HomeMy WebLinkAboutNC0020605_Complaince Evaluation Inspection_20180219February 19, 2018
Michael Allen, Tarboro WWTP Supervisor
Town of Tarboro
P O Box 220
Tarboro, NC 27886
Subject Compliance Evaluation Inspection
Tarboro WWTP
NPDES Permit No NCO020605
Edgecombe County
Dear Mr Allen
ROY COOPER
(7,0ve'Jln,
MICHAEL S REGATN
4ecl etai l
LINDA CULPEPPER
h7t,171)i Drrccuu
Mitch Hayes of the Raleigh Regional Office conducted the subject inspection on February 15,
2018 Your assistance with this inspection was appreciated Below is a list of findings developed
from the inspection and review of the permit
1 The subject permit became effective March 1, 2016 and will expire September 30, 2019
Permit renewal is required within six months of permit expiration date
2 The 5 0 MGD WWTP is composed of the following units influent pump station, manual
bar screen, mechanical grit removal, splitter box, three primary clarifiers, two (2) trickling
filters, four (4) secondary clarifiers, chlorine gas disinfection, chlorine contact tank, liquid
dechlorination, cascade aeration, two (2) mechanical aeration sludge basins; an anoxic
zone sludge basin, a diffused aeration sludge basin, sludge aeration holding lagoon,
twelve (12) sludge drying beds, three (3) anaerobic digesters; three (3) aerobic digesters,
sludge truck loading station, and an on -site generator
3 At the time of inspection, one primary clarifier was not in operation due to repairs being
made to a bent scum trough One mixer was out of service in the aerobic digester and
aerated sludge holding basin One trickling filter was being operated due to low inflow
Sludge blankets in the secondary clarifiers are kept at two feet in the two smaller clarifiers
and three feet in the larger clarifiers Effluent appeared clear with no foaming at the
cascade aerator Class B biosolids are land applied by Granville Farms under Land
Application permit WQ0002047 There was no sludge in the drying beds The on -site
generator is operated once a week under load
4 The laboratory was checked in a cursory manner All instruments, meters, probes,
photometric cells are maintained in good condition Temperatures on all equipment are
checked against an MIST thermometer. All standards, reagents and consumables used
are within expiration dates The influent sampler box was 4 5 degrees C and the effluent
sampler box was 5 degrees C The fecal coliform bath was 44 5 degrees C and the BOD
incubator was 20 0 degrees C A calibration log for all meters is kept up to date Flow
meters are calibrated once a quarter The last calibration was done January 31, 2018
cornpares �..
Division of Water Re6ources, Raleigh Regional Office, Water Quality Operations Section http //portal ncdenr org/web/wq/ap9
1628 Mail Service Center, Raleigh, NC 27699-1628 Phone (919) 791-4200
Location 3800 Barrett Drive Raleigh, vC 27609 Fax (919) 788-7159
5 Discharge Monitoring Reports (DMR's) for the period August 2015 through December
2017 were reviewed for compliance with permit limit and monitoring requirements There
were no violations for the period
6 Commercial lab results, chain of custody records, and bench sheets were compared with
data submitted on the DMR for December 2017 No discrepancies were noted Tarboro
WWTP laboratory analyses fecal coliform, pH, total suspended solids, dissolved oxygen,
ammonia, TRC, BOD, COO, and settleable solids Environment One analyses TP, TKN,
NO2-N + NO3-N, and metals Pace Analytical analyses toxicity and the annual pollutant
scan
I want to thank you again for your assistance with this inspection If you have any questions about
this letter or the inspection, please contact Mitch Hayes at 919 791 4261 or by email at
Sincerely,
Danny Smith,/Regional Supervisor
Raleigh Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NC DEQ
cc permit, central files
United States Environmental Protection Agency
Form Approved
Washington, D C 20460
EPA
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A National Data System Coding (i e , PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO020605 111 121 18/02/15 I17 18 I C l 19 I G I ' 201
21111111 111111111 11 1 11 1111 I 1 11111 111111111 11 l66
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ------ ------------ -- Reserved --- —---- ---------
67
72 Lj, _LI I80
73 L75I I I I I I
70 [—] 71 it
Section B Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10 30AM 18/02/15
