HomeMy WebLinkAboutNCG590009_Compliance Evaluation Inspection_20180309Environmental Quality 9 March 2018 Mr. Shannon Becker, President Aqua North Carolina, Inc. 202 Mackenan Court Cary, NC 27511 Subject: Compliance Evaluation Inspection Maplecrest WTP NPDES Permit No. NCG590006 Fox Run WTP NPDES Permit No. NCG590008 Keltic Meadows WTP NPDES Permit No. NCG590009 Oakley Park WTP NPDES Permit No. NCG590010 Gaston County Dear Mr. Becker: ROY COOPER Govenior MICHAEL S. REGAN Secretary LINDA CULPEPPER later;,.. Director Enclosed are copies of the Compliance Evaluation Inspection Reports for the inspections conducted at the subject facilities on March 7, 2018, by Ori Tuvia and Andrew Pitner. Rufus Masters' cooperation during the site visits was much appreciated. Please advise the staff involved with these NPDES Permits by forwarding a copy of the enclosed reports. The main areas of concern that were documented at the time of the inspections are: 1. The Chlorine meter used for sampling for all locations had a chlorine curve calibration that had expired on January 17, 2018. 2. Adjacent to well #1 at Oakley Park WTP, a tree had fallen onto the fence. Should the fence collapse, the tree may hit and adversely impact treatment units or endanger the staff. 3. The effluent pipe fitting at Maplecrest WTP was broken. 4. The ORC and staff must ensure that weekly visitations are documented on all future eDMRs. Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-16991 Fax: (704) 663-60401 Customer Service: 1-877-623-6748 Internet. ww .ncwaterquality,org 11E Environmental Quality ROY COOPER Governor MICHAEL S. REGAN secrernry LINDA CULPEPPER Interim Oimcmr If you any questions, please contact Ori Tuvia at (704) 235-2190, or via email at ori.tuviana,ncdenr. gov. Sincerely, W. Corey Basinger, Regional Supervisor Mooresville Regional Office Division of Water Resources, DEQ Cc: NPDES MRO Files Matt Costner (E -copy) Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-16991 Fax: (704) 663-60401 Customer Service: 1-877-623-6748 Internet: www.ncwaterquality.org United Stales Environmental Protection Agency Form Approved. EPA Washington, D C 20,160 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 1 3 I NCG590006 I 1 1 1 2 18/03/07 17 16 Li I 1 9 I C I 20I I 21111111 11111111 1 11 1111111 1 1 11111 1111111111- 166 Inspection Work Days Facility Self -Monitoring Evaluation Rating 61 OA -------------Reserved------------- 67 70 I. I 71 (r,, ( 72 Ni 731 751 I I 80 LJ L W —L_L Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 10:40AM 18/03/07 15/08/28 Maplecresl WTP Exit Time/Date permit Expiration Date Maplecrest Dr 11:05AM 18/03/07 19/07/31 Gastonia NC 28052 Name(s) of Onsite Representative(s)7Tilles(s)/Phone and Fax Number(s) Other Facility Data Rufus Mason Masters/ORC7704-507-8533/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Shannon V Becker,202 Mackenan Ct Cary NC 27511/President/919-653-5570/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit N Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Names) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Andrew Pilner MRO WQ/7704-663-1699 Ext.2180/ �/ Od A Tuvia MRO WQ//704-663-1699/ 3/q// Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. i%'� Page# 1 NPDES yr/mo/day Inspection Type NCG590006 I11 12 18/03/07 17 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) 1 Pagett 2 Permit NCG590006 Owner -Facility: Maplecrest WrP Inspection Date: 03/07/2018 Inspection Type: Compliance Evaluation Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? ❑ ❑ ❑ M Is the facility as described in the permit? M ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ M ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? M ❑ ❑ ❑ Comment: The subject permit expires on 7/31/2019. Permit was previously NC0086193. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? IN ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ ❑ M Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling _ Results of analysis and calibration Dales of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? M ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is = or> 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ M ❑ Comment: Records reviewed during the inspection were organized and well maintained. DMRs, CDCs. ORC visitation logs and calibration logs were reviewed for the period March 2017 through November 2017. EDMR for some months fail to show the ORC or staff weekly visit. The inspection verified that the ORC did visit the facility weekly. The ORC and staff must ensure that weekly visitations are documented on future EDMRs. Page# 3 PerrniC NCG590006 Owner -Facility: Maplecresl WTP Inspection Date: 03/07/2018 Inspection Type: Compliance Evaluation Yes No NA NE Is composite sampling flow proportional? ❑ ❑ Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? M ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ It Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ M ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: On-site field analvses (DH and total residual chlorine) are performed under Aqua North Carolina's field laboratory certification #5035. Water Tech Labs (TSS, turbidity, iron, manganese) has also been contracted to provide analytical support. It was discovered at the time of the inspection that the chlorine curve calibration has expired on January 17, 2018. Other than the expired chlorine curve, the laboratory instrumentation used for field analyses appeared to be properly calibrated/verified and documented. