HomeMy WebLinkAboutWQCSD0272_Compliance Evaluation Inspection_20180312 ROY COOPER
Gwenior
MICHAEL S.BEGAN
secritissry
Water Resources LINDA CW.PEPPER
6114004MENTAL% Litt htterizn-Director
Certified Mail # 7012 3050 0001 9398 9786
Return Receipt Requested
March 12, 2018
Milton Farmer, Mayor \REciav DIDENR ®AIR
Town of Wagram 2"PO Box 118 MAR 15
Wagram, NC 28396 Water Resource'
Pen-rutting SectionSUBJECT: Compliance Inspection Report
Town of Wagram Collection System
Collection System Permit No. WQCSD0272
Scotland County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Town of
Wagram Collection System on 2/27/2018. This inspection was conducted to verify that the
facility is operating in compliance with the conditions and limitations specified in Collection
System Permit No. WQCSD0272. The findings and comments noted during this inspection are
provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report".
Please respond in writing to this office within 30 days of your receipt of this letter regarding
your plans or measures to be taken to address the following issues:
The 24-hour notification signs at pump stations #1 and #2 are faded to the point of being
unreadable. These signs need to be replaced. Also, pump stations #4 and #5 each had one
pump that did not operate. Town personnel stated that impellers were on order for both
pumps to be repaired. These pumps need to be repaired or replaced immediately. In your
response please document when these pumps were put back in service.
State of North Carolina I Environmental Quality I Water Resources
225 Green Street,Suite 714,Fayetteville,NC 28301-5043
910-433-3300
If you should have any questions, please do not hesitate to contact Hughie White with the
Water Quality Regional Operations Section in the Fayetteville Regional Office at 910-433-3300.
_ Sincerely,
A-Zte,AVdt-Z- -
J. Trent Allen, Regional Supervisor
Water Quality Regional Operations Section
Fayetteville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Fayetteville Regional Office (HW)
PERCS Unit
State of North Carolma I Environmental Quality I Water Resources
225 Green Street,Suite 714,Fayetteville,NC 28301-5043
910-433-3300
Compliance Inspection Report
Permit WQCSD0272 Effective. 03/01/00 Expiration: Owner Town of Wagram
SOC. Effective. Expiration• Facility: Town of Wagram Collection System
County Scotland
Region: Fayetteville
Contact Person: Milton W Farmer Title. Mayor Phone. 910-369-2776
Directions to Facility
System Classifications
Primary ORC Certification: Phone
Secondary ORC(s)
On-Site Representative(s):
Related Permits.
Inspection Date 02/27/2018 Entry Time09 30AM Exit Time 02 OOPM
Primary Inspector: Hughie White 40/4/,___------ Phone. 910-433-3300 Ext 708
Secondary Inspector(s):
Trent AllenijL ,dr
e..-----
Reason for Inspection: Routine Inspection Type. Collection System Inspect Non Sampling
Permit Inspection Type Deemed permitted collection system management and operation
Facility Status • Compliant El Not Compliant
Question Areas.
• Miscellaneous Questions El Performance Standards • Operation&Maint Reqmts
El Records 111 Monitoring&Rpting Reqmts • Inspections
• Pump Station
_ (See attachment summary) _
Page 1
Permit WQCSD0272 Owner-Facility Town of Wagram
Inspection Date 02/27/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
Inspection Summary
Records and log books were available for review A copy cf the sewer use ordinance,grease ordinance,spill response plan
and map of the system were all available for review The spill response plan needs to be updated Grease education
materials are being distributed and as a reminder,education materials need to be distributed to all users of the collection
system twice per year The Town has no known high-priority lines to inspect and all sewer lines are within the streets
rights-of-ways so no outfall lines have to be maintained As noted elsewhere in this inspection report,the 24-hour
notification signs at pump stations#1 and#2 need to be replaced due to the signs being faded to the point of being
unreadable Also,at pump stations#5 and#4,each station had one pump that was not operating Town personnel stated
that impellers were on order for both pumps that did not wcrk Both issues, involving the 24-hour notification signs and the
pumps that are out of service, need to be resolved as soon as possible
Page 2
Permit WQCSD0272 Owner-Facility Town of Wagram
Inspection Date 02/27/2018 Inspection Type Collection System Inspect Non Sampling - Reason for Visit. Routine
Performance Standards Yes No NA NE
Is Public Education Program for grease established and documented? • ❑ 0 ❑
What educational tools are used?
