HomeMy WebLinkAboutWQCSD0563_Compliance Evaluation Inspection_20180221�.
K,
Water Resources
Environmental Quality
February 21, 2018
Federal Home Hardee Terrace LLC
274 Madison Ave., Rm. 401
New York, NY 10016
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Interim Director
RECEIVEDIDENPiDWR
MAR 01 2018
Water Resources
Permitting Section
Subject: Compliance Evaluation Inspection
Hardee Terrace Apartments Wastewater Collection System
Permit Number WQCSD0563
Durham County
Dear Permittee,
Jeremiah Dow of the Raleigh Regional Office conducted a compliance evaluation inspection on February 20,
2018. The assistance of Ms. Nichole Ward and Mr. Lewis Whitted was greatly appreciated. Please find the
attached Basin Wide Information Management System (BIMS) inspection checklist summarizing the inspection.
Below is a list of findings and recommendations developed from the inspection:
1. The subject permit was issued and became effective on March 1, 2000. Adoption of deemed permit rules
became effective April 17, 2006. All deemed permitted facilities are required to adhere to the
requirements and procedures for permitting, operation and maintenance of collection systems as stated in
15A NCAC 02T.0403.
2. The Hardee Terrace Apartments collection system does not have any pump stations or manholes on the
property. The collection system gravity feeds to the City of Durham collection system. Previous
inspections have documented one (1) high priority line, but myself and Mr. Whiffed were unable to locate
it at the time of the inspection. Mr. Whitted stated that contractors have been working on the facility's
sewer lines and may have altered this section of line. Please locate the high priority line and provide
photographs or verify that the line has been modified and is now located below ground.
The facility conducts a general observation of the entire system once a year as required by 15A NCAC
02T .0403 (6), but the observation is not documented. Please document yearly observation of the
system as required by 15A NCAC 02T.0403 (10).
4. Hardee Terrace Apartments did not have a map of the collection system available at the time of the
inspection as required by 15A NCAC 02T .0403 (2). Please develop a map of the collection system
identifying pipe location, flow direction, pipe size, and high priority lines if applicable.
15A NCAC 02T .0403 (a)(8)(b) requires at a minimum bi-annual distribution of grease education
materials to users of the collection system. At the time of the inspection, the grease control educational
-5->"Nothing Compares:..
State of North Carolina I Environmental Quality I Water Resources I Raleigh Regional Office
1628 Mail service Center I Raleigh, North Carolina 27699-1628
9197914200
program materials could not be produced, nor could information about the last date of distribution.
Please distribute and document grease education materials as required.
6. One (1) cleanout was observed that was damaged, missing a cap, and the pipe was filled with debris.
Please remove the debris, repair, and properly seal the cleanout.
7. Mr. Whitted stated that he was responsible for overflow response and cleanup. Please be aware that 15A
NCAC 02T .0403 (7) requires that overflows and bypasses be reported to the appropriate Division
regional office in accordance with 15A NCAC 02B .0506(a)
Please respond to this letter within 30 days of receipt. Your written response should detail how the bolded items
2, 3, 4, 5 and 6 listed above were addressed.
Thank you for your time and assistance with this inspection. If you have any questions about this inspection or
this letter, please contact Jeremiah Dow at jeremiah.downa ncdenr.gov or 919-791-4248.
rncely,
�
A7/7/
7/7 '
Danny Smith
Water Quality Regional Operations
Raleigh Regional Office
cc: Central Files
RRO File
Nichole Ward, Property Manager via email at: nward@homewoodre.com
Permit: WQCSD0563
SOC:
County: Durham
Region: Raleigh
Contact Person: Jim Rigsbee
Directions to Facility:
System Classifications:
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Compliance Inspection Report
Effective: 03/01/00 Expiration
Effective: Expiration
Title:
Certification:
Owner: Federal Home Hardee Terrace LLC
Facility: Hardee Terrace Apartments
Phone: 919-682-8426
Phone:
Inspection Date: 02/20/2018 Entry Time:
10:47AM Exit Time: 11:53AM
Primary Inspector: Jeremiah J Dow ,, ,,,, )-p- I /! Phone: 919-791-4248
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Deemed permitted collection system management and operation
Facility Status: Compliant F� Not Compliant
Question Areas:
Miscellaneous Questions Operation & Maint Reqmts Records
Monitoring & Rpting Reqmts Inspections Lines
(See attachment summary)
Page: 1
Permit: WQCSD0563 Owner • Facility: Federal Home Hardee Terrace LLC
Inspection Date: 02/20/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspection Summary:
Page: 2
Permit: WOCSDO563 Owner - Facility: Federal Home Hardee Terrace LLC
Inspection Date: 02/20/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspections
Yes No NA NE
Are maintenance records for sewer lines available?
