HomeMy WebLinkAboutNC0086053_Compliance Sampling Inspection_20171127
State of North Carolina | Environmental Quality | Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
November 27, 2017
Joey Cupp
Pilot Travel Centers LLC
PO Box 10146
Knoxville, TN 37939-0146
SUBJECT: Compliance Inspection Report
Pilot Travel Center #393
NPDES WW Permit No. NC0086053
Haywood County
Dear Mr. Cupp:
The North Carolina Division of Water Resources conducted a Compliance Sampling Inspection of
the Pilot Travel Center #393 on 11/08/2017. This inspection was conducted to verify that the
facility is operating in compliance with the conditions and limitations specified in NPDES WW
Permit No. NC0086053. The findings and comments noted during this inspection are provided in
the enclosed copy of the inspection report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a
response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Mikal Willmer with the
Water Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or
via email at mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
EC: WQS ARO Server
Laserfiche
20171127_NC0086053_CSI
DocuSign Envelope ID: 01D8250F-8F1C-42B2-820C-E4D1864D7650
State of North Carolina | Environmental Quality | Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
DocuSign Envelope ID: 01D8250F-8F1C-42B2-820C-E4D1864D7650
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0086053 17/11/08 S S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Pilot Travel Center #393
NC Hwy 209 At I-40
Waynesville NC 28786
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
12:34PM 17/11/08 16/12/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Joedavid Matthew Hall/ORC/828-586-5588/
Other Facility Data
01:30PM 17/11/08 21/01/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Joey Cupp,PO Box 10146 Knoxville TN 379390146//865-588-7488/8654502809 Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Self-Monitoring Program
Sludge Handling Disposal Facility Site Review Compliance Schedules Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Timothy H Heim ARO WQ//828-296-4665/
Mikal Willmer ARO WQ//828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 01D8250F-8F1C-42B2-820C-E4D1864D7650
11/27/2017
11/27/2017
11/27/2017
NPDES yr/mo/day
17/11/08
Inspection Type
S3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Inspectors, Mikal Willmer and Tim Heim with the Asheville Regional Office conducted a Compliance
Evaluation Inspection of the Pilot Travel Center's WWTP on November 8, 2017. This inspection was
conducted to assess what steps have been taken to repair the offline secondary clarifier since the
Engineering Analysis was received on July 5, 2017. Joedavid Hall, ORC, was present and assisted in
the inspection.
Special Permit conditions require Pilot Travel to submit an engineering analysis by December 2017
and implement repairs by December 2018. The engineering analysis was received on July 6, 2017.
The concrete around the offline clarifier has been repaired and a new weir box has been installed;
however, the ORC reports the seams of the weir box leak when filled. At the time of the inspection, it
appeared hydraulic cement or an epoxy was recently used to repair the leaking seams. The ORC has
not attempted to fill the clarifier since the repair to the seams.
The composite sampler recently quit working. Environmental Inc. has brought in a refrigerator and
time/flow proportional peristaltic pump. They hope to set up a portable sampler soon. A new sampler
may be beneficial and aid in maintaining sample temperature. Additionally, a composite sampler would
be better protected from the elements.
The effluent appeared to be free from significant visible solids at the time of the inspection.
Results from the Compliance Sampling Inspection are as follows:
TSS: 12 mg/L
Fecal: 3 cfu/100 mL
BOD: 35 mg/L
NC0086053 17 (Cont.)
Page#2
DocuSign Envelope ID: 01D8250F-8F1C-42B2-820C-E4D1864D7650
Permit:NC0086053
Inspection Date:11/08/2017
Owner - Facility:
Inspection Type:
Pilot Travel Center #393
Compliance Sampling
Compliance Schedules Yes No NA NE
Is there a compliance schedule for this facility?
Is the facility compliant with the permit and conditions for the review period?
PIlot Travel is required to submit a treatment system study by December 2017 and
implement recommendations by December 2018. Dynamis, on behalf of Pilot Travel,
submitted an Engineering Evaluation prepared by Mark Balik, PE on July 5, 2017. The
evaluation includes corrective measures to repair the offline clarifier.
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Joedavid, ORC, with Environmental Inc. stated they have begun to monitor MLSS more
frequently to help manage solids within the Aeration Basins. Environmental Inc. is pumping
the treatment units approximately once a quarter.
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
See compliance schedule section above.Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
The effluent was no longer overtopping the weir plate.Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Page#3
DocuSign Envelope ID: 01D8250F-8F1C-42B2-820C-E4D1864D7650
Permit:NC0086053
Inspection Date:11/08/2017
Owner - Facility:
Inspection Type:
Pilot Travel Center #393
Compliance Sampling
Bar Screens Yes No NA NE
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
The WWTP did not appear to be experiencing flow surges during the inspection. The ORC
reports all floats within the basin are working.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
There are still solids floating to the surface of the clarifier, but there did not appear to be
significant solids leaving the clarifier. It should be noted the second clarifier is still offline. See
inspection summary for details and corrective measures.
Comment:
Aeration Basins Yes No NA NE
Page#4
DocuSign Envelope ID: 01D8250F-8F1C-42B2-820C-E4D1864D7650
Permit:NC0086053
Inspection Date:11/08/2017
Owner - Facility:
Inspection Type:
Pilot Travel Center #393
Compliance Sampling
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
The blowers turned on within the aeration basins during the inspection.Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Chambers are being pumped once a quarter.Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Page#5
DocuSign Envelope ID: 01D8250F-8F1C-42B2-820C-E4D1864D7650
Permit:NC0086053
Inspection Date:11/08/2017
Owner - Facility:
Inspection Type:
Pilot Travel Center #393
Compliance Sampling
Effluent Sampling Yes No NA NE
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
The composite sampler recently quit working. Environmental Inc. has brought in a
refrigerator and portable time/flow proportional peristaltic pump to collect samples. A new
sampler may be beneficial and aid in maintaining sample temperature. Additionally, a
composite sampler would be better protected from the elements.
Comment:
Page#6
DocuSign Envelope ID: 01D8250F-8F1C-42B2-820C-E4D1864D7650