Memos on water bills several times per year
Is Sewer Use Ordinance/Legal Authority available? • ❑ ❑ ❑
Does it appear that the Sewer Use Ordinance is enforced? • 0 0 0
Is Grease Trap Ordinance available? • 0 ❑ 0
Is Septic Tank Ordinance available(as applicable,i e annexation) 000 •1
List enforcement actions by permittee,if any,in the last 12 months
Has an acceptable Capital Improvement Plan(CIP)been implemented? ❑ 0 II 0
Does CIP address short term needs and long term\"master plan\"concepts? ❑ ❑ ❑ •
Does CIP cover three to five year period? ❑ 0 0 U
Does CIP include Goal Statement? 0 0 ❑ II
Does CIP include description of project area? ❑ ❑ 0 II
Does CIP include description of existing facilities? , 0 ❑ ❑ •
Does CIP include known deficiencies? ❑ 0 0 •
Does CIP include forecasted future needs? 000 .
Is CIP designated only for wastewater collection and treatment? ❑ 0 ❑ U
Approximate capital improvement budget for collection system?
Total annual revenue for wastewater collection and treatment?
CIP Comments
Is system free of known points of bypass? • ❑ ❑ ❑
If no,describe type of bypass and location
Is a 24-hour notification sign posted at ALL pump stations? • ❑ ❑ ❑
#Does the sign include
Instructions for notification? • ❑ 0 0
Pump station identifier? • 000
24-hour contact numbers - • ❑ 0 0
If no,list deficient pump stations
Pump stations#1 and#2 have 24-hour notification sighns posted,however,the signs are faded to the point
where the writing cannot be seen These need to be replaced
#Do ALL pump stations have an"auto polling"feature/SCADA? ❑ • 0 0
Number of pump stations 5
Number of pump stations that have SCADA 0
Number of pump stations that have simple telemetry 5
Number of pump stations that have only audible and visual alarms 0
Page 3
Permit WQCSD0272 Owner-Facility Town of Wagram
Inspection Date: 02/27/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine _
Number of pump stations that do not meet permit requirements 0
#Does the permittee have a root control program? 0 0 0
#If yes,date implemented?
Describe
Comment The 24-hour notification signs at pump stations#1 and#2 need to be replaced due to being
faded.
Inspections Yes No NA NE
Are maintenance records for sewer lines available? • 0 0 0
Are records available that document pump station inspections? • ❑ ❑ ❑
Are SCADA or telemetry equipped pump stations inspected at least once a week? • 0 ❑.❑
Are non-SCADA/telemetry equipped pump stations inspected every day? 0 0 I 0
Are records available that document citizen complaints? ' • 0 0 ❑
#Do you have a system to conduct an annual observation of entire system? • 0 0 0
#Has there been an observation of remote areas in the last year? 0 0 II 0
Are records available that document inspections of high-priority lines? 0 0 IN 0
Has there been visual inspections of high-priority lines in last six months? ❑ 0 I 0
Comment This collection system has no known high-priority lines
Operation&Maintenance Requirements Yes No NA NE
Are all log books available? • 0 ❑ ❑
Does supervisor review all log books on a regular basis? • 0 0 0
' Does the supervisor have plans to address documented short-term problem areas? 0 0 II 0
What is the schedule for reviewing inspection,maintenance,&operations logs and problem areas?
Are maintenance records for equipment available? • 0 0 0
Is a schedule maintained for testing emergency/standby equipment? • 0 0 ❑
What is the schedule for testing emergency/standby equipment? monthly
Do pump station logs include -
Inside and outside cleaning and debris removal? • 0 0 0
Inspecting and exercising all valves? • 0 ❑ ❑
Inspecting and lubricating pumps and other equipment? • 0 0 0
Inspecting'alarms,telemetry and auxiliary equipment? ' • 0 0 0
Is there at least one spare pump for each pump station w/o pump reliability? 0 0 0 III
Are maintenance records for right-of-ways available? 0 ❑ I 0
Are right-of-ways currently accessible in the event of an emergency? 0 0 U ❑
Are system cleaning records available? • 0 ❑ ❑
Has at least 10%of system been cleaned annually? 0 ❑ IN 0
What areas are scheduled for cleaning in the next 12 months?