❑
N ❑ ❑
Are records available that document pump station inspections?
❑
❑ E ❑
Are SCADA or telemetry equipped pump stations inspected at least once a week?
❑
❑ E ❑
Are non-SCADA/telemetry equipped pump stations inspected every day?
❑
❑ 0 ❑
Are records available that document citizen complaints?
❑
❑ E ❑
# Do you have a system to conduct an annual observation of entire system?
N
❑ ❑ ❑
# Has there been an observation of remote areas in the last year?
N
❑ ❑ ❑
Are records available that document inspections of high-priority lines?
❑
0 ❑ ❑
Has there been visual inspections of high-priority lines in last six months?
❑
❑ 0 ❑
Comment: One high priority line is documented in previous inspections at the back of the property and
paralleling Highway 70. At the time of this inspection the line could not be located. Mr. Whitted
believes that recent work on sewer lines at the property may have resulted in the line being
modified and placed below ground.
Operation & Maintenance Requirements
Yes No NA NE
Are all log books available? ❑ 0 ❑ ❑
Does supervisor review all log books on a regular basis? ❑ M 1:11:1
Does the supervisor have plans to address documented short-term problem areas? ❑ ❑ ❑ E
What is the schedule for reviewing inspection, maintenance, & operations logs and problem areas?
Mr. Whitted inspects the system regularly, but does not been keeping a log.
Are maintenance records for equipment available?
❑ ❑ E ❑
Is a schedule maintained for testing emergency/standby equipment?
❑ ❑ N ❑
What is the schedule for testing emergency/standby equipment?
Do pump station logs include:
Inside and outside cleaning and debris removal?
❑ ❑ ❑
Inspecting and exercising all valves?
❑ ❑ ❑
Inspecting and lubricating pumps and other equipment?
❑ ❑ ❑
Inspecting alarms, telemetry and auxiliary equipment?
❑ ❑ N ❑
Is there at least one spare pump for each pump station w/o pump reliability?
❑ ❑ E ❑
Are maintenance records for right-of-ways available?
❑ ❑ 0 ❑
Are right-of-ways currently accessible in the event of an emergency?
❑ ❑ 0 ❑
Are system cleaning records available?
❑ ❑ ® ❑
Has at least 10% of system been cleaned annually?
❑ ❑ ❑
What areas are scheduled for cleaning in the next 12 months?
Is a Spill Response Action Plan available?
❑ ❑ 0 ❑
Does the plan include:
Page: 3
Permit: WQCSD0563 Owner - Facility: Federal Home Hardee Terrace LLC
Inspection Date: 02,120/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
24-hour contact numbers
❑
❑ ■ El
Response time
❑
El . El
Equipment list and spare parts inventory
❑
El M 0
Access to cleaning equipment
E]
1:1 ■
Access to construction crews, contractors, and/or engineers
❑
❑ M ❑
Source of emergency funds
❑ M
■
Site sanitation and cleanup materials
Pipe sizes
Post-overflow/spill assessment
❑ ■ 0
■
Is a Spill Response Action Plan available for all personnel?
El ■ 0
0 ❑
Is the spare parts inventory adequate?
❑ M ❑
■
Comment: There are no manholes or pump stations associated with the system
Mr. Whitted stated that he
Approximate pipe age
would be responsible for cleanup and reporting of any overflows
❑ ■ M
Number of service taps
Records
Yes No NA NE
Are adequate records of all SSOs, spills and complaints available?
El
0 F1 M
Are records of SSOs that are under the reportable threshold available?
El
El 0 ❑
Do spill records indicate repeated overflows (2 or more in 12 months) at same location?
❑
El 0 ❑
If yes, is there a corrective action plan?
❑
El 0 ❑
Is a map of the system available?
❑ M
Does the map include:
Pipe sizes
0
❑ ■ 0
Pipe materials
❑
El ■ 0
Pipe location
El
❑ M ❑
Flow direction
❑
❑ M
Approximate pipe age
❑
❑ ■ M
Number of service taps
❑
❑ M
Pump stations and capacity
❑
El 0 ❑
If no, what percent is complete?
0
List any modifications and extensions that need to be added to the map
The collection system map needs to be developed.
# Does the permittee have a copy of their permit?
■
Comment: They are a deemed system
Monitoring and Reporting Requirements Yes No NA NE
Are copies of required press releases and distribution lists available? ❑ El ■ EJ
Are public notices and proof of publication available? El ❑ ■ ❑
# Is an annual report being prepared in accordance with G.S. 143-215.1 C?
# Is permittee compliant with all compliance schedules in the permits? .
Page: 4
Permit: WQCSD0563 Owner - Facility: Federal Home Hardee Terrace LLC
Inspection Date: 02/20/2018 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
If no, which one(s)?
Comment:
Page: 5