HomeMy WebLinkAboutNC0023876_Compliance Evaluation Inspection Report_20171108Water Resources Environmental Quality November 8, 2017 Mr. Robert Patterson, Water Resources Director City of Burlington PO Box 1358 Burlington, NC 27216-1358 Subject: Compliance Evaluation Inspection Report NPDES Permit NCO023876 South Burlington WWTP, Alamance County Dear Mr. Patterson: ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER Interim Director ECEIVEDAICDECl WR Nov 16 2017 1Nater Quality perrnittir,ig Section On October 11 and 25, 2017, Paul DiMatteo of the Division of Water Resources ("Division"), Winston- Salem Regional Office conducted a Compliance Evaluation Inspection of the above referenced wastewater treatment system. The presence and cooperation of both Mr. Rick Asher and Mr. Glenn McGirt was greatly appreciated. This type of inspection consists of two basic parts: an on-site inspection of the facility and a review of facility files and self-monitoring data. Observations from each area of the inspection are summarized below. Site Review 1. Permit The current permit became effective on July 1, 2014 and expires on June 30, 2019. A copy of the current permit was available for review. Permitted components include a 3.5 million gallon aerated equalization basin, primary and secondary clarifiers, biological nutrient reduction, sand filtration, and gas chlorination. 2. Facility Site Review The facility was as described in the permit. At the time of Inspection, secondary clarifier #4 was down for routine maintenance. It was noted during the previous inspection that the plant planned to replace the gas chlorine disinfection system with liquid chlorine; however, Mr. Asher said that the details had not yet been finalized. The backup power generator is tested under lead for one hour every month. Mr. Asher said that if the generator's fuel tank is full it is capable of powering the entire plant for about 2 days. <5> Noti ing Compares -f__ State of North Carolina I Environmental Quality 450 W. Hanes Mill Road, Suite 300, Winston-Salem, North Carolina 27105 Phone. 336-776-98001 FAX 336-776-9797 3. Operation and Maintenance Rick Asher is the current Operator in Responsible Charge, and Mark Andrews and Elizabeth Whitfield are backup ORCs. All operators are properly designated and hold the correct credentials. However, as of the date of this letter Mr. Andrews has not received the required Continuing Education hours for 2017. The operators use the Hach Water Information Management Systems (WIMS) database to track trends in the treatment process and integrate reporting and documentation, and the Hach JOB Cal systemto track all preventative and repair work at the plant. 4. Flow Measurement Both influent and effluent flow meters are checked every 3 months and calibrated at least once per year by Carolina Tech. The meters were last calibrated in August, 2017. Only the effluent flow is reported. For both influent and effluent flow measurement, a 2 foot Parshall flume is used as the primary flow device, and an ultrasonic flow meter is used as the secondary device. At the effluent, it appeared that the secondary device may not have been in the correct location for accurately measuring flow. To ensure sufficient accuracy of reported flow data, please: a. Verify that the secondary device is in the proper location and that the device and recorder are accurate within 10% of the true flow value, and b. Submit a copy of the next effluent flow meter calibration check and any accompanying adjustments made to the meter to this office for review. 5. Effluent/Receiving Waters The effluent is discharged to the Big Alamance Creek in the Cape Fear River Basin. In -stream monitoring requirements have been waived as long as the City of Burlington remains a member of the Upper Cape Fear River Basin Association. Documentation Review 6. Records/Reports Discharge Monitoring Reports (DMRs) and lab data are maintained according to the permit. DMRs include all permit parameters. Copies of DMRs, operator visitation logs, lab reports and Chain -of - Custody forms were available for review during the inspection. Please note that Permit Part I, Condition A(9) requires a mercury minimization plan to be developed no later than January 1, 2015 and implemented during the permit term. A sample MMP was developed and is available on the Division's website. During the inspection Mr. Asher was not able to produce a copy of the sample MMP, but the facility's own plan was not available. Please ensure that a plan has been developed and implemented, and keep a copy of the plan available for inspection on-site. i 7. Self -Monitoring Program A review of DMRs from September, 2016 through September, 2017 showed only the following violation, which was addressed through separate correspondence: VIOLATIONDATE VIOLATION TYPE VIOLATION ACTION 07/17/2017 Aquatic toxicity permit limit violation Proceed to NOV A comparison of submitted DMR data and field records showed no errors or concerns. 