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type ❑ ❑ ❑ representative)? Comment: The subject permit requires effluent grab samples Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The facility appeared to be properly operated and well maintained. De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ 0 ❑ Is storage appropriate for cylinders? M ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Page# 4 Pertnit: NCG590006 Owner -Facility: Maplecrest WrP Inspection Date: 03/07/2016 Inspection Type: Compliance Evaluation De -chlorination Yes No NA NE Comment. Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 3 Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ M ❑ Is flow meter calibrated annually? ❑ ❑ 0 ❑ Is the flow meter operational? ❑ ❑ M ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: Instantaneous flows are based on the calculated backwash volume and duration. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? M ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ 0 ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: Effluent pipe fitting was broken Page# 5 United Stales Environmental Protection Agenq Form Approved. EPA Washington, 0,C. 2MO OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 1 3 I NCG590008 I11 121 18/03/07 I17 18 I r l 19 L!-' 20I I 21111111 1111111 U 111111111 1111111 1111111111_ 166 Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 OA -----------------Reserved------------ 67 1.0 70 L171 ILJI 72 L�J 731 174 75 I I I I 80 Section B: FacilityData Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 11 20A 18/03/07 16/03/01 Fox Run WTP Exit Time/Date Permit Expiration Date 4311 Greenhaven Ln Gastonia NC 28054 11:35AM 18/03/07 19/07/31 Name(s) of Onsite Representative(s)fritles(s)/Phone and Fax Number(s) Other Facility Data Rufus Mason Masters/ORC7704-507-8533/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Shannon V Becker,202 Mackenan Ct Cary NC 27511/Presidentl919-653-5570/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program 0 Facility Site Review EfFluent/Reoeiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Names) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Andrew Pitner MRO WO//704-663-1699 Ext.21 so/ _ Ori A Tuvia MRO W0//704-663-1699/ v/ Signature of Management O A Reviewer Agency/OfScs/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.. qre-eya =a zo e-6, Page# NPDES yr/mo/day Inspection Type 31 NCG590008 If 12I 18/03/07 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# Permit: NCG590008 Owner -Facility: Fox Run WTP Inspection Date: 03/07/2018 Inspection Type: Compliance Evaluation Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted anew ❑ ❑ 0 ❑ application? ❑ ❑ ❑ 0 Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ M ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The subiect permit expires on 7/31/2019. Permit was previously NC0072061. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? IN ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ ❑ 0 Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? M ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is = or > 5 MGD permitted Flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ M ❑ Comment: Records reviewed during the inspection were organized and well maintained. DMRs. CDCs ORC visitation logs, and calibration loos, were reviewed for the period March 2017 through November 2017. EDMR for some months fail to show the ORC or staff weekly visit. The inspection verified that the ORC did visit the facility weekly. The ORC and staff must ensure that weekly visitations are documented on future EDMRs. Page# 3 Permit: NCG590008 Owner -Facility: Fox Run VVrP Inspection Dale: 03/07/2018 Inspection Type: Compliance Evaluation Yes No NA NE Is composite sampling flow proportional? ❑ ❑ Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? M ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? M ❑ ❑ ❑ # Is the facility using a contract lab? M ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees M ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: On-site field analvses (DH and total residual chlorine) are performed under Aqua North Carolina's field laboratory certification #5035. Water Tech Labs (TSS, turbidity, iron, manganese) has also been contracted to provide analytical support. It was discovered at the time of the inspection that the chlorine curve calibration has expired on January 17, 2018. Other than the expired chlorine curve the laboratory instrumentation used for field analyses appeared to be properly calibrated/verified and documented. