Loading...
HomeMy WebLinkAboutNC0021628_Compliance_20171030Water Resources ENVIRONMENTAL QUALITY October 30, 2017 Mr John Mullis, Town Administrator Town of Norwood Post Office Box 697 Norwood, North Carolina 28128 ROY COOPER Governor MICHAEL S REGAN Secretary S JAY ZIMMERMAN Director RECEIVEDINCDEOWR NOV 0 7 2017 Water Quality Permitting Section SUBJECT Compliance Evaluation Inspection Norwood WWTP NPDES Permit NCO021628 Stanly County, NC Dear Mr Mullis On October 24, 2017, Roberto Scheller of this Office conducted an inspection at the subject facility This inspection was conducted as a Compliance Evaluation Inspection (CEI) to insure compliance with permit requirements and conditions At the time of inspection facility appeared to be well maintained and operated We wish to thank you and the operating staff for assistance regarding this inspection The enclosed report should be self-explanatory, however, should you have any questions, please do not hesitate to contact myself of Roberto Scheller at (704) 235-2204 or roberto scheller@ncdenr gov Enclosure- Inspection Report cc Thomas Johnson (ORC) email Wastewater Branch File Sincerely, W Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ tjohnson@envirolinkinc com State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations Mooresville Regional Office) 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115 704 663 1699 United States Environmental Protection Agency Form Approved EPA Washington, D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A National Data System Coding (i e , PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 I 3 I N00021628 I11 12 17/10/24 17 18 ICI 19 I G I 201 211 1IIII IIIIIII1II11111111 l llllll lllIIIIIIII 166 -- —Reserved--- — Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ---Reserved----- 67171 I I I 72 L N � 731 I 174 75 80 67 70 [2_j ilIII I I I Section B Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 02 38PM 17/10/24 14/02/01 Norwood WWTP 6896 US Hwy 52 Exit Time/Date Permit Expiration Date Norwood NC 28128 04 22PM 17/10/24 19/01/31 Name(s) of Onsite Representative(s)fTitles(s)/Phone and Fax Number(s) Other Facility Data /// - Thomas David Johnson/ORC/252-419-2199/ Name, Address of Responsible Officialfritle/Phone and Fax Number Contacted Dwight Smith,PO Box 679 Norwood NC 28128/Town No Adminstratorf704-474-3416!7044743201 Section C Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self-Monitonng Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Roberto Scheller MRO WQ//252-946-6481/ `V CS'U✓ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W Corey Basinger MRO WQ//704-235-2194/ EPA Form 33560-3 (Rev 9-94) Previous editions are obsolete Ale= Page# 1 NPDES yr/mo/day Inspection Type 1 31 NCO021628 111 121 17/10/24 1 17 18 ICI Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# 2 Permit NCO021628 Owner - Facility Norwood WWTP Inspection Date 10/24/2017 Inspection Type Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less) Has the permittee submitted a new ❑ ❑ 0 ❑ application? 0 ❑ ❑ ❑ Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? M ❑ ❑ ❑ Comment Current permit is for the discharge of 0 75 MGD Into Rocky river which is classified as C waters The Rocky River is in the Yadkin -Pee Dee River Basin Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required Information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab reg required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported CDCs Are DMRs complete do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? M ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility Classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? M ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ 0 Comment Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑ Page# 3 Permit. NCO021628 Inspection Date 10/24/2017 Owner - Facility Norwood WWTP Inspection Type. Compliance Evaluation Operations & Maintenance Yes No NA NE Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable 0 ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment It was noted at time of inspection that half of plant is down for maintenance and repairs Bar Screens Yes No NA NE Type -of bar screen Ext Air Type of aeration system a Manual ❑ Is the basin free of dead spots? N ❑ b Mechanical ❑ Are surface aerators and mixers operational? 