8. Laboratory All parameters are analyzed by the City of Burlington Wastewater Treatment Plant Laboratory under certification #188, except for headworks, toxicity and the effluent pollutant scan, which are analyzed by Meritech under certification #165. When a separate lab analyzes headworks samples, they also analyze all other samples collected that day. Operators of the plant analyze field parameters under the City of Burlington WWTP Lab's certification. Copies of all laboratory documentation are kept at the Burlington WWTP Lab. Effluent composite sampler is flow proportional. The thermometer inside the sampler read 3°C at the time of inspection, and the sampler produced a 150 ml aliquot. Composite samples are taken at around 2 AM every morning, and grab samples are generally taken around 6 AM. Sampling and field parameter measurement procedures appeared acceptable. 9. Sludge Handling Disposal A small percentage of solids from the plant are treated at the compost facility on site. The residuals are pressed and mixed to create the compost, which is sold on site. The remainder of the residuals from the plant are land applied under permit WQ0000520. If you should have any questions, please do not hesitate to contact Paul DiMatteo at (336) 776-9691 or our office at (336) 776-9800. Sincerely, t-L/Sherri V. Knight, P.E., Regional Supervisor Water Quality Regional Operations Section Winston-Salem Regional Office Division of Water Resources, NCDEQ Enclosures —Inspection Report and Summary CC: Rick Asher, by email WQS Winston-Salem Regional Office - Enforcement File NPDES Compliance/Enforcement Unit - Enforcement File Central Files United States Environmental Protection Agency Form Approved EPA Washington, D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires B-31-98 Section A National Data System Coding (i.e, PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 E 2 151 3 I N00023876 I11 12 17/10/11 17 18 I r. I 19 I � j 201I 211 111 1 1 1 1 1 1 11 1 1 I I I I I I I I I I 1 1 I I I I I 1 1 1 1 11 1 1 1 1 1_J6 Inspection Work Days Facility Self-Monitonng Evaluation Rating 131 QA--------Reseryed 67 70 u 71 I I 72 N 73 I X74 75 IJJ80 LJ I I I Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 10 15A 17/10/11 14/07/01 Southside WWTP Exit Time/Date Permit Expirabon Date 2471 Boy Wood Rd 01 00p 17/10/11 19/06/30 Burlington NC 27215 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Richard Brian Asher/ORC/336-227-6261/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Robert C Patterson,PO Box 1358 Burlington NC No 272161358//336-222-5130/3365706175 Section C Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program 0 Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D• Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Paul DiMatteo WSRO WQ//336-776-9691/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date L � 44 EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete Page# NPDES yr/mo/day Inspection Type (Cont.) 31 NCO023876 I11 12 17/10/11 17 18 I e. I Section D. Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Site Review 1 Permit The current permit became effective on July 1, 2014 and expires on June 30, 2019. A copy of the current permit was available for review Permitted components include a 3.5 million gallon aerated equalization basin, primary and secondary clarifiers, biological nutrient reduction, sand filtration, and gas chlorination. 2. Facility Site Review The facility was as described in the permit. At the time of inspection, secondary clarifier #4 was down for routine maintenance. It was noted during the previous inspection that the plant planned to replace the gas chlorine disinfection system with liquid chlorine, however, Mr Asher said that the details had not yet been finalized. The backup power generator is tested under lead for one hour every month. Mr Asher said that if the generator's fuel tank is full it is capable of powering the entire plant for about 2 days. 3 Operation and Maintenance Rick Asher is the current Operator in Responsible Charge, and Mark Andrews and Elizabeth Whitfield are backup ORCs. All operators are properly designated and hold the correct credentials However, as of the date of this letter Mr. Andrews has not received the required Continuing Education hours for 2017. The operators use the Hach Water Information Management Systems (WIMS) database to track trends in the treatment process and integrate reporting and documentation, and the Hach JOB Cal systemto track all preventative and repair work at the plant. 4. Flow Measurement Both influent and effluent flow meters are checked every 3 months and calibrated at least once per year by Carolina Tech The meters were last calibrated in August, 2017 Only the effluent flow is reported. For both influent and effluent flow measurement, a 2 foot Parshall flume is used as the primary flow device, and an ultrasonic flow meter is used as the secondary device. At the effluent, it appeared that the secondary device may not have been in the correct location for accurately measuring flow To ensure sufficient accuracy of reported flow data, please. a Verify that the secondary device is in the proper location and that the device and recorder are accurate within 10% of the true flow value, and b Submit a copy of the next effluent flow meter calibration check and any accompanying adjustments made to the meter to this office for review 5 