/25 owner: Town of Tryon SOC: Effective: Expiration: Facility: Tryon Collection System County: Polk 423 N Trade St Region: Asheville Tryon NC 28782 Contact Person: Andrew McCallister Title: ORC Phone: 828-859-5626 Directions to Facility: System Classifications: CS2, Primary ORC: Andrew Lee McCallister Certification: 995172 Phone: 828-859-6880 Secondary ORC(s): Gary Walker 13666 828-859-6654 On -Site Representative(s): 24 hour contact name Andrew Lee McCallister 828-859-6880 On-site representative Deborah M Bradley 828-859-5626 Related Permits: NC0021601 Town of Tryon - Tryon WWTP Inspection Date: 03/08/2018 psEntry Time: 09:20AM Exit Time: 01:OOPM Primary Inspector: Beverly Price Q % Phone: 828-296-4500 Secondary Inspector(s): Mikal Willmer °j� Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Collection system management and operation Facility Status: Compliant Not Compliant Question Areas: Miscellaneous Questions Performance Standards Operation & Maint Reqmts Records Monitoring & Rpting Reqmts Inspections Manhole (See attachment summary) Page: 1 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E Permit: WQCS00111 Owner - Facility: Town of Tryon Inspection Date: 03/08/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: The Collection System inspection was conducted by Beverly Price and Mikal Willmer of the Asheville Regional Office. Andrew McCallister and Deborah Bradley assisted with the inspection. The collection system consists of approximately 19 miles of gravity sewer; no pump stations. The system includes pvc, clay and ductile iron pipe. According to a map generated in 2005 by CAVANAUGH, there are 392 manholes. Overall the collection system is fairly well maintained given that there are currently only two employees for the entire system. The Town would benefit from an additional position to assist with collection system inspections and maintenance. The following items were determined to be non-compliant during the inspection: 1.Citizen complaint records are not maintained. See Permit Condition 111.2. & 11.2. 2.Response time should be added to the Spill Control Plan. See Permit Condition 11.9.b. 3.Inspections of high priority lines are not documented. See Permit Condition VA. 4.The map needs to be updated to include pipe size, pipe material, approximate age and the number of service taps. See Permit Condition 111.3. 5.The Capital Improvement Plan should include a three -five year period. See Permit Condition 1.6. The following additional items should be addressed: 1.Gary Walker is listed as the Backup ORC but the Division database shows that his certification is invalid. Please determine if the certification is valid and if not, a certified Backup ORC should be designated. 2.There were three SSO's at the manholes on Braewick Road and Melrose Ave. Ext. between December 5, 2017 and February 19, 2018. According to facility staff, the problem is associated with the Town's Water Treatment Plant alum pond. The pond appears to be close to capacity. The pond discharge contains debris which clogs lines and results in SSO's. The Town should make this a high priority. Page: 2 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E Permit: WQCS00111 Owner - Facility: Town of Tryon Inspection Date: 03/08/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Performance Standards Yes No NA NE Is Public Education Program for grease established and documented? 0 ❑ ❑ ❑ What educational tools are used? The Town of Tryon website. The Upstate Newspaper - twice per year. The Tryon Daily Bulletin. Is Sewer Use Ordinance/Legal Authority available? 