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? M ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: The subiect permit requires effluent grab samples Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The facility appeared to be properly operated and well maintained De -chlorination Yes No NA NE Type of system ? Liquid Is the feed ratio proportional to chlorine amount (1 to 1)? M ❑ ❑ ❑ Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ 0 ❑ Page# 4 Permit: NCG590008 Owner -Facility: Fox RunwrP Inspection Date: 03/07/2018 Inspection Type: Compliance Evaluation De -chlorination Yes No NA NE Comment: Are the tablets the proper size and type? ❑ ❑ 0 ❑ Are tablet de -chlorinators operational? ❑ ❑ M ❑ Number of tubes in use? Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ M ❑ Is flow meter calibrated annually? ❑ ❑ 0 ❑ Is the flow meter operational? ❑ ❑ M ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: Instantaneous flows are based on the calculated backwash volume and duration. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ M ❑ Comment: No discharges was observed during the inspection. Page# 5 United States Environmental Protection Agency Form Approved. EPA Washington, D.0 20,160 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 1 3 I NCG590009 I11 12 18/03/07 17 181x• 1 19 1 s 1 201 I 211111 1 11111 111 I I I I I 1 11 1 1 1 1 1 1 1 1 1 11 111 111 11 I I 1166 I Inspection Work Days Facility Self -Monitoring Evaluation Rating 81 QA -- Reserved 67 1.0 70 1. I 71 72 L.J 73 1 174 75 1 I I I 80 LJ [LJ1 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 11 10A 18/03/07 16/03/01 Keltic Meadows WrP #2 Exit Time/Date Permit Expiration Date End Of Ingonish Dr 150 11 25A 18/03/07 19/07/31 Gastonia NC 28052 Names) of Onsite Representative(s)/-ritles(s)/Phone and Fax Number(s) Other Facility Data /// Rufus Mason Masters/ORC/704-507-8533/ Name, Address of Responsible OfficiaUTille/Phone and Fax Number Contacted Shannon V Becker,202 Mackenan Ct Cary NC 27511/President/919-653-5570/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program N Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Andrew Pitner MRO WQW04-663-1699 Ext.2180/ Ori A Tuvia MRO WQ//704-663-1699/ / % //� — — /% Signature of Management Q A Reviewer Agenry/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA Form 60-3 (Rev 9-94) Previous editigpgare obsolete. 20lry Ate POP. Page# 1 NPDES yr/mo/day Inspection Type 31 NCG590009 I11 12I 18/03/07 117 18 U Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# 2 Permit: NCG590009 Owner -Facility: Kellic Meadows WrP#2 Inspection Date: 03/07/2018 Inspection Type: compliance Evaluation Yes No NA NE Are records kept and maintained as required by the permit? E ❑ Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? 0 ❑ ❑ ❑ Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ 0 ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? E ❑ ❑ ❑ Comment: The subject permit expires on 7/31/2019. Permit was previously NC0084468. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? E ❑ ❑ ❑ Is all required information readily available, complete and current? ❑ ❑ ❑ E Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is = or> 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: Records reviewed during the inspection were organized and well maintained. DMRs COCs ORC visitation logs and calibration logs were reviewed for the period March 2017 through November 2017 EDMR for some months fail to show the ORC or staff weekly visit. The inspection verified that the ORC did visit the facility weekly The ORC and staff must ensure that weekly visitations are documented on future EDMRs. Page# 3 Permit: NCG590009 Owner -Facility: Keltic Meadows wTP#2 Inspection Date: 03/07/2018 Inspection Type: Compliance Evaluation Yes No NA NE Is composite sampling flow proportional? ❑ ❑ Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? E ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ N ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: On-site field analvses (pH and total residual chlorine) are performed under Aqua North Carolina's field laboratory certification #5035. Water Tech Labs (TSS turbidity, iron manganese) has also been contracted to provide analytical support. It was discovered at the time of the inspection that the chlorine curve calibration has expired on January 17 2018. Other than the expired chlorine curve, the laboratory instrumentation used for field analyses appeared to be properly calibrated/verified and documented. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? - ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: The subiect permit requires effluent grab samples Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The facility appeared to be properly operated and well maintained. De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ 0 ❑ Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Page# 4 PenniC NGG590009 Owner -Facility: Keloc Meadows WTP #2 Inspection Date: 03/07/2018 Inspection Type: Compliance Evaluation De -chlorination Yes No NA NE Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 2 Comment: Facilitv has started using 2 rather than 3 dechlor tubes which solved the De -chlorination tablet residue that was noted in the past inspection. Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ Flow Measurement- Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ 0 ❑ Is flow meter calibrated annually? ❑ ❑ 0 ❑ Is the flow meter operational? ❑ ❑ 0 ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: Instantaneous flows are based on the calculated backwash volume and duration. