HomeMy WebLinkAboutNC0026557_CEI Report_20171214United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 15 1 3 I NCO026557 111 12 I 17/12/12 I17 18 I S J 19 L G j 201
211111 1 1 1 1 1 1 II I I I I I I I I I I I I I I I I I I I I I I I II I I I I 1166
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
67 70 IJ 71 Ij 72 u n 73 L_LJ74 751 I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
01:30PM 17/12/12
13/05/01
Bryson City WWTP
US Hwy 19W
Exit Time/Date
Permit Expiration Date
Bryson City NC 28713
03:30PM 17/12/12
17/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Everette Lamar Williams/ORC/828-479-3250/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Chad Simons,PO Box 726 Bryson City NC 28713//828-488-3335/8284889474
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Flow Measurement Operations & Maintenance 0 Sludge Handling Disposal 0 Facility Site Review
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Beverly Price ARO WQ//828-296-4500/
Timothy H Heim TIL ARO WQ//828-296-4665/ 12/14/2017
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCO026557 111 121 17/12/12 1 17 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim and Bev Price of the Asheville Regional Office performed a Collection System Compliance
Evaluation Inspection on December 12, 2017. Chad Simons (Town Manager) and Greg Passmore
(BORC) assisted with the inspection and records review. The facility appeared well maintained and
operated, and in compliance with Permit NC0026557.
In the summer of 2017, the facility experienced upset conditions that may have been caused by
discharge from local industry. The permittee is strongly encouraged to continue working to identify the
source of the upset conditions and institute measures to prevent reoccurrence.
Page#
Permit: NCO026557
Inspection Date: 12/12/2017
Owner - Facility: Bryson City WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Process controls include DO and Cl residual.
Maintain thermometers in the influent and effluent composite samplers.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Yes No NA NE
■
■
❑
❑
❑
❑
❑
❑
Yes No NA NE
0
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: The trailer used to collect screened materials was very
full at the time of the inspection.
Is the clarifier free of black and odorous wastewater?
0
Increase the frequency with which this is emptied to reduce risk of spilling screened material
❑
❑
on the ground.
E
❑
❑
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
❑
❑
Type of aeration system
Diffused
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
0 ❑
❑
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
0 ❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑
❑
0
Comment: ORC reports DO levels maintained at 1.5-2 mg/L.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
E
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Page# 3
Permit: NC0026557
Inspection Date: 12/12/2017
Secondary Clarifier
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Owner - Facility: Bryson City WWTP
Inspection Type: Compliance Evaluation
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately 1/4 of the sidewall depth)
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Comment: Increasing cleaning frequency of weir teeth as debris was noted accumulating in these
areas.
Drying Beds
Is there adequate drying bed space?
Is the sludge distribution on drying beds appropriate?
Are the drying beds free of vegetation?
# Is the site free of dry sludge remaining in beds?
Is the site free of stockpiled sludge?
Is the filtrate from sludge drying beds returned to the front of the plant?
# Is the sludge disposed of through county landfill?
# Is the sludge land applied?
(Vacuum filters) Is polymer mixing adequate?
Comment: Sludge is removed from facility and hauled to Homer, GA for landfill disposal.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Disinfection-Liaulid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
■
Yes No NA NE
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
Page# 4
Permit: NCO026557 Owner - Facility:
Bryson City WWTP
Type of system ?
Liquid
❑
Inspection Date: 12/12/2017 Inspection Type:
Compliance Evaluation
0 ❑
❑
❑
Disinfection -Liquid
Yes No NA NE
Is bulk storage tank containment area adequate? (free of leaks/open drains)
0
❑
❑
❑
Is the level of chlorine residual acceptable?
❑
❑
❑
0
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
0
Comment: Minor grease particles accumulating in the contact chamber. Review SUO and grease trap
inspection/enforcement program with goal of reduing FOG entering the facility.
De -chlorination
Yes No NA NE
Type of system ?
Liquid
❑
❑
Is the feed ratio proportional to chlorine amount (1 to 1)?
0 ❑
❑
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
M ❑
❑
❑
Comment:
Are the tablets the proper size and type? ❑ ❑ 0 ❑
Are tablet de -chlorinators operational? ❑ ❑ 0 ❑
Number of tubes in use?
Comment:
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
0
❑
❑
❑
Comment: Remove additional vegetation from the bank to allow visual observation of the effluent
pipe
from the contact chamber area.
Page# 5