SUBJECT: NOTICE OF VIOLATION
Tracking Number: NOV-2018-PC-0051
Permit No. WQ0036701
High Vista Country Club
Henderson County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the High Vista Country Club on
February 6, 2018. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non-discharge Permit No. WQ0036701. A summary of the findings and
comments noted during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following violation(s) were noted during the inspection:
Inspection Area Description of Violation _________________________________________________________________________________________________________________________________________________________________________
Record Keeping Freeboard readings are not documented weekly. _________________________________________________________________________________________________________________________________________________________________________
Record Keeping Operation & Maintenance records were not being maintained. There was no Operation &
Maintenance Plan.
DocuSign Envelope ID: AD87249F-5B64-4F5F-B7D2-455D73E46927
State of North Carolina | Environmental Quality | Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
_________________________________________________________________________________________________________________________________________________________________________
End Use-Reuse Standby generator is not available. _________________________________________________________________________________________________________________________________________________________________________
Storage There was no freeboard marker in the irrigation pond. The pond was overflowing at the
time of inspection. _________________________________________________________________________________________________________________________________________________________________________
Record Keeping Tracking records for the use of reclaimed effluent have not been g enerated. _________________________________________________________________________________________________________________________________________________________________________
In addition, the issues below must also be addressed:
Compliance Issue(s):
Notification about the use of reclaimed water, and that it is not intended for drinking should include
employees as well as the public.
Remedial actions should have already been taken to correct these problems and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law.
To prevent further action, please respond in writing to this office within 30 days upon your receipt of this Notice
of Violation regarding your plans or measures to be taken to address the indicated violations and other identified
issues, if applicable.
If you should have any questions, please do not hesitate to contact Beverly Price with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4500.
Sincerely,
G. Landon Davidson, P.G., Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Brooks Lowder, GC Superintendent
WQS ARO Server
Laserfiche
20180215_WQ0036701_NOV2018PC0051.rtf
DocuSign Envelope ID: AD87249F-5B64-4F5F-B7D2-455D73E46927
Compliance Inspection Report
Permit:WQ0036701 Effective:10/25/13 Expiration:09/30/18 Owner :High Vista Finance LLC
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Henderson
Asheville
Brooks Lowder
Effective:Expiration:Facility:High Vista Country Club
88 Country Club Dr
Mills River NC 28759
Title:Phone:828-747-9766GC Superintendent
Secondary ORC(s):
Phone:Certification:Primary ORC:
System Classifications:
24 hour contact name Brooks Lowder 828-747-9766
On-site representative Brooks Lowder 828-747-9766
On-Site Representative(s):
Related Permits:
WQ0015929 A&D Water Service Inc - High Vista WWTP
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
02/06/2018 10:00AM 10:45AM
Beverly Price 828-296-4500
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Reclaimed Water
Compliance Evaluation
Question Areas:
Miscellaneous Questions Treatment Record Keeping
Storage End Use-Reuse
(See attachment summary)
Page:1
DocuSign Envelope ID: AD87249F-5B64-4F5F-B7D2-455D73E46927
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0036701
02/06/2018 Compliance Evaluation
High Vista Finance LLC
Routine
Inspection Summary:
The inspection was conducted by Beverly Price of the Asheville Regional Office. Mr. Brooks Lowder and Mr. Justin Speir
assisted with the inspection.
Reclaimed effluent from the High Vista WWTP was distributed to the High Vista Golf Course in October & November 2016;
otherwise, the system has not been in use since the permit was issued in 2013.
Signs are placed in the golf course club house notifying users that reclaimed water is used for irrigation. This notification
should also extend to employees working with the reclaimed system.
The irrigation pumps located in the reclaimed effluent pump house, froze and burst because of the extreme cold during the
month of January. Parts for pump repairs have been purchased and a contractor has been secured to complete the repairs.
The following items were determined to be non-compliant with the permit at the time of inspection:
1.There was no freeboard marker in the pond.
2.The irrigation pond was overflowing.
3.The Operation & Maintenance Plan/maintenance log had not been generated.