Page 4
9 abed
O 00 ❑ 4,06 g6Z-Eti6 s 0 y}inn eouepi000e w pajedaid 6uieq podei ienuue ue sl#
❑ ❑ 0 0 calgepene uogeogqnd;opaid pue saogou oggnd eiv
❑ ❑ 0 0 4,algepene s;sq uognqu;sip pue sesealai ssaid pannbai;o seidoo aiy
3N VN ON saA
s;uawannpab bupouaa pue bupo;iuow
.;uawwoO
0 • 0 0 6;iwi0d n011};0 Adoo e aneq as;;ivied ay;sena#
dew ay;o}pappe aq o}peau;ey;suoisuapce pue suoi;eogipow/(ue;sii
e,a;aldwoo si}ueoiad mum'ou;l
- -
O 0 0 • A I3edeo pue suoge}s dwnd
• 0 ❑ 0 sde;aoin,as;o JagwnN
• 0 0 0 a6e adid a;ewixoiddd
❑ ❑ 0 U uogoanp Mold
D OOM uogeooi adid
❑ ❑ ❑ • sieua;ew°did
❑ ❑ ❑ I - sezis adid
apniow dew ay;saoQ
❑ ❑ 0 IN 6algepene wa;sAs Nilo dew e sl
❑ • 0 0 (ueid uogpe eni;oawoo e 0.10111 si`say(;I
O U 0 0 6uoimooi ewes le(sy;uow Z6 in OJOW Jo z)SMog.lOAO pomade.]a}eoipul spiooaa Rids oa
❑ M ❑ 0 t,algepene ploys°iy;aigepodeJ an Japun we my)s(SS;o spiooai any
0 • 0 0 e,aigepene s;uleidwoo pue sleds'sOSS Ile Jo spiooai ejenbape any
3N VN ON SOA
sp.oaael
sAeM-o-s;ybu sjeej s ay}m }IM ale sew'AMOS py u!e;u!ew
a}sABM Jo-s}ybu au!JAMOS ou seq uMol eq j pe;epdn eq 01 speeu ueid esuodseJ plds eq j ;uewwoo
• 0 ❑ ❑ 6a}enbepe fuo;uenw sped weds all sl
IN ❑ ❑ ❑ 6ieuuosJed Ile ao;a gepene ueid uoi;o 'asuodsa�l IpdS a sl
• 000 }uewssesse Ipds/Mol}ianoisod
• 000 sleua;ew dnuealo pue uoge;iues alis
• ❑ ❑ ❑ spun;Aoue6Jawe jo winos
• 0 ❑ ❑ sJaaw6ua Jo/pue'sJo;oej;uoo'man uogOru;suo3 o;ssaOO'
• ❑ ❑ ❑ ;uawdinbe 6uweeio o}ssaooy
• 0 ❑ ❑ tio;u°nui sped weds pue;sll;uewdmb3
• 0 0 ❑ ewi;asuodsa�l
• 0 ❑ 0 siegwnu;oe;uoo Jnoy-ve
epniow ueid ay;sena
❑ 0 ❑ • 4,aigeliene ueid uogo''asuodse lids e sl
eui;noa .;isiA.io;UOSBOM 61NdweS UON pedsul we;sAs uoi;oelloa edAj uoI;oadsul 9602/LZ/Z0 a;ea uo!;oedsul
weJ6eM;o uMoI /Ilgioej-Jaunt° ZLZOOSOOM ;!weed
Permit: WQCSD0272 Owner-Facility Town of Wagram
Inspection Date 02/27/2018 Inspection Type•Collection System Inspect Non Sampling Reason for Visit Routine
#Is permittee compliant with all compliance schedules in the permits? ❑ 000
If no,which one(s)?
c
Comment
#1 -
Pump Station
Yes No NA NE
Pump station type Duplex
Are pump station logs available? • 000
Is it accessible in all weather conditions? • 000
#Is general housekeeping acceptable? 111000
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? • ❑ ❑ ❑
Are wet wells free of excessive debris? • 1:101:1
Are upstream manholes free of excessive debris/signs of overf ow? U ❑ ❑ ❑
Are floats/controls for pumps/alarms operable? • 000
Is"auto polling"feature/SCADA present? ❑ ❑ U ❑
Is"auto polling"feature/SCADA operational? 001110
Is simple telemetry present? • 000
Is simple telemetry operational? • ❑ ❑ ❑
Are audio and visual alarms present? • 0110
Are audio and visual alarms operable? • 12110
Is the Pump station inspected as required? • ❑ ❑ ❑
Are backflow devices in place? ❑ ❑ ❑ •
Are backflow devices operable? ❑ ❑ ❑ M
Are air relief valves in place? ❑ ❑ ❑ U
Are air relief valves operable? ❑ ❑ ❑ M
# Is an emergency generator available? U ❑ ❑ ❑
Can the emergency generator run the pumps? • ❑ ❑ ❑
Is the pump station equipped for quick hook-up? 00110
Is the generator operable? • 000
#Is fuel in tank and sufficient? • 000
Is the generator inspected according to their schedule? • 000
Is a 24-hour notification sign posted? • E100
Does it include
Instructions for notification? U ❑ ❑ ❑
Pump station identifier? • 000
Emergency phone number • ❑ ❑ ❑
Page 6
Permit WQCSD0272 Owner-Facility Town of Wagram
Inspection Date 02/27/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit. Routine
Is public access limited? • 0 0 0
Is pump station free of overflow piping? • 0 0 ❑
Is the pump station free of signs of overflow'? • ❑ ❑ ❑
Are run times comparable for multiple pumps?
