November 15, 2017
Mr. Chip Swinnie, Plant Manager
Schneider Mills, Inc.
P.O. Box 519
Taylorsville, NC 28681
RECERIE DIN CD� 0XIII IR
Subject: Compliance Inspection
Schneider Mills WWTP
NPDES Permit No. NCO034860
Alexander County
Dear Mr. Swinnie:
NOV 21 2011
Water Qualay
Permitting Section
Enclosed is a copy of the Compliance Inspection for the inspection conducted at the
subject facility on November 3, 2016, by Ori Tuvia. Darren Webb's cooperation during the site
visit was much appreciated. Please advise the staff involved with this NPDES Permit by
forwarding a copy of the enclosed report.
The following areas of concern were observed during the inspection:
1) ORC Must Record the beginning and end time of composite sampling.
2) At the time of the inspection the flow meter values did not match the calculated value,
ORC will need to farther investigate.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Cc: NPDES Unit
MRO Files
Sincerely,
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, -DEQ
Mooresville Regional Office
Location. 610 East Center Ave., Suite 301 Mooresville, NC 28115
Phone (704) 663-16991 Fax; (704) 663-60401 Customer Service 1-877-623-6748
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A National Data System Coding (i a, PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 u 2 15 1 3 I NCO034860 I11 12 17/11/14 17 181,•1 19I c I 20I
1166
2111.11 1 1 1 1 1 1 II 11 I I I I I I I I I I I I I I I I I I I I I II I I I 1 I
Reserved------
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA-Reserved-
67 1 a 70 �d � 71 J� 72 1 ti � 731 I 174 75III j_U80
67110
LJ L_I I I I
Section B Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09 30AM 17/11/14
15/11/01
Schneider Mills WWTP
1170 NC Hwy 16 N
Exit Time/Date
Permit Expiration Date
Taylorsville NC 28681
11 30AM 17/11/14
20/07/31
Name(s) of Onsite Representabve(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
Darren David Webb/ORC/828-632-8181/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Chip Swinnie,PO Box 519 Taylorsviile NC 286810519/Plant Manager/828-632-8181/
No
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitonng Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
On A Tuwa .-• - � MRO W0/f704-663-1699/
Signature of Managem t Q v wer Agency/Office/Phone and Fax Numbers Date
Andrew Pltner , O WQ//704-663-1699 Ext 21 1 IS 1
, r
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete
Page#
NPDES yr/mo/day Inspection Type
31 NCO034860 I11 12 17/11/14 17 18 ICI
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
. _f
Permit NCO034860 Owner -Facility Schneider MillsWWTP
Inspection Date 11/14/2017 Inspection Type Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted a new
❑
❑
E
❑
application?
N
❑
❑
❑
Is the facility as described In the permit?
❑
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the Inspector granted access to all areas for Inspection?
N
❑
❑
❑
Comment: The subject permit expires on 7/31/2020
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required Information readily available, complete and current?
N
❑
❑
❑
Are all records maintained for 3 years (lab reg required 5 years)?
❑
❑
❑
0
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
sampling:
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete do they Include all permit parameters?
E
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
E
❑
on each shift?
Is the ORC visitation log available and current?
0 ❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0 ❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0 ❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑ ❑
❑
0
Comment. The records reviewed during the inspection were organized and well maintained
DMRs.
COCs. Calibration logs and ORC visitation logs were reviewed for the period November
2016 through September 2017. ORC must indicate the beginning and end time of composite
sampling:
Page# 3
Incubator (Fecal Coliform) set to 44 5 degrees Celsius+/- 0 2 degrees? ❑ ❑ 0 ❑
Incubator (BOD) set to 20 0 degrees Celsius +/-1 0 degrees? ❑ ❑ 0 ❑
Comment: On-site field analyses (dissolved oxygen PH, temperature, total residual chlorine) are
performed under the Company's field laboratory certification #5012 Water Tech Labs
(BOD TSS ammonia nutrients) and R & A Laboratories, Inc (toxicity and metals) have
also been contracted to provide analytical support
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
Permit N00034860 Owner -Facility Schneider Mills WWTP
❑
Is sample collected below all treatment units?
❑
Inspection Date 11/14/2017 Inspection Type Compliance Evaluation
❑
Is proper volume collected?
