HomeMy WebLinkAboutNC0032867_NOV2018PC0030_20180218Water Resources
NVIRONMENTAL QUALITY
16 February 2018
CERTIFIED MAIL # 7015 1370 0000 2596 0184
RETURN RECEIPT REQUESTED
Laeeq Khan, President
Malik's International, Inc.
3425 Carnoustie Drive
Chambersburg, PA 17202
ROY COOPER
Governor
MICHAEL S REGAN
Secretary
LINDA CULPEPPER
Interim Director
RECEIVEDIDENRIDWR
FEB 2 8 2018
Water Resources
Permitting Section
Subject: Notice of Continuing Violation and Recommendation for Enforcement
Tracking Number NOV-2018-PC-0030
Kings Mountain Travel Plaza WWTP
NPDES Permit NCO032867
Cleveland County
Dear Mr. Khan:
Please find enclosed the Compliance Evaluation Inspection conducted on February 1, 2018 by Mr. Andrew Pitner
and Ori Tuvia of the Mooresville Regional Office. Your cooperation during the site visit, along with that of Ron
Haynes, was much appreciated.
At the time of the inspection the following violations were observed and need to be addressed:
1. In accordance with Part II, Section D.6 of the subject permit, (Records and Retention), "Except for
records monitoring information required by this permit related to the Permittee's sewage sludge use
and disposal activities, which shall be retained for a period of at least five years (or longer as required
by 40 CFR 503), the Permittee shall retain records of all monitoring information including":
• All calibration and maintenance records;
• All original strip chart recording of continuous monitoring instrumentation;
• Copies of all reports required by the permit;
• Copies of all data used to complete the application for this permit.
These records or copies shall be maintained for a period of at least three (3) years from the date of
the sample, measurement, report or application. At the time of the inspection, no records were
available for review for the period August 1, 2014 through August 1, 2017. It is the duty of the
Mooresville Regional Office
Location 610 East Center Ave , Suite 301 Mooresville, NC 28115
Phone (704) 663-1699 � Fax (704)663-60401 Customer Service 1-877-623-6748
k
permittee to maintain all records for a least three (3) years. The records that were unavailable
include:
• Discharge Monitoring Reports (DMRs);
• Lab results with Chain of Custody;
• Flow meter readings;
• pH and other relevant instrument calibration records;
• ORC log (including visitation records);
• Septic tank pumping records;
• Maintenance logs.
At the time of the inspection and in addition to the missing records, the facility had failed to submit eDMRs for
the period of September 2017, October 2017, November 2017, and December 2017.
2. In accordance with Part II, Section C.2 of the subject permit, proper Operation and Maintenance
(0&M) of the WWTP is required. As noted at the time of the inspection, the following areas of
concern should be addressed:
• septic tank must be properly sealed to avoid leaking wastewater to the ground;
• The facility flow meter has not been calibrated in over one (1) year.
You are requested to resolve the following issues:
1. Pump all wastewater from the ground to either the wastewater treatment plant or to an approved
disposal location by a licensed hauler. As per meeting conducted February 16, 2018, it was indicated
by the permitee that the issue was resolved.
2. Leaking septic tanks observed February 1, 2018, have been bypassed as indicated on February 16,
2018. Continued visual monitoring should be conducted until such time as the tanks are officially
removed from the treatment component listed in the permit.
3. Submit all missing eDMRs, within 30 days of receipt of this letter;
4. Obtain missing records (noted below) for the period August 1, 2014 through August 1, 2017, within
60 days of receipt of this letter;
• Discharge Monitoring Reports (DMRs)
• Lab results with Chain of Custody
• Flow meter readings
• pH and other relevant instrument calibration records
• ORC log (including visitation records)
• Septic tank pumping records
• Maintenance logs
5. Calibrate the flow meter, within 30 days of receipt of this letter.
A Notice of Violation and Notice of Recommendation for Enforcement, pursuant to G.S. 143-215.6A, may result
in a civil penalty of not more than twenty-five thousand dollars ($25,000.00) per day, per violation and may be
assessed against any person who violates or fails to act in accordance with the terms, conditions, or
requirements of any permit issued pursuant to G.S. 143-215.1.
4'
Thank you for your attention to this matter. Please understand the severity of the violations detailed above, which
put surface waters and the public health at risk. This office requires that these violations be abated
immediately. Please note that these violations and any future violations are subject to civil penalty
assessments of up to $25,000.00 per day, per violation. Your response to this correspondence will be
considered in this process. Should you have any questions regarding this matter, please contact Ori Tuvia or
me at (704) 663-1699.