0 ❑ ❑ Are the bars adequately screening debris? N ❑ ❑ ❑ Is the screen free of excessive debris? N ❑ ❑ ❑ Is disposal of screening in compliance? E ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment Rags and grit are disposed of with dried sludge in landfill It Is recommended that disposal box used to haul off dried sludge be covered to keep rain water out Grit Removal Yes No NA NE Type of grit removal Ext Air Type of aeration system a Manual ❑ Is the basin free of dead spots? N ❑ b Mechanical ❑ Are surface aerators and mixers operational? 0 ❑ ❑ Is the grit free of excessive organic matter? E ❑ ❑ ❑ Is the grit free of excessive odor? 0 ❑ ❑ ❑ ❑ # Is disposal of grit In compliance? E ❑ ❑ ❑ Comment Aeration Basins Yes No NA NE Mode of operation Ext Air Type of aeration system Surface Is the basin free of dead spots? N ❑ ❑ ❑ Are surface aerators and mixers operational? 0 ❑ ❑ ❑ Are the diffusers operational? ❑ ❑ 0 ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? E ❑ ❑ ❑ Is the DO level acceptable? ❑ ❑ ❑ M Is the DO level acceptable?(1 0 to 3 0 mg/1) ❑ ❑ ❑ 0 Page# 4 I Permit. NCO021628 Inspection Date. 10/24/2017 Aeration Basins Owner - Facility Norwood WWTP Inspection Type Compliance Evaluation Yes No NA NE Comment Only one of the two aeation basins in operation Second basin down for clean out and maintenance Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids In center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately % of the sidewall depth) Comment Effluent turbid from heavv rain event on 10/23/2017 One of two clarifiers down for Yes No NA NE ■ ❑ ❑ ❑ N ❑ ❑ ❑ E ❑ ❑ ❑ E ❑ ❑ ❑ E ❑ ❑ ❑ ■ ❑ ❑ ❑ N ❑ ❑ ❑ E ❑ ❑ ❑ E ❑ ❑ ❑ ❑ N ❑ ❑ ❑ ❑ ❑ E replacement of drive unit and center well Pumps -RAS -WAS Yes No NA NE Are pumps in place? E ❑ ❑ ❑ Are pumps operational? 0 ❑ ❑ ❑ Are there adequate spare parts and supplies on site? ❑ ❑ ❑ N Comment Disinfection -Gas Are cylinders secured adequately? Are cylinders protected from direct sunlight? Is there adequate reserve supply of disinfectant? Is the level of chlorine residual acceptable? Is the contact chamber free of growth, or sludge buildup? Is there chlorine residual prior to de -chlorination? Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No 7782-50-5)? If yes, then is there a Risk Management Plan on site? If yes, then what is the EPA twelve digit ID Number? (1 000--) Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ■ ❑ ❑ ❑ E ❑ Page# 5 Permit NC0021628 Owner - Facility Norwood VVVVfP Inspection Date. 10/24/2017 Inspection Type, Compliance Evaluation Disinfection -Gas Yes No NA NE If yes, then when was the RMP last updated? Comment De -chlorination Type of system ? Is the feed ratio proportional to chlorine amount (1 to 1)? Is storage appropriate for cylinders? # Is de -chlorination substance stored away from chlorine containers? Comment Are the tablets the proper size and type? Are tablet de -chlorinators operational? Number of tubes in use? Comment Souium bisuldite used for dechlcrination Flow Measurement - Influent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (if units are separated) Does the chart recorder match the flow meter? Comment Drying Beds Is there adequate drying bed space? Is the sludge distribution on drying beds appropriate? Are the drying beds free of vegetation? # Is the site free of dry sludge remaining In beds? Is the site free of stockpiled sludge? Is the filtrate from sludge drying beds returned to the front of the plant? # Is the sludge disposed of through county landfill? # Is the sludge land applied? (Vacuum filters) Is polymer mixing adequate? Yes No NA NE ❑ ❑ M ❑ ■ 01:11:1 ■ ❑ 1:11:1 ❑ ❑ ■ ❑ ❑ ❑ M ❑ Yes No NA NE Comment Sludge drying beds are inadequate for this facility Sludge handling and treatment equipmenht should be updated to meet facility's needs M ❑ ❑ ❑ M ❑ ❑ ❑ ■ ❑ ❑ ❑ M ❑ ❑ ❑ Yes No NA NE ❑ M ❑ ❑ M ❑ ❑ ❑ M ❑ ❑ ❑ M ❑ ❑ ❑ M ❑ 1:11:1 M ❑ ❑ ❑ M ❑ ❑ ❑ ❑ ❑ M ❑ ❑ ❑ M ❑ Page# 6 Permit NC0021628 owner -Facility Norwood WWTP Inspection Date 10/24/2017 Inspection Type Compliance Evaluation Aerobic Digester Yes No NA NE Is the capacity adequate? ❑ 0 ❑ ❑ Is the mixing adequate? ❑ ❑ 0 ❑ Is the site free of excessive foaming In the tank? 0 ❑ ❑ ❑ # Is the odor acceptable? 0 ❑ ❑ ❑ # Is tankage available for properly waste sludge? ❑ M ❑ ❑ Comment Old Imhoff tank Is being used to thicken and digest sludge Tank appeared to be working Properly at time of Inspection Page# 7