HomeMy WebLinkAboutNC0061930_Compliance Inspection Report_20180305WaterResources
ENVIKMMEWAL QUALITY
March 05, 2018
Ronnie D Waller
Mark Laurel Homeowner's Association
PO Box 155
Highlands, NC 28741
SUBJECT: Compliance Inspection Report
Mark Laurel WWTP
NPDES WW Permit No. NCO061930
Macon County
Dear Permittee:
ROY COOPER
Gmrerwr
MICHAEL S. REGA
S,y roffi-'
UNDA CULPEPPER
lmlereRP Dlreco?
The North Carolina Division of Water Resources conducted an inspection of the Mark Laurel
WWTP on 2/27/2018. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0061930.
The findings and comments noted during this inspection are provided in the enclosed copy of
the inspection report entitled "Compliance Inspection Report".
Inspection items of note include the following:
• Access to the facility requires crossing a low area of wet ground. This represents an
ice/mud fall hazard to both the ORC, inspection staff, and contactors. The area should
be filled with gravel or permanently drained to eliminate the hazard.
• One of the eight UV bulbs was broken at the time of the inspection and should be
replaced.
• The flow meter is of a make and model that can no longer be serviced or repaired.
Replace the flow meter with a make and model which can be serviced.
• The pump station alarm is not visible to passers-by and overflow to surface water could
occur without being observed for a significant period. It is recommended that the high-
level alarm in the wet well be connected to an autodialer system.
State of North Carolina I Environmental Quality I Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
If you should have any questions, please do not hesitate to contact me with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
ATTACHMENTS
Cc: WQS-ARO Server
LF
Sincerely,
EDocuSigned by:
l
Tim Heim, ., environmental Engineer
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
State of North Carolina I Environmental Quality I Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NC0061930 111 12 I 18/02/27 I17 18 I S J 19 LG] 201 I
211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
67 70 I I 71 I I 72 I r l 73 I I 174 751 I I I 1 1 1 I80
u ty I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:OOAM 18/02/27
17/12/01
Mark Laurel WWTP
Moonlight Dr
Exit Time/Date
Permit Expiration Date
Highlands NC 28741
11:00AM 18/02/27
22/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Brandon Keith Buchanan/ORC/828-586-5588/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Ronnie D Waller,PO Box 155 Highlands NC 28741//828-526-1772/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Operations & Maintenance 0 Records/Reports Facility Site Review
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim Ds ARO WQ//828-296-4665/ 3/5/2018
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCO061930 111 121 18/02/27 1 17 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a Compliance Evaluation Inspection on February
27, 2018. Brandon Buchanan (ORC) was present at the time of the inspection. The facility appeared to
be in compliance with Permit NC0061930. The following items were noted:
Access to the facility requires crossing a low area of wet ground. This represents an ice/mud slip
hazard to both the ORC, inspection staff, and contactors. The area should be filled with gravel or
permanently drained to eliminate the hazard.
One of the eight UV bulbs was broken at the time of the inspection and should be replaced.
The flow meter is of a make and model that can no longer be serviced or repaired. Replace the flow
meter with a make and model which can be serviced.
The pump station alarm is not visible to passers-by and overflow to surface water could occur without
being observed for a significant period. It is recommended that the high-level alarm in the wet well be
connected to an autodialer system.
Page#
Permit: NCO061930
Inspection Date: 02/27/2018
Owner - Facility: Mark Laurel WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Access to the facility requires crossing a low area of wet ground. This represents an
ice/mud slip hazard to both the ORC, inspection staff, and contactors. The area should be
filled with gravel to eliminate the hazard.
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment: Correct access safety hazard as indicated above.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ■ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ■ ❑ ❑
■ ❑ ❑ ❑
Comment: One of the eight UV bulbs was broken at the time of the inspection and should be replaced.
Page# 3