Sincerely,
.
wr� T.R. JW. - N-
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
Cc: Ron Haynes (E -copy)
NPDES (Derek Denard)
MRO Files
Cleveland County Health Department
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A National Data System Coding (i e , PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 1 1 3 I NCO032867 I11 121 18/02/01 I17 18 I S I 19 I S I 20I
LL1 -
211
1 1 11=1 1 1 1 1 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 1 J I I I r6
Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA Reserved
67 1 0 70 72 _n_] 73 80
174 751 I I I I I
71 L]
_L
Section B Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09 50AM 18/02/01
14/01/01
Kings Mountain Travel Plaza
Exit Time/Date
permit Expiration Date
400 Dixon School Rd
11 45P 18/02/01
18/08/31
Kings Mountain NC 28086
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Ron Haynes/Operator/704-824-3518/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Laeeq Khan,PO Box 805 Kings Mtn NC
No
280860805/P res ident/704-739-6415!7047390732
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance N Records/Reports
Self-Monitonng Program 0 Facility Site Review Effluent/Receiving Waters
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Andrew Pitney MRO WQ/1704-663-1699 EM 2180/
On A Tuvia MRO WQ//704-663-1699/
21161)? � � �� /
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W Corey Basinger MRO WQ//704-235-2194/
EPA For 560-3 (Rev g04) Previous ed
itions
are obsolete A
® C zv's.-
Page# 1
NPDES yr/mo/day Inspection Type
31 NCo032867 I11 121 18/02/01 117 18 ICI
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) +
1
Page# 2
Permit NCO032867 Owner - Facility Kings Mountain Travel Plaza
Inspection Date 02/01/2018 Inspection Type Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted a new 0 ❑ ❑ ❑
application?
Is the facility as described in the permit?
0
❑ ❑
❑
# Are there any special conditions for the permit?
❑
0 ❑
❑
Is access to the plant site restricted to the general public?
E
❑ ❑
❑
Is the Inspector granted access to all areas for inspection?
0
❑ ❑
❑
Comment Previous inspection conducted on 11/02/2017 resulted in an Notice of Continuing
Violation
❑
(NOV -2017-PC-0602)
0
❑
Is the chain -of -custody complete?
The facility permit will expire on 08/31/2018 a permit renewal has not been submitted at this
❑
time
❑
Dates, times and location of sampling
❑
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ 0 ❑ ❑
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable ❑ 0 ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment ORC log were not avilable for review for the period of August 2014 - August 2017
At the time of theinspection the following operational issues were noted Untreated
wastewater had accumulated on the ground beside the leaking septic tanks
The microbial population in the operable aeration basin appeared very low
Flow meter had not been calibrated in over a year
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
❑
0
❑
❑
Is all required Information readily available, complete and current?
❑
N
❑
❑
Are all records maintained for 3 years (lab reg required 5 years)?
❑
❑
0
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
0
❑
Is the chain -of -custody complete?
❑
❑
0
❑
Dates, times and location of sampling
❑
Name of individual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses ❑
Transported COCs ❑
Are DMRs complete do they include all permit parameters? ❑ ❑ 0 ❑
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ E ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ E ❑
on each shift?
Page# 3
Permit NCO032867 Owner - Facility Kings Mountain Travel Plaza
2017 -
# Is flow meter used for reporting?
❑
Inspection Date 02/01/2018 Inspection Type Compliance Evaluation
N
❑
Is flow meter calibrated annually?
❑
Record Keeping
Yes No NA NE
Is the ORC visitation log available and current?
❑
0
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
0
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
N
❑
Is a copy of the current NPDES permit available on site?
❑
❑
0
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment No recoreds were avilable for review for the period of Auqust 1, 2014 - Auqust 1, 2017 At the
time of the Inspection the facllllty has not submitted EDMR for the months of August
2017 -
# Is flow meter used for reporting?
❑
November 2017
N
❑
Is flow meter calibrated annually?
❑
Septic Tank
Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
❑
0
❑
❑
Is septic tank pumped on a schedule-,
❑
❑
0
❑
Are pumps or syphons operating properly?
❑
E
❑
❑
Are high and low water alarms operating properly?
❑
❑
N
❑
Comment Septic tanks had cracks, waste water leached has was evident by the untreated wastewater
that had accumulated on the ground beside the leaking septic tanks
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
❑
❑
N
❑
Is flow meter calibrated annually?
❑
❑
❑
Is the flow meter operational?
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment Flow meter had not been calibrated In over a year
Page# 4
I