Loading...
HomeMy WebLinkAboutNC0086436_Compliance Inspection_20171127DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55 WQterilZesou CeS EHWROMMEWAl QUALITY November 27, 2017 Clark Wyatt Buncombe County Schools 175 Bingham Rd Asheville, NC 28806 SUBJECT: Compliance Inspection Report Cane Creek Elementary School WWTP NPDES WW Permit No. NCO086436 Buncombe County Dear Permittee: ROY COOPER Gorerna, MICHAEL S. REGAN Sacre�� LT -NDA CFULPEPPER lhJ err m Direclar The North Carolina Division of Water Resources conducted an inspection of the Cane Creek Elementary School Wastewater Treatment Plant (WWTP) on 11/08/2017. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0086436. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". If you have any questions, please do not hesitate to contact me at 828-296-4500 or via email at linda.wiggs@ncdenr.gov. Sincerely, Linda Wiggs Water Quality Regional Operations Section Asheville Regional Office Division of Water Resources, NCDEQ ATTACHMENT -Inspection Report Cc: WQS Asheville Regional Office NPDES Compliance/Enforcement Unit State of North Carolina I Environmental Quality I Water Resources 2090 U.S. 70 Highway, Swannanoa, NC 28778 828-296-4500 DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 15 I 3 I NCO086436 111 12 I 17/11/08 I17 18 I S J 19 LG] 201 I 211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----------------------Reserved------------------- 67 70 I I 71 I I 72 I r l 73 I I 174 751 1 1 1 1 1 1 180 u I� I I i Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 09:45AM 17/11/08 16/01/01 Cane Creek Elementary School 570 Lower Brush Creek Rd Exit Time/Date Permit Expiration Date Fletcher NC 28732 10:30AM 17/11/08 20/12/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Clark Wyatt, 175 Bingham Rd Asheville NC 28806//828-232-4244/ Yes Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance 0 Records/Reports Facility Site Review Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Linda S Wiggs -4w ARO WQ//828-296-4500 Ext.4653/ 11/22/2017 Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date P 11/22/2017 EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55 NPDES yr/mo/day Inspection Type NC0086436 111 121 17/11/08 1 17 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) The Inspector, Linda Wiggs, met onsite with Richard Swilling, the ORC. The facility appeared to be compliant at the time of the inspection, however rust remains an issue at this plant. It does not appear actions have been taken to paint this plant. Given the age of this WWTP, the amount of rust is concerning. Therefore, as noted in a previous inspection, Buncombe County Schools should draw down this plant and evaluate the need for sanding and painting. Page# DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55 Permit: NCO086436 Owner - Facility: Cane Creek Elementary School Inspection Date: 11/08/2017 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: ORC stated settleability, pH and TRC are periodically checked at this WWTP. The WWTP has rust. It is not that old of a WWTP; the amount of rust should be evaluated. Solids were recently removed by Mike's Septic, 11/3/2017. Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new 0 ❑ ❑ ❑ application? 0 ❑ ❑ ❑ Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ 0 ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: Equalization Basins Yes No NA NE Is the basin aerated? 0 ❑ ❑ ❑ Is the basin free of bypass lines or structures to the natural environment? 0 ❑ ❑ ❑ Is the basin free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? 0 ❑ ❑ ❑ Are all pumps operable? 0 ❑ ❑ ❑ Are float controls operable? 0 ❑ ❑ ❑ Are audible and visual alarms operable? 0 ❑ ❑ ❑ # Is basin size/volume adequate? 0 ❑ ❑ ❑ Comment: Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? ❑ ❑ 0 ❑ Does the foam cover less than 25% of the basin's surface? ❑ ❑ 0 ❑ Page# 3 DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55 Permit: NCO086436 Owner - Facility: Cane Creek Elementary School Inspection Date: 11/08/2017 Inspection Type: Compliance Evaluation Aeration Basins Yes No NA NE Is the DO level acceptable? ❑ ❑ ❑ 0 Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑ 0 Comment: No foam was present. Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? 0 ❑ ❑ ❑ Is the site free of weir blockage? 0 ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ 0 ❑ Is the return rate acceptable (low turbulence)? 0 ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) ❑ ❑ ❑ 0 Comment: Clarifier was murky. Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? 0 ❑ ❑ ❑ Number of tubes in use? 2 Yes No NA NE Type of system ? Tablet Is the level of chlorine residual acceptable? ❑ ❑ ❑ 0 Is the contact chamber free of growth, or sludge buildup? M ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ 0 Comment: The chlorine contact chamber is plumbed back to the EQ basin to allow for cleaning, the ORC states he generally does this weekly. De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ 0 ❑ Is storage appropriate for cylinders? ❑ ❑ 0 ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ 0 ❑ Page# 4 DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55 Permit: NCO086436 Owner - Facility: Cane Creek Elementary School Inspection Date: 11/08/2017 Inspection Type: Compliance Evaluation De -chlorination Yes No NA NE Comment: Are the tablets the proper size and type? ❑ ❑ ❑ Are tablet de -chlorinators operational? ❑ ❑ ❑ Number of tubes in use? 1 Comment: Standby Power Yes No NA NE Is automatically activated standby power available? 0 ❑ ❑ ❑ Is the generator tested by interrupting primary power source? ❑ ❑ ❑ 0 Is the generator tested under load? ❑ ❑ ❑ 0 Was generator tested & operational during the inspection? ❑ ❑ ❑ 0 Do the generator(s) have adequate capacity to operate the entire wastewater site? 0 ❑ ❑ ❑ Is there an emergency agreement with a fuel vendor for extended run on back-up power? ❑ ❑ ❑ 0 Is the generator fuel level monitored? ❑ ❑ 0 ❑ Comment: Natural gas is fuel for the generator. School maintenance staff maintain generator. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: The WWTP was not discharging during the inspection. The ORC stated this facility discharges on an average of twice a week. Page# 5