16/03/01
Tarboro WWTP
US Hwy 64 Bypass
Exit Time/Date
Permit Expiration Date
Tarboro NC 27886
11 30AM 18/02/15
19/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
Kevin Ray Peaden/ORC/252-641-4253/
Michael Allen//252-641-4251 /
Michael Glenn Allen/ORC/252-641-4251/
Name, Address of Responsible Official/Title/Phone and Fax Number -
Contacted
Michael AIIen,PO Box 220 Tarboro NC 278860220//252-641-4251/2526414230
Yes
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
® Permit ® Flow Measurement ® Operations & Maintenance ® Records/Reports
® Self -Monitoring Program ® Sludge Handling Disposal ® Facility Site Review Effluent/Receiving Waters
® Laboratory
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Mitchell S Hayes RRO WQ//919-791-4200/
/V r
ra)tu,,o',fMana,, ement evlewer Agency/Office/Phone and Fax Numbers Date
av/
EPA Form? 60-3 (Rev 9-94) Previous editions are obsolete
Page#
11
NPDES yr/mo/day Inspection Type (Cont)
31 NCO020605 I11 121 18/02/15 117 18 1 r
11-1
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The 5 0 MGD WWTP Is composed of the following units Influent pump station, manual bar screen,
mechanical grit removal, splatter box, three primary clarifiers, two (2) trickling filters, four (4) secondary
clarifiers, chlorine gas disinfection, chlorine contact tank, liquid dechlorinatlon, cascade aeration, two
(2) mechanical aeration sludge basins, an anoxic zone sludge basin, a diffused aeration sludge basin,
sludge aeration holding lagoon, twelve (12) sludge drying beds, three (3) anaerobic digesters, three (3)
aerobic digesters, sludge truck loading station, and an on -site generator
At the time of inspection, one primary clarlfle, was not In operation due to repairs being made to a bent
scum trough One mixer was out of service Ir the aerobic digester and aerated sludge holding basin
One trickling filter was being operated due to low Inflow Sludge blankets in the secondary clarifiers are
kept at two feet In the two smaller clarifiers and three feet In the larger clarifiers Effluent appeared clear
with no foaming at the cascade aerator Class B biosolids are land applied by Granville Farms under
Land Application permit W00002047 There was no sludge in the drying beds The on -site generator Is
operated once a week under load
The laboratory was checked In a cursory manner All instruments, meters, probes, photometric cells
are maintained In good condition Temperatures on all equipment are checked against an NIST
thermometer All standards, reagents and cons,_Imables used are within expiration dates The Influent
sampler box was 4 5 degrees C and the effluent sampler box was 5 degrees C The fecal collform bath
was 44 5 degrees C and the BOD Incubator was 20 0 degrees C A calibration log for all meters Is kept
up to date Flow meters are calibrated once a quarter The last calibration was done January 31, 2018
Discharge Monitoring Reports (DMR's) for the period August 2015 through December 2017 were
reviewed for compliance with permit limit and monitoring requirements There were no violations for the
period
Commercial lab results, chain of custody records, and bench sheets were compared with data
submitted on the DMR for December 2017 No diEcrepancles were noted Tarboro WWTP laboratory
analyses fecal collform, pH, total suspended solids, dissolved oxygen, ammonia, TRC, BOD, COD,
and settleable solids Environment One analyses TP, TKN, NO2-N + NO3-N, and metals Pace
Analytical analyses toxicity and the annual pollutant scan
Page# 2
P
Permit NCO020605 Owner - Facility Tarboro VWVTP
Inspection Date 02/1512018 Inspection Type Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑ ❑
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable ® ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment
Permit
Yes No NA
NE
(if the present permit expires in 6 months or less) Has the permittee submitted a new
❑
❑
®
❑
application?
Is the facility as described in the permit?
M
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
M
❑
❑
❑
Comment There are no special conditions
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
®
❑
❑
❑
Are all records maintained for 3 years (lab reg required 5 years)?
®
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
®
❑
❑
❑
Is the chain -of -custody complete?
®
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete do they include all permit parameters?