0 ❑ ❑ ❑ Does it appear that the Sewer Use Ordinance is enforced? ❑ ❑ ❑ Is Grease Trap Ordinance available? ❑ ❑ ❑ Is Septic Tank Ordinance available (as applicable, i.e. annexation) ❑ ❑ ❑ List enforcement actions by permittee, if any, in the last 12 months Has an acceptable Capital Improvement Plan (CIP) been implemented? ❑ ❑ ❑ Does CIP address short term needs and long term \"master plan\" concepts? ❑ ❑ ❑ Does CIP cover three to five year period? ❑ ❑ ❑ Does CIP include Goal Statement? ❑ ❑ ❑ Does CIP include description of project area? ❑ ❑ ❑ Does CIP include description of existing facilities? ❑ ❑ ❑ Does CIP include known deficiencies? ❑ ❑ ❑ Does CIP include forecasted future needs? ❑ ❑ ❑ Is CIP designated only for wastewater collection and treatment? ❑ ❑ ❑ Approximate capital improvement budget for collection system? Total annual revenue for wastewater collection and treatment? CIP Comments The CIP covers the next twenty years and projects are listed in order of priority; it is not specific for the next 3-5 year period - this was noted in the last inspection. The Water & Sewer budget for FY 2017-2018 is $1,617,813. Is system free of known points of bypass? ❑ ❑ ❑ If no, describe type of bypass and location Is a 24-hour notification sign posted at ALL pump stations? ❑ ❑ 0 ❑ # Does the sign include: Instructions for notification? ❑ ❑ 0 ❑ Pump station identifier? ❑ ❑ 0 ❑ 24-hour contact numbers ❑ ❑ 0 ❑ If no, list deficient pump stations # Do ALL pump stations have an "auto polling" feature/SCADA? ❑ ❑ 0 ❑ Number of pump stations Number of pump stations that have SCADA Page: 3 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E Permit: WQCS00111 Owner - Facility: Town of Tryon Inspection Date: 03/08/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Number of pump stations that have simple telemetry Number of pump stations that have only audible and visual alarms Number of pump stations that do not meet permit requirements # Does the permittee have a root control program? ❑ ❑ ❑ # If yes, date implemented? Describe: The root control program was implemented approximately 12 years ago; solvents and root cutters are used. Comment: The CIP includes water system infrastructure. Inspections Yes No NA NE Are maintenance records for sewer lines available? ❑ ❑ ❑ Are records available that document pump station inspections? ❑ ❑ ❑ Are SCADA or telemetry equipped pump stations inspected at least once a week? ❑ ❑ ❑ Are non-SCADA/telemetry equipped pump stations inspected every day? ❑ ❑ ❑ Are records available that document citizen complaints? ❑ ❑ ❑ # Do you have a system to conduct an annual observation of entire system? ❑ ❑ ❑ # Has there been an observation of remote areas in the last year? ❑ ❑ ❑ Are records available that document inspections of high-priority lines? ❑ ❑ ❑ Has there been visual inspections of high-priority lines in last six months? ❑ ❑ ❑ Comment: Citizen complaints are loaaed at Town Hall and relaved to the collection system Dersonnel. Citizen complaints should be logged and available for review. 15,495' sewer lines were cleaned & replaced in 2017. Inspections of high priority lines are required and should be documented. There are currently only 2 collection system employees which makes proper maintenance of the entire system difficult. Operation & Maintenance Requirements Are all log books available? Does supervisor review all log books on a regular basis? Does the supervisor have plans to address documented short-term problem areas? What is the schedule for reviewing inspection, maintenance, & operations logs and problem areas? Reviews are ongoing - problem areas are addressed as they arise. Are maintenance records for equipment available? Is a schedule maintained for testing emergency/standby equipment? What is the schedule for testing emergency/standby equipment? Do pump station logs include: Inside and outside cleaning and debris removal? Inspecting and exercising all valves? Yes No NA NE ❑■❑❑ ❑❑■❑ There are no pump stations in this system so there are no backup generators. ❑❑0❑ Page: 4 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E Permit: WQCS00111 Owner - Facility: Town of Tryon Inspection Date: 03/08/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspecting and lubricating pumps and other equipment? ❑ ❑ 0 ❑ Inspecting alarms, telemetry and auxiliary equipment? ❑ ❑ ❑ Is there at least one spare pump for each pump station w/o pump reliability? ❑ ❑ ❑ Are maintenance records for right-of-ways available? ❑ ❑ ❑ Are right-of-ways currently accessible in the event of an emergency? ❑ ❑ ❑ Are system cleaning records available? ❑ ❑ ❑ Has at least 10% of system been cleaned annually? ❑ ❑ ❑ What areas are scheduled for cleaning in the next 12 months? Is a Spill Response Action Plan available? 