Comment The 24-hour notification signs is faded to the point where you can't read it The sign needs to be
replaced
#5 -
Pump Station Yes No NA NE
Pump station type Duplex
Are pump station logs available? • ❑ ❑ ❑
Is it accessible in all weather conditions? • ❑ ❑ ❑
#Is general housekeeping acceptable? • ❑ 0 0
Are all pumps present? • 0 0 0
Are all pumps operable? ❑ • 0 0
Are wet wells free of excessive debris'? • 0 0 0
Are upstream manholes free of excessive debris/signs of overflow'? • ❑ 0 ❑
Are floats/controls for pumps/alarms operable? I ❑ ❑ ❑
Is"auto polling"feature/SCADA present? ❑ 0 IN ❑
Is"auto polling"feature/SCADA operational? ❑ ❑ II ❑
Is simple telemetry present? • 0 0 0
Is simple telemetry operational? • ❑ ❑ 0
Are audio and visual alarms present? • ❑ El ❑
Are audio and visual alarms operable'? • ❑ El ❑
Is the Pump station inspected as required? • El El ❑
Are backflow devices in place'? ❑ ❑ ❑ •
Are backflow devices operable'? ❑ ❑ ❑ •
Are air relief valves in place'? ❑ ❑ 0
Are air relief valves operable? ❑ ❑ ❑ U
# Is an emergency generator available'? - • ❑ ❑ ❑
Can the emergency generator run the pumps'? • ❑ ❑ ❑
Is the pump station equipped for quick hook-up? ❑ ❑ • ❑
Is the generator operable? • El 0 ❑
#Is fuel in tank and sufficient? • ❑ ❑ ❑
Is the generator inspected according to their schedule'? • ❑ ❑ ❑
Is a 24-hour notification sign posted? • ❑ ❑ ❑
Does it include
Page 7
Permit WQCSD0272 Owner-Facility Town of Wagram
Inspection Date 02/27/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
Instructions for notification? • ❑ ❑ ❑
Pump station identifier? 11 ❑ ❑ ❑
Emergency phone number 11 ❑ ❑ ❑
Is public access limited? • 01:10
Is pump station free of overflow piping? 111:11:11:1
Is the pump station free of signs of overflow? • 1:1110
Are run times comparable for multiple pumps?
Comment Pump#1 was not working Mr Locklear indicated that a new impeller for this pump had been
ordered
#4 -
Pump Station Yes No NA NE
Pump station type Duplex
Are pump station logs available? • 000
Is it accessible in all weather conditions? • 01:10
#Is general housekeeping acceptable? MOOD
Are all pumps present? 11000
Are all pumps operable? 0 ,100
Are wet wells free of excessive debris? M ❑ ❑ ❑
Are upstream manholes free of excessive debris/signs of overflow? • 000
Are floats/controls for pumps/alarms operable? I ❑ ❑ ❑
Is"auto polling"feature/SCADA present? 00 • 0
Is"auto polling"feature/SCADA operational? 00110
Is simple telemetry present? M ❑ ❑ ❑
Is simple telemetry operational? • ❑ ❑ ❑
Are audio and visual alarms present? • 1:101:1
Are audio and visual alarms operable? • 000
Is the Pump station inspected as required? • 000
Are backflow devices in place? ❑ ❑ ❑ M
Are backflow devices operable? - 000111
Are air relief valves in place? 00011
Are air relief valves operable? 00011
# Is an emergency generator available? MOOD
Can the emergency generator run the pumps? U ❑ ❑ ❑
Is the pump station equipped for quick hook-up? 00110
Is the generator operable? 11000
#Is fuel in tank and sufficient? 11000
Page 8
Permit WQCSD0272 _ Owner-Facility Town of Wagram
Inspection Date 02/27/2018 Inspection Type.Collection System Inspect Non Sampling Reason for Visit Routine
Is the generator inspected according to their schedule? • 0 0 0
Is a 24-hour notification sign posted? • 0 0 0
Does it include
Instructions for notification? • 0 0 0
Pump station identifier? ' • ❑ 0 0
Emergency phone number • ❑ 0 0
Is public access limited? • 0 0 ❑
Is pump station free of overflow piping? • 0 0 0
Is the pump station free of signs of overflow? • 0 ❑ ❑
Are run times comparable for multiple pumps?
