HomeMy WebLinkAboutWQCSD0148_Compliance Evaluation Inspection_20180215February 15, 2018
Chuck Powell, Sr EHS Specialist
Environmental Health & Safety
Pfizer Inc
4300 Oak Park
Sanford, NC 27330
ROY COOPER
rover nor
MICHAEL S REGAN
Secrctary
LINDA CULPEPPER
Interim Director
RECENEDIDENRIDWR
FEB %I ZgiB
Water Re,30urc s
Subject Compliance Evaluation Inspection Permitbn9
on
Wyeth (Pfizer) Collection System— WQCSD0148
Lee County
Dear Mr Powell,
Andy Neal of the Raleigh Regional Office conducted a compliance evaluation inspection on February 14, 2018
Your assistance, along with that of Mr Roy McDevitt, maintenance lead, Mr Connor Jarvis, EHS associate, and
Mr Randy Heard, utilities technician, was greatly appreciated Please find the attached Basin Wide Information
Management System (BIMS) inspection checklist summarizing the inspection Findings during the inspection
were as follows
WQCSDO148 Wyeth (Pfizer) Collection System Compliance Inspection Evaluation
All wastewater flow is conveyed to the City of Sanford wastewater collection system (WQCS00047) and
is treated-afthe City of Sanford wastewater treatment plant (NC0024147)
2 Grease traps in the kitchen area are pumped out every 90 days An email is sent to Melame Pruitt with
Sodexho every January and July reminding the kitchen staff to pump out grease traps. Documentation is
kept on computer
DWR records indicate that there has not been any sanitary sewer overflows (SSOs) reported for the
subject collection
4. The entire collection system is observed and inspected once a year There is one high priority line that is
inspected weekly
There are six pump stations in the collection system All pump stations have secured access, audible /
visual alarms, telemetry, and emergency contact information signs Alarms operated when the high-water
float was lifted Status of all wet wells and pump stations is monitored by a Delta V computer system
Information is sent to a monitoring station in a control room All wet wells exhibited very little to no
waste build up. Pump stations are connected to on-site generators which are check for leaks, etc weekly
and exercised once a month.
�` N ci t h ing Cornparos :�_
State ofNorth Carolina I Environmental Quality I Water Resources I Raleigh Regional Office
1628 Mail service Center I Ralei.gii, North Carolina 27699-1628
•0
.- -,.- -.. �.✓� 3rkra� '�' �f � �' '� t'S;e.� �P ��" �4� � a c Xz'�m %, 01
'� q ,,� ,� �u:�l, ���'�, „ _ �.,,�„_.».� fes; �� �� "�^�`, , <r �-�,..���vw�.�„r� . �,,, �� �€ r �'�.,s,, �,n,,,k . -•+
Wyeth (Pfizer) Collection System — WQCSDO148
Compliance Evaluation Inspection — page 2 of 2
Thank you for your time and assistance with this inspection If you have any questions about this inspection or
this letter, please contact Andy Neal at ands n-eal;u ncdenr ,o,, or 919-791-4200
Sincerely,
Danny Smith
Water Quality Regional Operations
Raleigh Regional Office
cc Central Files
RRO File
Compliance Inspection Report
Permit WQCSD0148 Effective 03/01/00 Expiration
SOC Effective Expiration
County Lee
Region Raleigh
Contact Person J Kenneth Taft Title
Directions to Facility
System Classifications
Primary ORC Certification
Secondary ORC(s)
On -Site Representative(s)
Related Permits
WQCS00047 City Of Sanford - Sanford Collection System
NC0024147 City Of Sanford - Big Buffalo WWTP
Inspection Date 02/14/2018 Entry Time 01 OOPM
Primary Inspector Andrew W Neal
Secondary Inspector(s)
Owner Wyeth LLC
Facility Wyeth Collection System
Phone 919-775-7100
Phone
Exit Time 02 30PM
Phone 919-79114248
Reason for Inspection Routine Inspection Type. Collection System Inspect Non Sampling
Permit Inspection Type Deemed permitted collection system management and operation
Facility Status ® Compliant F� Not Compliant
Question Areas
® Miscellaneous Questions ® Performance Standards ® Operation & Maint Reqmts
® Records ® Inspections ® Pump Station
(See attachment summary)
Page 1
Permit WQCSDO148 Owner - Facility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
Inspection Summary
All wastewater flow is conveyed to the City of Sanford wastewater collection system (WQCS00047) and is treated at the
City of San-ord wastewater treatment plant (NC0024147)
- - -Grease traps in the kitchen area are pumped out every 90 days An email is sent to Melanie Pruitt with Sodexho every
January and July reminding the kitchen staff to pump cut grease traps Documentation is kept on computer
DWR records Indicate that there has not been any sanitary sewer overflows (SSOs) reported for the subject collection
The entire collection system is observed and Inspected once a year There Is one high priority line that Is Inspected weekly,
more or less
There a -e six pump stations In the collection system All pump stations have secured access, audible / visual alarms,
telemety, and emergency contact Information signs Alarms operated when the high water float was lifted up Status of all
wet weds and pump stations Is monitored by a Delta V computer system Information is sent to a monitoring station In a
control room All wet wells exhibited very little to no waste build up Pump stations are connected to on-site generators
which are check for leaks, etc weekly and exercised once a month
Page 2
Permit WQCSDO148 Owner - Facility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
Performance Standards Yes No NA NE
Is Public Education Program for grease established and documented? N ❑ ❑ ❑
What educational tools are used?