0 ❑ ❑ ❑ Does the plan include: 24-hour contact numbers 0 ❑ ❑ ❑ Response time ❑ ❑ ❑ Equipment list and spare parts inventory ❑ ❑ ❑ Access to cleaning equipment ❑ ❑ ❑ Access to construction crews, contractors, and/or engineers ❑ ❑ ❑ ❑ Source of emergency funds ❑ ❑ ❑ ❑ Site sanitation and cleanup materials ❑ ❑ ❑ ❑ Post-overflow/spill assessment ❑ ❑ ❑ Is a Spill Response Action Plan available for all personnel? ❑ ❑ ❑ Is the spare parts inventory adequate? 0 ❑ ❑ ❑ Comment: The response time should be added to the Spill Response Plan: this was noted in the last inspection. Records Yes No NA NE Are adequate records of all SSOs, spills and complaints available? ❑ ❑ ❑ Are records of SSOs that are under the reportable threshold available? ❑ ❑ ❑ Do spill records indicate repeated overflows (2 or more in 12 months) at same location? ❑ ❑ ❑ If yes, is there a corrective action plan? ❑ ❑ ❑ Is a map of the system available? ❑ ❑ ❑ Does the map include: Pipe sizes ❑ 0 ❑ ❑ Pipe materials ❑ ❑ ❑ Pipe location ❑ ❑ ❑ Flow direction ❑ ❑ ❑ Approximate pipe age ❑ ❑ ❑ Number of service taps ❑ ❑ ❑ Pump stations and capacity ❑ ❑ ❑ Page: 5 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E Permit: WQCS00111 Owner - Facility: Town of Tryon Inspection Date: 03/08/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine If no, what percent is complete? List any modifications and extensions that need to be added to the map The map needs to be updated to include the following: pipe size, pipe material, approximate age and the number of service taps - this was noted in the last inspection. # Does the permittee have a copy of their permit? 0 ❑ ❑ ❑ Comment: There have been 3 SSO's between 12/5/17 and 2/19/18 at Braewick Rd and Melrose Ext.; all involved discharges to surface waters. The SSO's appear to be related to the Water Treatment Plant alum pond backwash system. Monitoring and Reporting Requirements Yes No NA NE Are copies of required press releases and distribution lists available? ❑ ❑ ❑ Are public notices and proof of publication available? ❑ ❑ ❑ # Is an annual report being prepared in accordance with G.S. 143-215.1 C? ❑ ❑ ❑ # Is permittee compliant with all compliance schedules in the permits? ❑ ❑ 0 ❑ If no, which one(s)? Comment: PACKARD WOODWORKS - Manhole Yes No NA NE Is manhole accessible? 0 ❑ ❑ ❑ # Is manhole cover/vent above grade? ❑ ❑ ❑ Is the manhole free of visible signs of overflow? ❑ ❑ ❑ Is the manhole free of sinkholes and depressions? ❑ ❑ ❑ Is manhole cover present? ❑ ❑ ❑ # Is manhole properly seated? ❑ ❑ ❑ # Is manhole in good condition? ❑ ❑ ❑ # Is invert in good condition? ❑ ❑ ❑ Is line free-flowing and unrestricted in manhole? ❑ ❑ ❑ Is manhole free of excessive amounts of grease? ❑ ❑ ❑ Is manhole free of excessive roots? ❑ ❑ ❑ Is manhole free of excessive sand? ❑ ❑ ❑ Is manhole's extended vent screened? ❑ ❑ ❑ Are vents free of submergence? ❑ ❑ ❑ Are manholes free of bypass structures or pipes? 0 ❑ ❑ ❑ Comment: There is a minor depression/eroded area on the northeast side of the manhole. 10 - Braewick Rd & Melrose Manhole Yes No NA NE Is manhole accessible? 0 1:11:1 ❑ # Is manhole cover/vent above grade? ❑ 0 ❑ ❑ Page: 6 DocuSign Envelope ID: 23EE5395-E168-497A-A149-862F52CB673E Permit: WQCS00111 Owner - Facility: Town of Tryon Inspection Date: 03/08/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Is the manhole free of visible signs of overflow? ❑ ❑ ❑ Is the manhole free of sinkholes and depressions? ❑ ❑ ❑ Is manhole cover present? ❑ ❑ ❑ # Is manhole properly seated? ❑ ❑ ❑ # Is manhole in good condition? ❑ ❑ ❑ # Is invert in good condition? ❑ ❑ ❑ Is line free-flowing and unrestricted in manhole? ❑ ❑ ❑ Is manhole free of excessive amounts of grease? ❑ ❑ ❑ Is manhole free of excessive roots? ❑ ❑ ❑ Is manhole free of excessive sand? ❑ ❑ ❑ Is manhole's extended vent screened? ❑ ❑ ❑ Are vents free of submergence? ❑ ❑ ❑ Are manholes free of bypass structures or pipes? 0 ❑ ❑ ❑ Comment: This MH receives flow from the water treatment plant alum pond. The alum pond appears to be the main cause of recent overflows at both this MH and MH#11 located at Braewick Rd Right of Way. Page: 7