HomeMy WebLinkAboutNC0066788_Compliance Evaluation Inspection_20171127DocuSign Envelope ID: E914E78C-EFBD-4E5E-9529-5C7D6FD09CC0
WQterilZesou ces
EHWROMMEWAl QUALITY
November 27, 2017
Clark Wyatt
Buncombe County Schools
175 Bingham Rd
Asheville, NC 28806
SUBJECT: Compliance Inspection Report
Fairview Elementary School WWTP
NPDES WW Permit No. NCO066788
Buncombe County
Dear Permittee:
ROY COOPER
Gorerna,
MICHAEL S. REGAN
Sacre��
LT -NDA CFULPEPPER
lhJ err m Direclar
The North Carolina Division of Water Resources conducted an inspection of the Fairview
Elementary School Wastewater Treatment Plant on 11/08/2017. Although the plant appeared
to be compliant at the time of the inspection, there are several areas of concern that need your
attention. The findings and comments noted during this inspection are provided in the
enclosed copy of the inspection report entitled "Compliance Inspection Report" for your review.
If you have any questions, please do not hesitate to contact me at 828-296-4500 or via email at
linda.wiggs@ncdenr.gov.
Sincerely,
Linda Wiggs
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENT -Inspection Report
Cc: WQS Asheville Regional Office
NPDES Compliance/Enforcement Unit
State of North Carolina I Environmental Quality I Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
DocuSign Envelope ID: E914E78C-EFBD-4E5E-9529-5C7D6FD09CC0
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO066788 111 12 I 17/11/08 I17 18 I S J 19 LG] 201 I
211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
67 70 I I 71 I I 72 I r l 73 I I 174 751 I I I 1 1 1 I80
u ty I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:35AM 17/11/08
16/01/01
Fairview Elementary School
1355 Charlotte Hwy
Exit Time/Date
Permit Expiration Date
Fairview NC 28730
11:25AM 17/11/08
20/12/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Clark Wyatt, 175 Bingham Rd Asheville NC 28806//828-232-4244/
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance 0 Records/Reports
Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Linda S Wiggs -4w ARO WQ//828-296-4500 Ext.4653/
11/22/2017
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EI en11/22/2017
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: E914E78C-EFBD-4E5E-9529-5C7D6FD09CC0
NPDES yr/mo/day Inspection Type (Cont.)
NC0066788 111 121 17/11/08 1 17 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The Inspector, Linda Wiggs, met onsite with Richard Swilling, the ORC.
The facility appeared to be compliant at the time of the inspection, however there are areas of concern
as mentioned below that the Permittee needs to address.
The EQ basin at this facility is a beneficial component, although too much improper paper products
can damage the pumps and large slugs of chemicals will not be absorbed by the EQ and will pass
through to the biological treatment units, killing the biota.
Excessive paper products are coming into this plant. Signage in the school restrooms may alleviate
this, however, proper toilet seat covers supplied in the restrooms may be more appropriate. This effort
should also extend to the recreation field facilities.
When the school does large cleaning operations or when the floors are stripped and re -waxed the plant
is impacted. Smaller cleaning operations with less toxic chemicals should be considered. When the
floors are stripped and re -waxed, Buncombe County Schools needs to contract a company that will
properly dispose of this wastewater.
Grease was not noted as an issue, however Buncombe County Schools need to make sure not only
their cafeteria grease traps are properly maintained but also that the Subway in the gas station
maintain their grease trap.
This WWTP has safety concerns. It is an above ground plant without railings and requires stairs for
access. Concrete blocks have been placed for access to the EQ area of the plant. There are no safety
rails or walkways. Metal grates cover the basins and must be removed for operations. The ORC is
onsite alone. Buncombe County Schools needs to evaluate this site for OSHA requirements.
Page#
DocuSign Envelope ID: E914E78C-EFBD-4E5E-9529-5C7D6FD09CC0
Permit: NCO066788
Inspection Date: 11/08/2017
Owner - Facility: Fairview Elementary School
Inspection Type: Compliance Evaluation
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: This WWTP has safety concerns.
Chemicals, wax and paper products are also a concern.
See summary.
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
Yes No NA NE
■ ❑ ❑ ❑
❑ ■ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The permit list "post aeration", this facility does not have post aeration. This needs to be
removed from the components list next permit renewal.
Bar Screens
Yes No NA NE
Type of bar screen
0
❑
❑
❑
a.Manual
0
❑
❑
❑
b.Mechanical
❑
❑
❑
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
❑
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: Excessive paper products are coming into this plant.
See summary.
Equalization Basins
Yes No NA NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Page# 3
DocuSign Envelope ID: E914E78C-EFBD-4E5E-9529-5C7D6FD09CC0
Permit: NCO066788 Owner - Facility: Fairview Elementary School
Inspection Date: 11/08/2017 Inspection Type: Compliance Evaluation
Equalization Basins Yes No NA NE
Are audible and visual alarms operable? 0 ❑ ❑ ❑
# Is basin size/volume adequate? 0 ❑ ❑ ❑
Comment: The alarm light was working.
See summary for more information.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
❑
❑
Type of aeration system
Diffused
❑
❑
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
❑ ❑
0
❑
Does the foam cover less than 25% of the basin's surface?
❑ ❑
0
❑
Is the DO level acceptable?
❑ ❑
❑
0
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑
❑
0
Comment: No foam was noted during the inspection.
See summary.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
❑
❑
❑
0
Comment: There was a small amount of floating sl
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? 0 ❑ ❑ ❑
Page# 4
DocuSign Envelope ID: E914E78C-EFBD-4E5E-9529-5C7D6FD09CC0
Permit: NCO066788
Inspection Date: 11/08/2017
Owner - Facility: Fairview Elementary School
Inspection Type: Compliance Evaluation
Type of system ?
Tablet
❑
Disinfection -Tablet
Yes No NA NE
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
3
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
Is the level of chlorine residual acceptable?
❑
❑
❑
0
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
0
Comment:
De -chlorination
Yes No NA NE
Type of system ?
Tablet
❑
0
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑ ❑
0
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 2
Comment:
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
❑
❑
0
❑
Is proper volume collected?
❑
❑
0
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: The ORC stated he has requested a new flow meter.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Page# 5
DocuSign Envelope ID: E914E78C-EFBD-4E5E-9529-5C7D6FD09CC0
Permit: NCO066788
Inspection Date: 11/08/2017
Effluent Pipe
Comment:
Owner - Facility: Fairview Elementary School
Inspection Type: Compliance Evaluation
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Yes No NA NE
Yes No NA NE
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
Comment: Buncombe County School maintenance staff maintain the generator. Generator is on a
natural gas line. ORC stated the county has plans to install a new generator.
Page# 6