Email sent to cafeteria staff (Melanie Pruitt with Sodexho) to pump out grease traps first week of January and
first week of July of each year
Is Sewer Use Ordinance/Legal Authority available? ® 1:11:1 ❑
Does it appear that the Sewer Use Ordinance is enforced? ❑ ❑ ❑
Is Grease Trap Ordinance available? 0 ❑ ❑ ❑
Is Septic Tank Ordinance available (as applicable, i e annexation) ❑ ❑ ■ ❑
List enforcement actions by permittee, if any, in the last 12 months
NA
Has an acceptable Capital Improvement Plan (CIP) been implemented?
❑ ❑ E ❑
Does CIP address short term needs and long term \"master plan\" concepts?
❑ ❑ ® ❑
Does CIP cover three to five year period?
❑ ❑ ® ❑
Does CIP include Goal Statement?
❑ ❑ N ❑
Does CIP include description of project area?
❑ ❑ E ❑
Does CIP include description of existing facilities?
❑ ❑ ■ ❑
Does CIP include known deficiencies?
❑ ❑ ■ ❑
Does CIP include forecasted future needs?
❑ ❑ ■ ❑
Is CIP designated only for wastewater collection and treatment?
❑ ❑ ® ❑
Approximate capital improvement budget for collection system?
Total annual revenue for wastewater collection and treatment?
CIP Comments
NA
Is system free of known points of bypass? ® ❑ ❑ ❑
If no, describe type of bypass and location
Is a 24-hour notification sign posted at ALL pump stations? ® ❑ ❑ ❑
# Does the sign include
Instructions for notification? ® ❑ ❑ ❑
Pump station identifier? ® ❑ ❑ ❑
24-hour contact numbers 0 ❑ ❑ ❑
If no, list deficient pump stations
# Do ALL pump stations have an "auto polling" feature/SCADA? ® ❑ ❑ ❑
Number of pump stations 6
Number of pump stations that have SCADA 0
Number of pump stations that have simple telemetry 6
Number of pump stations that have only audible and visual alarms 0
Page 3
Permit WQCSDO148 Owner • Facility Wyeth LLC
Inspect,on Date 02/14/2018 Inspectio-i Type Collection System Inspect Non Sampling Reason for Visit Routine
Number of pump stations that do not meet permit requirements 0
# Does the permittee have a root control program? ❑ ❑ M ❑
# If yes, date implemented?
Describe
Comment — - - --- - _ - -
Inspections
Yes No NA NE
Are maintenance records for sewer lines available?
®
❑ ❑ ❑
Are records available that document pump station inspec'ions?
®
❑ ❑ ❑
Are SCADA or telemetry equipped pump stations inspected at least once a week?
■
❑ ❑ ❑
Are non-SCADA/telemetry equipped pump stations inspected every day?
❑
❑ ® ❑
Are records available that document citizen complaints-,
❑
❑ ® ❑
# Do you have a system to conduct an annual observation of entire system?
®
❑ ❑ ❑
# Has there been an observation of remote areas in the last year?
■
❑ ❑ ❑
Are records available that document inspections of hich-pnority lines?
®
❑ ❑ ❑
Has t-lere been visual inspections of high-priority lines in last six months?