Effluent/Receiving Waters The effluent is discharged to the Big Alamance Creek in the Cape Fear River Basin. In -stream monitoring requirements have been waived as long as the City of Burlington remains a member of the Upper Cape Fear River Basin Association. Documentation Review 6. Records/Reports , Discharge Monitoring Reports (DMRs) and lab data are maintained according to the permit. DMRs include all permit parameters. Copies of DMRs, operator visitation logs, lab reports and Chain -of -Custody forms were available for review during the inspection. Please note that Permit Part I, Condition A(9) requires a mercury minimization plan to be developed no later than January 1, 2015 and implemented during the permit term. A sample MMP was developed and is available on the Division's website. During the inspection Mr. Asher was not able to produce a copy of the sample MMP, but the facility's own plan was not available. Please ensure that a plan has been developed and implemented, and keep a copy of the plan available for inspection on-site 7. Self -Monitoring Program A review of DMRs from September, 2016 through September, 2017 showed only the following violation, which was addressed through separate correspondence• Page# Permit: NCO023876 Inspection Date: 10/11/2017 Owner -Facility. SouthsideWWTP Inspection Type Compliance Evaluation VIOLATIONDATE VIOLATION TYPE VIOLATION ACTION 07/17/2017 Aquatic toxicity permit limit violation Proceed to NOV A comparison of submitted DMR data and field records showed no errors or concerns 8. Laboratory All parameters are analyzed by the City of Burlington Wastewater Treatment Plant Laboratory under certification #188, except for headworks, toxicity and the effluent pollutant scan, which are analyzed by Meritech under certification #165 When a separate lab analyzes headworks samples, they also analyze all other samples collected that day Operators of the plant analyze field parameters under the City of Burlington WWTP Lab's certification. Copies of all laboratory documentation are kept at the Burlington WWTP Lab. Effluent composite sampler is flow proportional. The thermometer inside the sampler read YC at the time of inspection, and the sampler produced a 150 ml aliquot Composite samples are taken at around 2 AM every morning, and grab samples are generally taken around 6 AM. Sampling and field parameter measurement procedures appeared acceptable 9. Sludge Handling Disposal A small percentage of solids from the plant are treated at the compost facility on site The residuals are pressed and mixed to create the compost, which is sold on site The remainder of the residuals from the plant are land applied under permit WQ0000520. Page# Permit NCO023876 Owner - Facility. Southside wwTP Inspection Date- 10/11/2017 Inspection Type- Compliance Evaluation V Operations $ Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑ Does the facility analyze process control parameters, for ex- MLSS, MCRT, Settleable 0 ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment Permit Yes No NA NE (If the present permit expires in 6 months or less) Has the permittee submitted a new ❑ ❑ 0 ❑ application? M ❑ ❑ ❑ Is the facility as described in the permit? M ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ ❑ ❑ Is access to the plant site restricted to the general public? M ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? M ❑ ❑ ❑ Comment. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? M ❑ ❑ ❑ Is all required information readily available, complete and current? M ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ❑ ❑ ❑ ❑ Is the chain -of -custody complete? ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete- do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? 0 ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator N ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? M ❑ ❑ ❑ Page# 4 N Permit, NCO023876 Inspection Date: 10/11/2017 Record Keeping Facility has copy of previous year's Annual Report on file for review? Owner -Facility: SouthsideWWTP Inspection Type Compliance Evaluation Yes No NA NE ■ ❑ ❑ ❑ Comment: Mr Asher said that almost all laboratory documents are sent to and kept bv_the City's Water Resources lab. Yes No NA NE # Is flow meter used for reporting? M ❑ Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? M ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? M ❑ ❑ ❑ Is flow meter calibrated annually? N ❑ ❑ ❑ Is the flow meter operational? N ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment- Both influent and effluent flow meters are checked about every 3 months and calibrated at least once per year by Carolina Tech. Only the effluent flow is reported. Secondary effluent flow device is a Siemens Milltronics OCM III. Primary flow device is a 2' Parshall flume. It appeared that the secondary device may not have been in the correct location Please verify that the secondary device is in the proper location and that the device and recorder are accurate to within 10% of the true flow value. Equalization Basins Yes No NA NE Is the basin aerated? 0 ❑ ❑ ❑ Is the basin free of bypass lines or structures to the natural environment? M ❑ ❑ ❑ Is the basin free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? 