Comment Pump#1 did not work at this station Mr Locklear indicated that a new impeller had been
ordered for this pump, as well
#3 -
Pump Station Yes No NA NE
Pump station type Duplex
Are pump station logs available? • 0 ❑ ❑
Is it accessible in all weather conditions? • ❑ 0 0
#Is general housekeeping acceptable? • ❑ ❑ 0
Are all pumps present? • 0 ❑ ❑
Are all pumps operable? • 0 ❑ El
Are wet wells free of excessive debns? • 0 El ❑
Are upstream manholes free of excessive debris/signs of overflow? • El ❑ ❑
Are floats/controls for pumps/alarms operable? • ❑ 0 ❑
Is"auto polling"feature/SCADA present? 0 El II ❑
Is"auto polling"feature/SCADA operational? ❑ 0 II El
Is simple telemetry present? • 0 ❑ El
Is simple telemetry operational? • ❑ 0 ❑
Are audio and visual alarms present? • 0 ❑ 0
Are audio and visual alarms operable? - - - - - - - - • 0 ❑ ❑
Is the Pump station inspected as required? • 0 ❑ 0
Are backflow devices in place? ❑ ❑ 0 U
Are backflow devices operable? 0 0 ❑ MI
Are air relief valves in place? ❑ 0 ❑ II
Are air relief valves operable? ❑ 0 0 MI
# Is an emergency generator available? • ❑ 0 ❑
Can the emergency generator run the pumps? • ❑ ❑ 0
Page 9
Permit: WQCSD0272 Owner-Facility Town of Wagram
Inspection Date 02/27/2018 Inspection Type:Collection System Inspect Non Sampling Reason for Visit Routine
Is the pump station equipped for quick hook-up? 0 0 • 0
Is the generator operable? • 0 0 0
#Is fuel in tank and sufficient? • 0 0 0
Is the generator inspected according to their schedule? • ❑ 0 ❑
Is a 24-hour notification sign posted? • 0 0 0
Does it include
Instructions for notification? • ❑ 0 0
Pump station identifier? • 0 0 0
Emergency phone number • 0 0 0
Is public access limited? • 0 0 0
Is pump station free of overflow piping? • 0 0 0
Is the pump station free of signs of overflow? • 0 0 0
Are run times comparable for multiple pumps?
Comment
#2 -
Pump Station
Yes No NA NE
Pump station type Duplex
Are pump station logs available? • 0 ❑ ❑
Is it accessible in all weather conditions? • 0 0 0
#Is general housekeeping acceptable? • 0 0 0
Are all pumps present? • 0 0 0
Are all pumps operable? • ❑ ❑ ❑
Are wet wells free of excessive debris? • 0 ❑ 0
Are upstream manholes free of excessive debris/signs of overflow? • 0 0 ❑
Are floats/controls for pumps/alarms operable? • 0 0 0
Is"auto polling"feature/SCADA present? 0 0 U ❑
Is"auto polling"feature/SCADA operational? 0 0 U 0
Is simple telemetry present? • 0 0 0
Is simple telemetry operational? • 0 ❑ 0
Are audio and visual alarms present? • 0 0 0
Are audio and visual alarms operable? • 0 0 0
Is the Pump station inspected as required? • 0 0 0
Are backflow devices in place? 0 0 0 •
Are backflow devices operable? 0 0 0 MI
Are air relief valves in place? 0 0 0 MI
Are air relief valves operable'? 0 0 0
Page 10
Permit WQCSD0272 Owner-Facility Town of Wagram
Inspection Date. 02/27/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
# Is an emergency generator available? • 0 0 0
Can the emergency generator run the pumps? • 0 0 0
Is the pump station equipped for quick hook-up? 0 0 • 0
Is the generator operable? • 0 0 0
#Is fuel in tank and sufficient? • 0 0 0
Is the generator inspected according to their schedule? • 0 0 0
Is a 24-hour notification sign posted? • 0 0 0
Does it include
Instructions for notification? • 0 0 0
Pump station identifier? • 0 0 0
Emergency phone number • 0 0 0
Is public access limited? • 0 0 0
Is pump station free of overflow piping? • 0 0 0
Is the pump station free of signs of overflow? • 0 0 ❑
Are run times comparable for multiple pumps?
Comment The 24-hour notification sign posted at this station is faded to the point of belnq unreadable This
sign needs to be replaced.
Page 11