®
❑ ❑ ❑
Comment
9
❑ ❑ ❑
Operation & Maintenance Requirements
Yes No NA NE
Are all log books available?
®
❑ ❑ ❑
Does supervisor review all log books on a regular basis?
®
❑ ❑ ❑
Does the supervisor -have plans to address documented short-term problem areas?
®
❑ ❑ ❑
What is the schedule for reviewing inspection, maintenance, & operations logs and problem areas?
Weekly All information is logged electronically
Are maintenance records for equipment available?
®
❑ ❑ ❑
Is a schedule maintained for testing emergencylstandby equipment?
®
❑ ❑ ❑
What is the schedule for testing emergency/standby equipment?
Do pump station logs include
Inside and outside cleaning and debris removal?
9
❑ ❑ ❑
Inspecting and exercising all valves?
M
❑ ❑ ❑
Inspecting and lubricating pumps and other equipment?
18
❑ ❑ ❑
Inspecting alarms, telemetry and auxiliary equipment?
N
❑ ❑ ❑
Is there at least one spare pump for each pump station w/o pump reliability?
11
❑ ❑ ❑
Are maintenance records for right-of-ways available?
❑
❑ 12 ❑
Are right-of-ways currently accessible in the event of an emergency?
❑
❑ 0 ❑
Are system cleaning records available?
❑
❑ IN ❑
Has at least 10% of system been cleaned annually?
❑
❑ ❑
What areas are scheduled for cleaning in the next 12 months?
Page 4
Permit WQCSDO148 Owner - Facility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling
Reason for Visit Routine
Is a Spill Response Action Plan available?
M ❑ ❑ ❑
Does the plan include
❑ ❑ M ❑
24-hour contact numbers
❑ ❑ ❑
Response time
0 ❑ ❑ ❑
Equipment list and spare parts inventory
0 ❑ ❑ ❑
Access to cleaning equipment
M ❑ ❑ ❑
Access to construction crews, contractors, and/or engineers
M ❑ ❑ ❑
Source of emergency funds
0 ❑ ❑ ❑
Site sanitation and cleanup materials
0 ❑ ❑ ❑
Post-overflow/spill assessment
M ❑ ❑ ❑
Is a Spill Response Action Plan available for all personnel?
■ ❑ ❑ ❑
Is the spare parts inventory adequate?
® ❑ ❑ ❑
Comment
®❑ ❑ ❑
Records
Yes No NA NE
Are adequate records of all SSOs, spills and complaints available?
❑ ❑ M ❑
Are records of SSOs that are under the reportable threshold available?
❑ ❑ M ❑
Do spill records indicate repeated overflows (2 or more in 12 months) at same location?
❑ ❑ ® ❑
If yes, is there a corrective action plan?
❑ ❑ ® ❑
Is a map of the system available?
❑ ❑ ❑
Does the map include
Pipe sizes
® ❑ ❑ ❑
Pipe materials
® ❑ ❑ ❑
Pipe location
® ❑ ❑ ❑
Flow direction
® ❑ ❑ ❑
Approximate pipe age
® ❑ ❑ ❑
Number of service taps
® ❑ ❑ ❑
Pump stations and capacity
®❑ ❑ ❑
If no, what percent is complete?
List any modifications and extensions that need to be added to the map
# Does the permittee have a copy of their permit?
❑ ❑ M ❑
Comment
BUILDING 107 -
Pump Station
Yes No NA NE
Pump station type Duplex
Are pump station logs available? ® ❑ ❑ ❑
Is it accessible in all weather conditions? im ❑ ❑ ❑
Page 5
Permit WQCSDO148 Owner - cacility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
# Is general housekeeping acceptable?
Are all pumps present?
Are all pumps operable?
Are wet wells free of excessive debris?
Are upstream manholes free of excessive debris/signs of overflow?
Are floats/controls for pumps/alarms operable?
Is "auto polling" feature/SCADA present?
Is "auto polling" feature/SCADA operational?
Is simple telemetry present?
Is simple telemetry operational?
Are audio and visual alarms present?
Are audio and visual alarms operable?
Is the Pump station inspected as required?
Are backflow devices in place?
Are backflow devices operable?
Are air relief valves in place?
Are air relief valves operable?
# Is an emergency generator available?
Can the emergency generator run the pumps?
Is the pump station equipped for quick hook-up?
Is the generator operable?