4.Freeboard is not being recorded weekly.
5.Records tracking the amount of reclaimed water used were not being maintained.
6.A standby generator should be available.
Page:2
DocuSign Envelope ID: AD87249F-5B64-4F5F-B7D2-455D73E46927
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0036701
02/06/2018 Compliance Evaluation
High Vista Finance LLC
Routine
Type Yes No NA NE
Lagoon Spray, LR
Infiltration System
Single Family Spray, LR
Recycle/Reuse
Activated Sludge Drip, LR
Activated Sludge Spray, HR
Activated Sludge Spray, LR
Single Family Drip
Reuse (Quality)
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
The permit description lists a standby power generator. There is no generator at this facility.
The reclaimed irrigation pumps were not working. The parts have been purchased for needed
repairs; Pro Pumps has been contracted to complete the repairs.
Comment:
Record Keeping Yes No NA NE
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Page:3
DocuSign Envelope ID: AD87249F-5B64-4F5F-B7D2-455D73E46927
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0036701
02/06/2018 Compliance Evaluation
High Vista Finance LLC
Routine
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
Operation & Maintenance records were not being maintained.Comment:
End Use-Reuse Yes No NA NE
Is the acreage in the permit being utilized?
Does the acreage specified in the permit correspond to the measured acreage at the site?
Are all essential units provided in duplicate?
Is an automatically activated standby power source available?
Is the equalization capacity adequate?
Is aerated flow equalization present?
Has the turbidity meter been calibrated in the last 12 months?
Does the turbidity meter have recording capabilities?
Is all flow diverted at the appropriate times?
Is all upset wastewater diverted from reuse storage unit?
Is all upset wastewater treated, retreated, or disposed of acceptably?
Is upset wastewater treated prior to discharge to irrigation storage?
Is public access restricted from irrigation area during active site use?
If golf course, is a sign posted in plain sight on the club house?
Is the cover crop acceptable?
Are buffers adequate?
Is the site free of ponding/runoff?
Is the acreage in the permit being utilized?
Is the application equipment acceptable?
Is the application area free of limiting slopes?
How close is the closest water supply well?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
Is municipal water available in the area?
Are GW monitoring wells required?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Page:4
DocuSign Envelope ID: AD87249F-5B64-4F5F-B7D2-455D73E46927
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0036701
02/06/2018 Compliance Evaluation
High Vista Finance LLC
Routine
The facility has received reclaimed effluent from the High Vista WWTP on two occasions since
the permit was issued, October & November 2016.
Standby power is not available.
The irrigation pumps were not operable but parts have been purchased and a contractor has
been hired for repairs.
Groundwater monitoring is not required.
The WWTP components referenced here are not controlled by this permittee; they are controlled
by A&D Water Services under permit WQ0015929.
Comment:
IRRIGATION POND -
Storage Yes No NA NE
Storage Type?Pond
Storage amount?1000000
Gallons
# At what point is side-stream wastewater returned to treatment?
Is there a Spill Control Plan?
Aerated or Mixed?AERATED
If aeration is present, is it adequate?
If present, are diffusers cleaned regularly?
Is influent structure acceptable?
Are banks/berms free of seepage and erosion?
Are banks/berms free of excessive vegetation?
Is pond lined?
Liner Type Unknown
Is liner acceptable?
Are baffles/curtains acceptable?
Does the pond have a freeboard marker?
Required freeboard?1
Feet
Actual freeboard?0
Feet
Is there suitable grassed vegetation?
Is the vegetation maintained?
Is the area free of excessive weeds and/or woody species?
Is the area free from signs of overflow?
Is color acceptable?
Are floating mats acceptable?
No excessive buildup of solids?
Are aerators/mixers acceptable?
Page:5
DocuSign Envelope ID: AD87249F-5B64-4F5F-B7D2-455D73E46927
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0036701
02/06/2018 Compliance Evaluation
High Vista Finance LLC
Routine
Is effluent structure acceptable?
If present, is pond cover acceptable?
There was no spill control plan.
There was no freeboard marker.
The pond was overflowing.