HomeMy WebLinkAboutNC0086436_Compliance Inspection_20171127DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55
WQterilZesou CeS
EHWROMMEWAl QUALITY
November 27, 2017
Clark Wyatt
Buncombe County Schools
175 Bingham Rd
Asheville, NC 28806
SUBJECT: Compliance Inspection Report
Cane Creek Elementary School WWTP
NPDES WW Permit No. NCO086436
Buncombe County
Dear Permittee:
ROY COOPER
Gorerna,
MICHAEL S. REGAN
Sacre��
LT -NDA CFULPEPPER
lhJ err m Direclar
The North Carolina Division of Water Resources conducted an inspection of the Cane Creek
Elementary School Wastewater Treatment Plant (WWTP) on 11/08/2017. This inspection was
conducted to verify that the facility is operating in compliance with the conditions and
limitations specified in NPDES WW Permit No. NC0086436. The findings and comments noted
during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
If you have any questions, please do not hesitate to contact me at 828-296-4500 or via email at
linda.wiggs@ncdenr.gov.
Sincerely,
Linda Wiggs
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENT -Inspection Report
Cc: WQS Asheville Regional Office
NPDES Compliance/Enforcement Unit
State of North Carolina I Environmental Quality I Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCO086436 111 12 I 17/11/08 I17 18 I S J 19 LG] 201 I
211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
67 70 I I 71 I I 72 I r l 73 I I 174 751 1 1 1 1 1 1 180
u I� I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:45AM 17/11/08
16/01/01
Cane Creek Elementary School
570 Lower Brush Creek Rd
Exit Time/Date
Permit Expiration Date
Fletcher NC 28732
10:30AM 17/11/08
20/12/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Clark Wyatt, 175 Bingham Rd Asheville NC 28806//828-232-4244/
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance 0 Records/Reports
Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Linda S Wiggs -4w ARO WQ//828-296-4500 Ext.4653/ 11/22/2017
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
P 11/22/2017
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55
NPDES yr/mo/day Inspection Type
NC0086436 111 121 17/11/08 1 17 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The Inspector, Linda Wiggs, met onsite with Richard Swilling, the ORC.
The facility appeared to be compliant at the time of the inspection, however rust remains an issue at
this plant.
It does not appear actions have been taken to paint this plant. Given the age of this WWTP, the amount
of rust is concerning. Therefore, as noted in a previous inspection, Buncombe County Schools should
draw down this plant and evaluate the need for sanding and painting.
Page#
DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55
Permit: NCO086436 Owner - Facility: Cane Creek Elementary School
Inspection Date: 11/08/2017 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: ORC stated settleability, pH and TRC are periodically checked at this WWTP.
The WWTP has rust. It is not that old of a WWTP; the amount of rust should be evaluated.
Solids were recently removed by Mike's Septic, 11/3/2017.
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
0
❑
❑
❑
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment:
Equalization Basins
Yes No NA NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
0
❑
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment:
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
❑ ❑
0
❑
Does the foam cover less than 25% of the basin's surface?
❑ ❑
0
❑
Page# 3
DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55
Permit: NCO086436 Owner - Facility: Cane Creek Elementary School
Inspection Date: 11/08/2017 Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Is the DO level acceptable? ❑ ❑ ❑ 0
Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑ 0
Comment: No foam was present.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
❑
❑
❑
0
Comment: Clarifier was murky.
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? 0 ❑ ❑ ❑
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Number of tubes in use? 2
Yes No NA NE
Type of system ?
Tablet
Is the level of chlorine residual acceptable?
❑ ❑
❑
0
Is the contact chamber free of growth, or sludge buildup?
M ❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑ ❑
❑
0
Comment: The chlorine contact chamber is plumbed back to the EQ basin to allow for cleaning,
the
ORC states he generally does this weekly.
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑ ❑
0
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
❑
Page# 4
DocuSign Envelope ID: 77D31884-E9A3-408F-BCF4-E483010A3E55
Permit: NCO086436 Owner - Facility: Cane Creek Elementary School
Inspection Date: 11/08/2017 Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Comment:
Are the tablets the proper size and type? ❑ ❑ ❑
Are tablet de -chlorinators operational? ❑ ❑ ❑
Number of tubes in use? 1
Comment:
Standby Power
Yes No NA NE
Is automatically activated standby power available?
0
❑
❑
❑
Is the generator tested by interrupting primary power source?
❑
❑
❑
0
Is the generator tested under load?
❑
❑
❑
0
Was generator tested & operational during the inspection?
❑
❑
❑
0
Do the generator(s) have adequate capacity to operate the entire wastewater site?
0
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
❑
❑
❑
0
Is the generator fuel level monitored?
❑
❑
0
❑
Comment: Natural gas is fuel for the generator. School maintenance staff maintain generator.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The WWTP was not discharging during the inspection. The ORC stated this facility
discharges on an average of twice a week.
Page# 5