# Is fuel in tank and sufficient?
Is the generator inspected according to their schedule?
Is a 24-hour notification sign posted?
Does it include
Instructions for notification?
Pump station identifier?
Emergency phone number
Is public access limited?
Is pump station free of overflow piping?
Is the pump station free of signs of overflow?
Are run times comparable for multiple pumps?
Comment
BUILDING 116 -
Pump Station
Pump station type
0 ❑ ❑ ❑
0
❑ ❑ ❑
®
❑ ❑ ❑
- 0-❑
N 0
■❑❑❑
❑
❑ M ❑
❑
❑ 0 ❑
•
❑ ❑ ❑
0
❑ ❑ ❑
0
❑ ❑ ❑
0
❑ ❑ ❑
0
❑ ❑ ❑
■❑❑❑
0❑❑❑
❑❑0❑
❑
❑ 0 ❑
0
❑ ❑ ❑
0
❑ ❑ ❑
❑❑ME]
0
❑ ❑ ❑
®
❑ ❑ ❑
0❑❑❑
0011❑
Yes No NA NE
Duplex
Page 6
Permit WQCSD0148 Owner -Facility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling
Reason for Visit Routine
Are pump station logs available?
0 ❑ ❑ ❑
Is it accessible in all weather conditions?
i ❑ ❑ ❑
# Is general housekeeping acceptable?
M ❑ ❑ ❑
Are all pumps present?
i ❑ ❑ ❑
Are all pumps operable?
0 ❑ ❑ ❑
Are wet wells free of excessive debris?
0 ❑ ❑ ❑
Are upstream manholes free of excessive debris/signs of overflow?
M ❑ ❑ ❑
Are floats/controls for pumps/alarms operable?
® ❑ ❑ ❑
Is "auto polling" feature/SCADA present?
❑ ❑ 0 ❑
Is "auto polling" feature/SCADA operational?
❑ ❑ 0 ❑
Is simple telemetry present?
M ❑ ❑ ❑
Is simple telemetry operational?
0 ❑ ❑ ❑
Are audio and visual alarms present?
® ❑ ❑ ❑
Are audio and visual alarms operable?
® ❑ ❑ ❑
Is the Pump station inspected as required?
® ❑ ❑ ❑
Are backflow devices in place?
® ❑ ❑ ❑
Are backflow devices operable?
® ❑ ❑ ❑
Are air relief valves in place?
❑ ❑ ® ❑
Are air relief valves operable?
❑ ❑ ® ❑
# Is an emergency generator available?
® ❑ ❑ ❑
Can the emergency generator run the pumps?
® ❑ ❑ ❑
Is the pump station equipped for quick hook-up?
❑ ❑ ® ❑
Is the generator operable?
® ❑ ❑ ❑
# Is fuel in tank and sufficient?
® ❑ ❑ ❑
Is the generator inspected according to their schedule?
® ❑ ❑ ❑
Is a 24-hour notification sign posted?
® ❑ ❑ ❑
Does it include
Instructions for notification?
Pump station identifier?
Emergency phone number
Is public access limited?
Is pump station free of overflow piping?
Is the pump station free of signs of overflow?
Are run times comparable for multiple pumps?
Comment
BUILDING 114 -
® ❑ ❑ ❑
❑ ❑ ❑
11 ❑ ❑ ❑
11 ❑ ❑ ❑
Page 7
Permit WQCSD0148 Owner - Faz:ility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling
Reason for Visit Routine
Pump Station
Yes No NA NE
Pump station type
Duplex
Are pump station logs available?
❑ ❑ ❑
Is it accessible in all weather conditions?
❑ ❑ ❑
----- -- - # Is general -housekeeping acceptable?
- ❑ ❑ ❑ -
Are all pumos present?
❑ ❑ ❑
Are all pumps operable?
M ❑ ❑ ❑
Are wet wells free of excessive debris?
M ❑ ❑ ❑
Are upstream manholes free of excessive debris/signs of overflow?
❑ ❑ 0 ❑
Are floats/controls for pumps/alarms operable?
■ ❑ ❑ ❑
Is "auto polling" feature/SCADA present?
❑ ❑ ® ❑
Is "auto polling" feature/SCADA operational?
❑ ❑ ® ❑
Is simple telemetry present?
M ❑ ❑ ❑
Is simple telemetry operational?