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ E ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: No discharges was observed during the inspection. Page# 5 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 iu i 2 15 I 3 I NCG69DO10 I11 121 18/03/07 17 18 1 r• t 19 1 !-j 201 I 2111111111111111 111111111111111111111111111- 166 Inspection Work Days Facility Self -Monitoring Evaluation Rating 61 QA -----------------Reserved------------- 67 10 70 In I 72 L.J 73 174 751 I I 80 LJ 711LJ1 Section B: FacilityData Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09 55A 18/03/07 16/03/01 Oakley Park WrP Exit Time/Date Permit Expiration Date Sequoia Dr 10 20A 18/03/07 19/07/31 Gastonia NC 28052 Name(s) of Onsite Representative(s)rrities(s)/Phone and Fax Number(s) Other Facility Data Rufus Mason Masters/ORCR04-507-8533/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Shannon V Becker,202 Mackenan Cl Cary NC 27511/President/919-653-5570/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit E Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Andrew Pilner MRO WQ//704-663-1699 Ext.21 SO/ �/ !q. / Ori A Tuvia MRO WQ//704-663-1699/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA Form 3560-3 (Rev 9-94) Previous edaans are obsolete. • Zia 8 V� Page# 1 NPDES yr/mo/day Inspection Type NCG590010 �11 121 18/03/07 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# Permit: NCG590010 Owner -Facility: Oakley Park VVTP Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ Inspection Date: 03/07/201B Inspection Type: Compliance Evaluation ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? ❑ ❑ ❑ Dates, times and location of sampling Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ 0 ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? M ❑ ❑ ❑ Comment: The subject permit expires on 7/31/2019. Transported COCs In the permit the well numbers are reversed where well #2. 133 Sequoia Drive is listed as well #1 and well #1. Pinto Lane Well is listed as #2. M ❑ ❑ ❑ Permit was previously NC0086142. ❑ ❑ M ❑ Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ ❑ 0 Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? M ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ M ❑ (If the facility is = or> 5 MGD permitted Flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? M ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Page# 3 Permit: NCG590010 Inspection Date: 03/07/2018 Record Keeping Owner - Facility: Oakley Park WTP Inspection Type: Compliance Evaluation Yes No NA NE Comment. Records reviewed during the inspection were oraanized and well maintained. DMRs COCs ORC visitation loos and calibration logs were reviewed for the period March 2017 through November 2017. EDMR for some months fail to show the ORC or staff weekly visit. The inspection verified that the ORC did visit the facility weekly. The ORC and staff must ensure that weekly visitations are documented on future EDMRs. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? ❑ ❑ 0 ❑ Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/_ 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ M ❑ Comment: On-site field analvses (pH and total residual chlorine) are performed under Aqua North Carolina's field laboratory certification #5035. Water Tech Labs (TSS, turbidity, iron, manganese) has also been contracted to provide analytical support. It was discovered at the time of the inspection that the chlorine curve calibration has expired on January 17, 2018. Other than the expired chlorine curve the laboratory instrumentation used for field analyses appeared to be properly calibrated/verified and documented. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ M ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type M ❑ ❑ ❑ representative)? Comment: The subject permit requires effluent grab samples Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The facility appeared to be properly operated and well maintained. Adjacent to well #1 at Oakley Park WTP a tree had fallen onto the fence. Should the fence collapse the tree may hit and adversely impact treatment units or endanger the staff. Page# 4 Permit: NCG590010 Owner -Facility: Oakley Park WrP # Is flow meter used for reporting? ❑ Inspection Date: 03/07/2018 Inspection Type: compliance Evaluation ❑ Is flow meter calibrated annually? Operations & Maintenance Yes No NA NE De -chlorination Yes No NA NE Type of system ? Tablet ❑ 0 Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ 0 ❑ Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 3 Comment: Sodium bisulfte tablets are used for de-chlornation. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ M ❑ Is flow meter calibrated annually? ❑ ❑ 0 ❑ Is the flow meter operational? ❑ ❑ 0 ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: Instantaneous flows are based on the calculated backwash volume and duration. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ 0 ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ M ❑ Comment: No discharges were observed at both outfalls during the inspection. Page# 5