0 ❑ ❑ ❑ Are all pumps operable? ❑ ❑ ❑ Are float controls operable? ❑ ❑ ❑ Are audible and visual alarms operable? ❑ ❑ ❑ 0 # Is basin size/volume adequate? 0 ❑ ❑ ❑ Comment: Primary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? 0 ❑ ❑ ❑ Page# 5 Permit NCO023876 Owner -Facility. Southside WWTP Yes No NA NE Is the clarifier free of black and odorous wastewater? N ❑ Inspection Date- 10/11/2017 Inspection Type Compliance Evaluation ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? M ❑ Primary Clarifier Yes No NA NE Are weirs level? M ❑ ❑ ❑ Is the site free of weir blockage? M ❑ ❑ ❑ Is the site free of evidence of short-circuiting? M ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? M ❑ ❑ ❑ Is the drive unit operational? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? ❑ ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately '/a of the sidewall depth) ❑ ❑ ❑ M Comment Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? N ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? M ❑ ❑ ❑ Are weirs level? M ❑ ❑ ❑ Is the site free of weir blockage? M ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? 0 ❑ ❑ ❑ Is the return rate acceptable (low turbulence)? 0 ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately 1/4 of the sidewall depth) 0 ❑ ❑ ❑ Comment: Sludge blanket level was — 6 inches ORC said he tries to keep it at this level because of a possible premature release of phosphorus if the level is higher. Clarifier #4 is out of service for maintenance. Aeration Basins Mode of operation Type of aeration system Is the basin free of dead spots? Are surface aerators and mixers operational? Are the diffusers operational? Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Yes No NA NE Ext Air Diffused M ❑ ❑ ❑ ❑ ❑ ■ ❑ M ❑ ❑ ❑ ■ ❑ ❑ ❑ M ❑ ❑ ❑ Page# 6 B Permit NCO023876 Owner - Facility. Southside WwTP Inspection Date. 10/11/2017 Inspection Type- Compliance Evaluation Aeration Basins Yes No NA NE Is the DO level acceptable? N ❑ ❑ ❑ Is the DO level acceptable?(1 0 to 3.0 mg/1) 0 ❑ ❑ ❑ Comment: Nutrient Removal Yes No NA NE # Is total nitrogen removal required? ❑ ❑ ❑ ❑ # Is total phosphorous removal required? ❑ ❑ ❑ ❑ Type N ❑ ❑ ❑ # Is chemical feed required to sustain process? ❑ ❑ ❑ ❑ Is nutrient removal process operating properly? ❑ ❑ ❑ ❑ Comment. Disinfection -Gas Yes No NA NE Are cylinders secured adequately? N ❑ ❑ ❑ Are cylinders protected from direct sunlight? 0 ❑ ❑ ❑ Is there adequate reserve supply of disinfectant? N ❑ ❑ ❑ Is the level of chlorine residual acceptable? ❑ ❑ ❑ E Is the contact chamber free of growth, or sludge buildup? E ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ 0 Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No 7782-50-5)? ❑ ❑ ❑ 0 If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ 0 If yes, then what is the EPA twelve digit ID Number? (10007 Ifyes, then when was the RMP last updated? Comment. Standby Power Yes No NA NE Is automatically activated standby power available? 0 ❑ ❑ ❑ Is the generator tested by interrupting primary power source? 0 ❑ ❑ ❑ Is the generator tested under load? N ❑ ❑ ❑ Was generator tested & operational during the inspection? ❑ ❑ ❑ E Do the generator(s) have adequate capacity to operate the entire wastewater site? E ❑ ❑ ❑ Is there an emergency agreement with a fuel vendor for extended run on back-up power? ❑ ❑ ❑ Is the generator fuel level monitored? ❑ ❑ ❑ Page# 7 Permit- NCO023876 Inspection Date. 10/11/2017 Standby Power Comment: Owner - Facility Southside WWTP Inspection Type. Compliance Evaluation Laboratory Are field parameters performed by certified personnel or laboratory? Are all other parameters(excluding field parameters) performed by a certified lab? # Is the facility using a contract lab? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Incubator (Fecal Coliform) set to 44 5 degrees Celsius+/- 0.2 degrees? Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees? M Yes No NA NE Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment Accordinq to their thermometers BOD Incubator was 19 5 C and fecal coliform Incubator was 44.5 C at the time of Inspection. Influent Sampling Yes No NA NE # Is composite sampling flow proportional? ❑ ❑ ❑ M Is sample collected above side streams? 0 ❑ ❑ ❑ Is proper volume collected? ❑ ❑ ❑ 0 Is the tubing clean? M ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ ❑ Celsius)? Is sampling performed according to the permit? N ❑ ❑ ❑ Comment: Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ ❑ Is sample collected below all treatment units? ❑ ❑ ❑ Is proper volume collected? ❑ ❑ ❑ N Is the tubing clean? M ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type ❑ ❑ ❑ representative)? Comment: Flow Measurement - Influent Yes No NA NE Page# 8 9 Permit• NC0023876 Owner -Facility. SouthsideWWTP Inspection Date- 10/11/2017 Inspection Type Compliance Evaluation Flow Measurement - Influent Yes No NA NE # Is flow meter used for reporting? ❑ M ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? N ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ N ❑ Comment Influent flow measuring primary device is a 24" Parshall flume with an ultrasonic secondary device. Page# 9