® ❑ ❑ ❑
Are audio and visual alarms present?
® ❑ ❑ ❑
Are a.idio and visual alarms operable?
® ❑ ❑
Is the Pump station inspected as required?
® ❑ ❑ ❑
Are backflow devices in place?
® ❑ ❑ ❑
Are backflow devices operable?
® ❑ ❑ ❑
Are air relief valves in place?
❑ ❑ ® ❑
Are air relief valves operable?
❑ ❑ ® ❑
# Is an emergency generator available?
® ❑ ❑ ❑
Can the emergency generator run the pumps'
® ❑ ❑ ❑
Is the pump station equipped for quick hook -tip?
❑ ❑ ® ❑
Is the generator operable?
® ❑ ❑ ❑
# Is fuel in tank and sufficient?
® ❑ ❑ ❑
Is the generator inspected according to their schedule?
® ❑ ❑ ❑
Is a 24-hour notification sign posted?
a ❑ ❑ ❑
Does It include
Instructions for notification? M ❑ ❑ ❑
Pump station identifier? Is ❑ ❑ ❑
Emergency phone number 0 ❑ ❑ ❑
Is public access limited? B ❑ ❑ ❑
Is pump station free of overflow piping? M ❑ ❑ ❑
Is the pump station free of signs of overflow? N ❑ ❑ ❑
Are run times comparable for multiple pumps?
Page 8
Permit WQCSDO148 Owner . Facility Wyeth LLC
IN ❑ ❑ ❑
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling
Reason for Visit Routine
Comment
11 ❑ ❑ ❑
BUILDING 110 -
9 ❑ ❑ ❑
Pump Station
Yes No NA NE
Pump station type
Duplex
Are pump station logs available?
■ ❑ ❑ ❑
Is It accessible In all weather conditions?
M ❑ ❑ ❑
# is general housekeeping acceptable?
E ❑ ❑ ❑
Are all pumps present?
0 ❑ ❑ ❑
Are all pumps operable?
E ❑ ❑ ❑
Are wet wells free of excessive debris?
0 ❑ ❑ ❑
Are upstream manholes free of excessive debris/signs of overflow?
0 ❑ ❑ ❑
Are floats/controls for pumps/alarms operable?
■ ❑ ❑ ❑
Is "auto polling" feature/SCADA present?
❑ ❑ ® ❑
Is "auto polling" feature/SCADA operational?
❑ ❑ ❑
Is simple telemetry present?
■ ❑ ❑ ❑
Is simple telemetry operational?
0 ❑ ❑ ❑
Are audio and visual alarms present?
® ❑ ❑ ❑
Are audio and visual alarms operable?
❑ ❑ ❑
Is the Pump station inspected as required?
❑ ❑ ❑
Are backflow devices in place?
® ❑ ❑ ❑
Are backflow devices operable?
® ❑ ❑ ❑
Are air relief valves in place?
❑ ❑ ® ❑
Are air relief valves operable?
❑ ❑ ® ❑
# Is an emergency generator available?
® ❑ ❑ ❑
Can the emergency generator run the pumps?
® ❑ ❑ ❑
Is the pump station equipped for quick hook-up?
❑ ❑ ® ❑
Is the generator operable?
® ❑ ❑ ❑
# is fuel in tank and sufficient?
® ❑ ❑ ❑
Is the generator inspected according to their schedule?
H ❑ ❑ ❑
Is a 24-hour notification sign posted?
® ❑ ❑ ❑
Does it include
Instructions for notification?
IN ❑ ❑ ❑
Pump station Identifier?
M ❑ ❑ ❑
Emergency phone number
11 ❑ ❑ ❑
Is public access limited?
9 ❑ ❑ ❑
Is pump station free of overflow piping?
E ❑ ❑ ❑
Page 9
Permit WQCSDO148 Owner -Facility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
Is the pump station free of signs of overflow? ® ❑ ❑ ❑
Are run times comparable for multiple pumps?
Comment
PH EFFLUENT -
Purtip Stailoll —
Yes No NA NE
Pump statin type
Duplex
Are pump station logs available?
M ❑ ❑ ❑
Is it accessible in all weather conditions?
M ❑ ❑ ❑
# Is general housekeeping acceptable?
■ ❑ ❑ ❑
Are all pimps present?
® ❑ ❑ ❑
Are all pumps operable?
® ❑ ❑ ❑
Are we: wells free of excessive debris?
