HomeMy WebLinkAboutNC0040070_BIMS Compliance Report_20180221United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO040070 111 12 I 18/02/21 I17 18 I S i 19 LG] i 201 I
211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
67 1.0 70 71 I„ I 72 n 73 � i 74 751 I I I 1 1 1 I80
u u I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
01:30PM 18/02/21
15/04/01
Two Rivers Utilities WTP
313 N Falls St
Exit Time/Date
Permit Expiration Date
Gastonia NC 28052
02:45PM 18/02/21
19/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Christopher Robert High/ORC/704-866-6024/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Ed Cross,PO Box 1748 Gastonia NC 280531748//704-866-6827/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Maria Schutte Division of Water Quality//704-663-1699)
Ori A Tuvia MRO WQ//704-663-1699/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
A14CC681 AF27425...
Page#
NPDES yr/mo/day Inspection Type
NCO040070 111 121 18/02/21 1 17 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO040070 Owner - Facility: Two Rivers Utilities WTP
Inspection Date: 02/21/2018 Inspection Type: Compliance Evaluation
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
❑
❑
0
❑
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The subject permit expires on 1/31/2019. The Permit is inactive but was activated for the
period of Jan 7 - Jan 17, 2018 due to a dual pump failure. When inactive, the facility is not
required to complete monthly/quarterly reporting requirement.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
0
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
0
❑
Is the chain -of -custody complete?
❑
❑
0
❑
Dates, times and location of sampling
❑
Name of individual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses
❑
Transported COCs
❑
Are DMRs complete: do they include all permit parameters?
❑
❑
0
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Page# 3
Permit: NCO040070
Inspection Date: 02/21/2018
Record Keeping
Owner - Facility: Two Rivers Utilities WTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: For the 2 -week period for which the facilitv was active. samDlina were conducted for the
weekly parameters. Sampling was not done for the quarterly parameters (Aluminum, Iron,
Copper, Manganese, Fluoride, Zinc, Phosphors, Nitrogen and Chronic toxicity). CIRC was
instructed not to force a discharge in order to sample the quarterly requirements.
A log sheet is maintained to document weekly maintenance checks. A separate logbook is
kept to document all sludge processing.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
❑
❑
■
❑
M
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
■
❑
❑
❑
Comment: When active, the facility is required to collect grab samples. When inactive the facility is not
required to complete monthly reporting requirement.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
❑
0
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: All samplina reauirements (TSS. DH. Chlorine. Turbiditv) were samDled under the facilitv's in
house lab (#567).
At the time of the inspection it was determined that the facility chlorine sampling method is
inadequate, due to the fact it can only detect chlorine level under 50 ug/L, while permit limit is
17ug/L. The sampling method should have adequately low detection limits to meet permit
requirements.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Page# 4
Permit: NCO040070
Inspection Date: 02/21/2018
Owner - Facility: Two Rivers Utilities WTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Comment: The Permit has been inactive since March 2006, but was activated for the period of Jan 7 -
Jan 17, 2018 due to a dual pump failure.
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
■
❑
❑
❑
❑
❑
❑
■
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
■
❑
❑
❑
■
❑
❑
❑
Comment: The sludge is stored in basin #2 until filled and then dewatered and landfilled in addition the
facility can land apply under Long Creek WWTP solids permit
Page# 5