11
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
IN
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
M
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
IN❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
W
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
M
❑
❑
❑
Is a copy of the current NPDES permit available on site?
M
❑
❑
❑
Page# 3
Permit NC0020605 Owner - Facility Tarboro VWVTP
Inspection Date 0211512018
Inspection Type Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? ■ ❑ ❑ ❑
Comment December 2017 data checked and found no descripances in data transcription
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained %
®
❑
❑ ❑
-- ---------- --- -- - -
Are the receiving water free of foam other than trace amounts and other debris?
■
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■ ❑
Comment Effluent appeared clear with no foam entering the Tar River
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting?
®
❑
❑
❑
Is flow meter calibrated annually?
®
❑
❑
❑
Is the flow meter operational?
®
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
®
❑
❑
❑
Comment Flow meter is calibrated quarterly Last calibration was 01 31 2018
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? ❑ ® ❑ ❑
Is flow meter calibrated annually? ® ❑ ❑ ❑
Is the flow meter operational? ❑ ❑ ❑
(If units are separated) Does the chart recorder match the Tlow meter? E ❑ ❑ ❑
Comment Flow meter is calibrated guarterl
Aerobic Digester
Yes No NA NE
IN
❑
❑
❑
Is the capacity adequate?
12
❑
❑
❑
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
11
❑
❑
❑
# Is the odor acceptable?
ig
❑
❑
# Is tankage available for properly waste sludge? E ❑ ❑ ❑
Comment One mixer was not in service
Anaerobic Digester Yes No NA NE
Type of operation Fixed cover
Page# 4
A
/
Permit NCO020605
Inspection Date 02/15/2018
Owner - Facility Tarboro WVVTP
Inspection Type Compliance Evaluation
Anaerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
# Is gas stored on site?
❑
❑
.
❑
Is the digester(s) free of tilting covers?
❑
❑
0
❑
Is the gas burner operational?
❑
❑
0
❑
Is the digester heated?
❑
❑
0
❑
Is the temperature maintained constantly?
❑
❑
0
❑
Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment Digesters are operating at ambient temperatures
Drying Beds
Yes No NA NE
Is there adequate drying bed space?
®
❑
❑
❑
Is the sludge distribution on drying beds appropriate?
❑
❑
0
❑
Are the drying beds free of vegetation?
0
❑
❑
❑
# Is the site free of dry sludge remaining In beds?
0
❑
❑
❑
Is the site free of stockpiled sludge?
0
❑
❑
❑
Is the filtrate from sludge drying beds returned to the front of the plant?
0
❑
❑
❑
# Is the sludge disposed of through county landfill?
❑
0
❑
❑
# Is the sludge land applied?
®
❑
❑
❑
(Vacuum filters) Is polymer mixing adequate?
❑
❑
0
❑
Comment Class B Sludge Is land applied by Granville Farms
Pump Station - Influent
Yes No NA
NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
M
❑
❑
❑
Are all pumps present?
H
❑
❑
❑
Are all pumps operable?
IN
❑
❑
❑
Are float controls operable?
M
❑
❑
❑
Is SCADA telemetry available and operational?
❑
❑
N
❑
Is audible and visual alarm available and operational?
❑
❑
❑
Is
Comment
Bar Screens Yes No NA NE
Type of bar screen
Page# 5
Permit NC0020605
Inspection Date 0211512018
Owner - Facility Tarboro WVVTP
Inspection Type Compliance Evaluation
Bar Screens
Yes No NA NE
a Manual
i
b Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening In compliance?
®
❑
❑
❑
Is the unit in good condition?
®
❑
❑
❑
Comment
Grit Removal
Yes
No NA NE
Type of grit removal
a Manual
❑
b Mechanical
Is the grit free of excessive organic matter?
®
❑ ❑ ❑
Is the grit free of excessive odor?
®
❑ ❑ ❑
# Is disposal of grit In compliance?
®
❑ ❑ ❑
Comment
Primary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
®
❑
❑
❑
Is the site free of excessive buildup of solids In center well of circular clarifier?
®
❑
❑
❑
Are weirs level?
®
❑
❑
❑
Is the site free of weir blockage?
®
❑
❑
❑
Is the site free of evidence of short-circuiting?