® ❑ ❑ ❑
Are upstream manholes free of excessive debris/signs of overflow?
® ❑ ❑ ❑
Are floats/controls for pumps/alarms operable?
® ❑ ❑ ❑
Is "auto polling" feature/SCADA present?
❑ ❑ M ❑
Is "auto polling" feature/SCADA operational?
❑ ❑ M ❑
Is simple telemetry present?
® ❑ ❑ ❑
Is s mple telemetry operational?
® ❑ ❑ ❑
Are audio and visual alarms present?
■ ❑ ❑ ❑
Are audio and visual alarms operable?
® ❑ ❑ ❑
Is the Pump station inspected as required?
® ❑ ❑ ❑
Are backflow devices in place?
® ❑ ❑ ❑
Are backflow devices operable?
® ❑ ❑ ❑
Are air relief valves in place?
❑ ❑ ® ❑
Are air relief valves operable?
❑ ❑ ® ❑
# Is an emergency generator available?
® ❑ ❑ ❑
Can the emergency generator run the pumps?
0 ❑ ❑ ❑
Is the pump station equipped for quick hook-up?
❑ ❑ ® ❑
Is the generator operable?
a ❑ ❑ ❑
# Is fuel in tank and sufficient?
® ❑ ❑ ❑
Is the generator inspected according to their schedule?
M ❑ ❑ ❑
Is a 24-hour notification sign posted?
® ❑ ❑ ❑
Does It Include
Instructions for notification?
® ❑ ❑ ❑
Pump station identifier?
M ❑ ❑ ❑
Emergency phone number
8 ❑ ❑ ❑
Page 10
Permit WQCSDO148 Owner - Facility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
Is public access limited? E ❑ ❑ ❑
Is pump station free of overflow piping? ■ ❑ ❑ ❑
Is the pump station free of signs of overflow? ■ ❑ ❑ ❑
Are run times comparable for multiple pumps?
Comment
BUILDING 101 -
Pump Station
Yes No NA NE
Pump station type
Duplex
Are pump station logs available?
® ❑ ❑ ❑
Is it accessible in all weather conditions?
® ❑ ❑ ❑
# Is general housekeeping acceptable?
® ❑ ❑ ❑
Are all pumps present?
M ❑ ❑ ❑
Are all pumps operable?
® ❑ ❑ ❑
Are wet wells free of excessive debris?
® ❑ ❑ ❑
Are upstream manholes free of excessive debris/signs of overflow?
® ❑ ❑ ❑
Are floats/controls for pumps/alarms operable?
® ❑ ❑ ❑
Is "auto polling" feature/SCADA present?
❑ ❑ ® ❑
Is "auto polling" feature/SCADA operational?
❑ ❑ ® ❑
Is simple telemetry present?
® ❑ ❑ ❑
Is simple telemetry operational?
® ❑ ❑ ❑
Are audio and visual alarms present?
® ❑ ❑ ❑
Are audio and visual alarms operable?
® ❑ ❑ ❑
Is the Pump station inspected as required?
® ❑ ❑ ❑
Are backflow devices in place?
19 ❑ ❑ ❑
Are backflow devices operable?
® ❑ ❑ ❑
Are air relief valves in place?
❑ ❑ ® ❑
Are air relief valves operable?
❑ ❑ ® ❑
# Is an emergency generator available?
® ❑ ❑ ❑
Can the emergency generator run the pumps?
9❑ ❑ ❑
Is the pump station equipped for quick hook-up?
❑ ❑0 ❑
Is the generator operable?
0 ❑ ❑ ❑
# Is fuel in tank and sufficient?
N ❑ ❑ ❑
Is the generator inspected according to their schedule?
M ❑ ❑ ❑
Is a 24-hour notification sign posted?
M ❑ ❑ ❑
Does It Include
Instructions for notification?
M ❑ ❑ ❑
Page 11
Permit WQCSD0148 Owner - Facility Wyeth LLC
Inspection Date 02/14/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit Routine
Pump station identifier? M ❑ ❑ ❑
Emergency phone number 0 ❑ ❑ ❑
Is public access limited? M ❑ 1:10
Is pump staaon free of overflow piping? ® ❑ ❑ ❑
Is the pump station free of signs of overflow? 0 ❑ ❑ ❑ -
Are run times comparable for multiple pumps?
Comment
Page 12