0
❑
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
E
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
E
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
N
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44 5 degrees Celsius+/- 0 2 degrees? ❑ ❑ 0 ❑
Incubator (BOD) set to 20 0 degrees Celsius +/-1 0 degrees? ❑ ❑ 0 ❑
Comment: On-site field analyses (dissolved oxygen PH, temperature, total residual chlorine) are
performed under the Company's field laboratory certification #5012 Water Tech Labs
(BOD TSS ammonia nutrients) and R & A Laboratories, Inc (toxicity and metals) have
also been contracted to provide analytical support
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
❑
Is sample collected below all treatment units?
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
N
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
❑
❑
❑
representative)?
Comment The subject permit requires both composite and grab effluent samples The Division
improved a vanance'to collect time -based composite samples on 5/26/1998 provided
that
the flows do not vary by more than 30% The sampler was collecting 300 ml aliquot every
twenty minutes with an internal temperature of less than four degrees celsius
Upstream / Downstream Samplina Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and ❑ ❑ ❑
sampling location)?
Comment
Operations & Maintenance Yes No NA NE
` Is the plant generally clean with acceptable housekeeping? N ❑ ❑ ❑
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable E ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment The wastewater facility appeared to be properly operated and well maintained. The ORC
incorporates a comprehensive process control program with all measurements being
properly documented and maintained on-site
Page# 4
14
m
Permit NCO034860
Inspection Date 11/14/2017
Owner -Facility Schneider Mills WWTP
Inspection Type Compliance Evaluation
Bar Screens
Type of bar screen
a Manual
b Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening In compliance?
Is the unit in good condition?
Comment- Bar screenings are disposed at the Alexander County Landfill
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
E ❑ ❑ ❑
* ❑ ❑ ❑
* ❑ ❑ ❑
* ❑ ❑ ❑
Yes No NA NE
E ❑ ❑ ❑
N ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment- The influent flow meter (Outfall 001) is calibrated twice per vear and was last calibrated b
ISI At the time of the Inspection the flow meter values did not match the calculated value.
ORC will need to investigate
The flows for Outfall 002 are based on the calculated backwash volume (3.150 -gallons) and
the number of backwash events per day
Aeration Basins Yes No NA NE
Mode of operation Ext Air
Type of aeration system
Surface
Is the basin free of dead spots?
N
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
N
❑
Are the diffusers operational?
❑
❑
N
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1 0 to 3 0 mg/1)
❑
❑
E
❑
Comment- Agueous lime and soda ash are added to maintain appropriate pH/alkalinity levels The
ORC also adds food (BOD)/nutrient (nitrogen and phosphorus) supplements and selective
microrganisms to maintain the biological treatment process.
Secondary Clarifier
Yes No NA NE
Page# 5
Permit NC0034860 Owner -Facility
Schneider Mills WWTP
Is right of way to the outfall properly maintained?
0
❑
Inspection Date 11/14/2017 Inspection Type
Compliance Evaluation
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
E
❑
❑
❑
Is the site free of excessive buildup of solids In center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
N
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
❑
❑
0
❑
Is the site free of excessive floating sludge?
E
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
0
❑
❑
❑
Comment. Polymer Is added to the clarifier influent to enhance settling
Pumps -RAS -WAS Yes No NA NE
Are pumps in place? 0 ❑ ❑ ❑
Are pumps operational? ❑ ❑ ❑
Are there adequate spare parts and supplies on site? ❑ ❑ ❑ 0
Comment
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
❑
0
Comment At the time of the inspection the effluent appeared to be clear
E
❑
❑
❑
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
❑
❑
❑
Is the mixing adequate?
❑
❑
❑
Is the site free of excessive foaming in the tank?
N
❑
❑
❑
# Is the odor acceptable?
E
❑
❑
❑
# Is tankage available for properly waste sludge?
E
❑
❑
❑
Comment
Page# 6
R
d
Permit NC0034860
Inspection Date 11/14/2017
Dryrna Beds
Is there adequate drying bed space?
Is the sludge distribution on drying beds appropriate?
Owner -Facility Schneider Mills WWTP
Inspection Type Compliance Evaluation
Are the drying beds free of vegetation?
# Is the site free of dry sludge remaining in beds?
Is the site free of stockpiled sludge?
Is the filtrate from sludge drying beds returned to the front of the plant?
# Is the sludge disposed of through county landfill?
# Is the sludge land applied?
(Vacuum filters) Is polymer mixing adequate?
Yes No NA NE
E ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
N ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ N ❑
❑ ❑ N ❑
Comment. The dewatered sludges from the wastewater treatment system (drying beds) and water
treatment system are transported to the Alexander County Landfill for disposal
Page# 7