HomeMy WebLinkAboutNC0032867_NOV2017PC0602_20171117WaterResources
NVIRONMENTAL QUALITY
November 6, 2017
CERTIFIED MAIL # 70151370 0000 2595 7313
RETURN RECEIPT REQUESTED
Laeeq Khan, President
Malik's International, Inc.
3425 Carnoustie Drive
Chambersburg, PA 17202
Subject: Notice of Continuing Violation
Tracking Number NOV-2017-PC-0602
Kings Mountain Travel Plaza WWTP
NPDES Permit NCO032867
Cleveland County
Dear Mr. Khan:
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Interim Director
RECEIVED/WDEOWR
NOV 14 2011
;Uality
c• ,, W, 'ection
Please find enclosed the Compliance Evaluation Inspection conducted on November 2, 2017 by Ori Tuvia.
The cooperation of Daniel Dougherty and Ron Haynes during the site visit was much appreciated.
The facility has shown progress with regard to determining if the effluent from the truck stop reaches
the treatment unit but the following violations still need to be addressed:
In accordance with Part II, Section D.6 of the subject permit, (Records and Retention), "Except for
records monitoring information required by this permit related to the permittee's sewage sludge
use and disposal activates, which shall be retained for a period of at least five years (or longer as
required by 40 CFR,503), the permittee'shall retain records of all monitoring information
including,,:
• All calibration and maintenance records
• All original strip chart recording of continuous monitoring instrumentation
• Copies of all reports required by the permit
• Copies of all data used to complete the application for this permit.
These records or copies shall be maintained for a period of at least three (3) years from the date of the
sample, measurement, report or application. At the time of the inspection, no records were available for
review for the period August 1, 2014 through August 1, 2017. It is the duty of the permittee to maintain all
records for a least three (3) years. The records that were unavailable include:
• Discharge Monitoring Reports (DMRs)
• Lab results with Chain of Custody
Is Flow meter readings
• pH and other relevant instrument calibration records
Mooresville Regional Office
Location, 610 East Center Ave, Suite 301 Mooresville, NC 28115
• ORC log (including visitation records)
• Septic tank pumping records
• Maintenance logs
2. In accordance with Part II, Section C.2 of the subject permit, proper Operation and Maintenance
(0&M) of the WWTP is required. As noted at the time of the inspection, the following areas of
concern should be addressed:
• Dye test is needed to determine if the effluent from the truck stop reaches the treatment
unit and to the find the location of the second discharge location. This should be
investigated as low solids could indicate that no solids are reaching the wastewater
treatment plant.
• septic tank must be properly sealed to avoid leaching wastewater to the ground.
• The facility has two (2) treatment trains: One is active and the other is inactive. The active
train has broken grating. The inactive treatment train has missing grating. Proper grating is
needed to insure a safe work environment.
Please be advised this letter is a Notice of Continuing Violation. If all issues are not resolved or addressed
within fifteen (15) days of receipt, the next step will be the issuance of a Notice of Violation and Notice of
Recommendation for Enforcement (NOV/NRE).
A Notice of Violation and Notice of Recommendation for Enforcement, pursuant to G.S. 143-215.6A, may
result in a civil penalty of not more than twenty-five thousand dollars ($25,000.00) per day, per violation and
may be assessed against any person who violates or fails to act in accordance with the terms, conditions, or
requirements of any permit issued pursuant to G.S. 143-215.1.
The report should be self-explanatory; however, should you have any questions concerning this report,
please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia@ncdenr.gov.
Sincerely,
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
Cc: Ron Haynes (E -copy)
NPDES (Derek Denard)
MRO Files
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A National Data System Coding (i e, PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 u 2 15 1 3 I NCO032867 I11 12 17/11/02 17 18 ICI 19 I S I 20I
21111111 111111111111111111 1111111 11111111111 166
I
Inspection Work Days Facility Self-Mondonng Evaluation Rating B1 QA Reserved
67 10 70 I I 71 I I 72 L N C 731 I 174 75 80
u LJ LJ_J
Section B Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09 55AM 17/11/02
14/01/01
Kings Mountain Travel Plaza
400 Dixon School Rd
Exit Time/Date
Permit Expiration Date
Kings Mountain NC 28086
11 10AM 17/11/02
18/08/31
Name(s) of Onsite Representative(s)/TiUes(s)/Phone and Fax Numbers)
Other Facility Data
///
Daniel James Dougherty/ORC/704-477-5514/
W Ronald Haynes/ORC/828-495-4268/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Laeeq Khan,PO Box 805 Kings Mtn NC
280860805/President/704-739-6415/7047390732 No
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
On A Tuvia MRO W0//704-663-1699/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previotys edibons are obsolete• � � /�
Page#
NPDES
yr/mo/day
31 NCO032867 111 121 17/11/02 117
Inspection Type
18 ICI
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Previous Inspection resulted In a NOV (NOV-2017-PC-0602)
Violations found during the follow up Inspection are under the same NOV code
1
` a
r•'nw v `moi , �%
Page# 2
Permit NCO032867 Owner -Facility K ngs Mountain Travel Plaza
Inspection Date 11/02/2017 Inspection Type Compliance Evaluation
Permit
Yes No NA NE
(if the present permit expires in 6 months or less) Has the permittee submitted a new
❑
❑
0
❑
application?
❑
❑
❑
❑
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
E
❑
❑
Is access to the plant site restricted to the general public?
N
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment Previous Inspection resulted in a NOV (NOV-2017-PC-0602)
Violations found during the follow up Inspection are under the same NOV code
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
❑
0
❑
❑
Is all required information readily available, complete and current?
❑
❑
❑
❑
Are all records maintained for 3 years (lab reg required 5 years)?
❑
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
N
❑
Is the chain -of -custody complete?
❑
❑
0
❑
Dates, times and location of sampling
❑
❑
❑
❑
Name of individual performing the sampling
❑
❑
❑
❑
Results of analysis and calibration
❑
❑
❑
❑
Dates of analysis
❑
❑
0
❑
Name of person performing analyses
❑
Transported COCs
❑
Are DMRs complete do they include all permit parameters?
❑
❑
E
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(if the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
E
❑
on each shift?
Is the ORC visitation log available and current?
❑
M
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
N
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment No records were available for review for the period of August 1 .2014 - August 1, 2017
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ N ❑ ❑
Page# 3
Permit NCO032867
Inspection Date 11/02/2017
Owner -Facility Kings Mountain Travel Plaza
Inspection Type Compliance Evaluation
Operations & Maintenance Yes No NA NE
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable ❑ ❑ 0 ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment, ORC log records were not available for review for the period of August 1 .2014 - August 1.
2017.
At the time of the inspection the facility needed the following items to be
repaired/investigated (see attached letter)
Septic Tank
Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
❑
0
❑
❑
Is septic tank pumped on a schedule?
❑
❑
E
❑
Are pumps or syphons operating properly?
❑
0
❑
❑
Are high and low water alarms operating properly?
❑
❑
0
❑
Comment Septic tanks were pumped since the last inspection it was discovered that a septic tank has
cracks in and leaches waste into the ground