E
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
M
❑
❑
❑
Is the drive unit operational?
E
❑
❑
❑
Is the sludge blanket level acceptable?
H
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/< of the sldewall depth)
❑
❑
❑
Comment
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
IN
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
E
❑
❑
❑
Page# 6
1
Permit NCO020605 Owner - Facility Tarboro VVWTP
Inspection Date 02/15/2018 Inspection Type Compliance Evaluation
Secondary Clarifier
Yes No NA NE
Are weirs level?
❑
❑
❑
i
Is the site free of weir blockage?
❑
❑
❑
■
Is the site free of evidence of short-circuiting?
❑
❑
❑
Is scum removal adequate?
■
❑
❑
❑
Is the site free of excessive floating sludge?
■
❑
❑
❑
Is the drive unit operational?
i
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
®
❑
❑
❑
Comment weirs are covered preventing Inspection
Disinfection -Gas
Yes No NA
NE
Are cylinders secured adequately?
®
❑
❑
❑
Are cylinders protected from direct sunlight?
®
❑
❑
❑
Is there adequate reserve supply of disinfectant?
®
❑
❑
❑
Is the level of chlorine residual acceptable?
®
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
®
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
®
❑
❑
❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No 7782-50-5)?
❑
❑
®
❑
If yes, then is there a Risk Management Plan on site?
❑
❑
®
❑
If yes, then what is the EPA twelve digit ID Number? (1 000--�
If yes, then when was the RMP last updated?
Comment
De -chlorination
Yes No NA NE
Type of system ?
Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
®
❑
❑
❑
Is storage appropriate for cylinders?
❑
❑
11
❑
# Is de -chlorination substance stored away from chlorine containers?
K
❑
❑
❑
Are the tablets the proper size and type?
❑
❑
IN
❑
Comment Powdered Sodium metabisulphite is made into a solution and stored Into two large vessels
Are tablet de-chlonnators operational? ❑ ❑ ❑
Number of tubes in use?
Page# 7
Permit NC0020605
owner -Facility Tarboro WVVTP
Inspection Date 02/15/2018
Inspection Type Compliance Evaluation
De -chlorination Yes No NA NE
Comment
Standby Power
Yes
No NA NE
Is automatically activated standby power available?
N
❑
❑
❑
Is the generator tested by Interrupting primary po'Ner source?
®
❑
❑
❑
®
❑
❑
❑
Is the generator tested under load?
Was generator tested & operational during the Inspection?
❑
®
❑
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
®
❑
❑
❑
®
❑
❑
❑
Is the generator fuel level monitored?
Comment Generator is operated under load once a week
Pumps-RAS-WAS
Yes No NA NE
®❑
❑
❑
Are pumps in place?
❑
®
❑
❑
Are pumps operational?
Are there adequate spare parts and supplies on site?
®
❑
❑
❑
Comment One out of three pumps were operational
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or labcratory?
9
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
9
❑
❑
❑
❑
❑
❑
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
11
❑
❑
❑
Celsius)?
El
El
El
Incubator (Fecal Coliform) set to 44 5 degrees Celsius+/- 0 2 degrees?
Incubator (BOD) set to 20 0 degrees Celsius +/- 1 0 degrees?
Is
❑
❑
❑
Comment Tarboro VWVFP laboratory analyses fecal conform pH total suspended solids dissolved
oxVqen, ammonia TRC BOD COD and settleable solids Environment One analyses TP,
TKN NO2 N + NO3 N and metals Pace Anaiviical analyses toxicity
and the annual
pollutant scan
Disinfection -Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant? ❑ ❑ 2 ❑
(Sodium Hypochlorite) Is pump feed system operational? IM ❑ ❑ ❑
Is bulk storage tank containment area adequate? (free of leaks/open drains) N ❑ ❑ ❑
Page#
Permit NCO020605
Inspection Date 02/15/2018
Owner - Facility Tarboro VWVTP
Inspection Type Compliance Evaluation
Disinfection -Liquid
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlonnatlon?
Comment Chlorine gas Is used for disinfection
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Is sampling performed according to the permit?
Comment
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment
Yes No NA NE
® ❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
Yes No NA NE
Page# 9