HomeMy WebLinkAboutNC0061123_Compliance Inspection Report_20170918A' . �
' WMS- T
Certified Mail # 7016 1370 0001 6571 8027
Return Receipt Requested
September 18, 2017
Matthew Velker
The Mountain Retreat & Learning Center
PO Box 1299
Highlands, NC 28741-1299
*19"
RECEI V ED NCDEW WR
SUBJECT: Compliance Inspection Report SEP 2 5 2017
The Mountain Retreat & Learning Center WWTP
NPDES WW Permit No. NCO061123 Water Quality
Macon County Permitting Section
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the The Mountain
Retreat & Learning Center WWTP on 9/12/2017. This inspection was conducted as part of the
permit renewal process and to discuss options for a potential permit modification. Items noted
and discussed during the inspection can be found in the attached Compliance Inspection
Report.
There were no significant issues or findings noted during the inspection and therefore, a
response to this inspection report is not required. If you should have any questions, please do
not hesitate to contact me at 828-296-4500 or via email at mikal.willmer@ncdenr.gov.
Sincerely,
DocuSigned by
C� 4B4
OBABAEBEC2434B4
Mika[ Willmer, Environmental Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Cc WQS Asheville Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
G \WR\WQ\Macon\Wastewater\Minors\Mountain Retreat 61123\Inspections\Inspect.
9-12-17\NC0061123.CVRLTR.091317. rtf
State of North Carolina I Environmental Quality I Water Resources
2090 U S 70 Highway, Swannanoa, NC 28778
828-296-4500
DocuSign Envelope ID D30FD396-2DF9-4C84-A21E-A20272E573F2
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
-- - -- - WaterCampliance Inspactlon Report__ -`--4= '
ApprovaleXpirerSs=-31-98--Section
A National Data System Coding (i e , PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 E 2 15 I 3 I NCO061123 I11 12 17/09/12 117 18 Li I 19 I G I 201
21111111 1111111111111111111111111 11111111111 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA -Reserved —
67 70 I I 71 I I 72 L r, � 731 1 174 75III
l_1 LJ I 1 I
80
Section B Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10 15AM 17/09/12
12/09/01
The Mountain Retreat & Learning Center WWTP
3872 Dillard Rd
Exit Time/Date
Permit Expiration Date
Highlands NC 28741
11 30AM 17/09/12
17/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Brandon Keith Buchanan/ORC/828-586-5588/
Name, Address of Responsible Official[Title/Phone and Fax Number
Contacted
Matthew Velker,PO Box 1299 Highlands NC 287411299//828-526-5838/8285264505
Yes
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit E Flow Measurement E Operations & Maintenance N Facility Site Review
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy R Fox DocuSigned by ARO WQ//828-296-4500/
Mika[ WillmerE ARO WQ//828-296 4686/ 9/13/2017
zlz,�
OBABAEBEC2434B4
Signature of Manage me o Mp&% Agency/Office/Phone and Fax Numbers Date
_ 9/13/2017
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete
Page#
DocuSign Envelope ID D30FD396-2DF9-4C84-A21E-A20272E573F2
NPDES yr/mo/day Inspect(on Type (Cont)
31 NCO061123 I11 12 17/09/12 17 18 ICI
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Inspectors Mika] Willmer and Tim Fox with the Asheville Regional Office conducted a Compliance
Evaluation Inspection of the WWTP that serves the Mountain Retreat and Learning Center on
September 12, 2017 This inspection was conducted as part of the permit renewal process and to
discuss options for a potential permit modification. Ted Wisniewski,with the Mountain Retreat, was
present and assisted in the inspection.
Overall it appeared the plant is being well maintained The facility is located a quarter of a mile down a
gravel access road on the property Public access is limited because of its location, however, the
Mountain Retreat may wish to consider installing a fence around the surface sand filters This would
prevent public access to the plant and would help prevent wildlife from disturbing the sand filters and
distribution lines
Influent flow is used for permit reporting Please clarify if the facility has a continuous discharge If so,
weekly instantaneous flow readings and required monitoring parameters are to be sampled and
recorded on the monthly DMRs
The permittee is considering requesting a switch to Ammonia limits in lieu of Chronic Toxicity Testing
The options and speculative limits for such a switch were discussed during the inspection The WWTP
discharges into Abes Creek, a Class C, Tr, ORW The Summer 7Q10 for Abes Creek is currently
listed as 0. Suggested the Permittee contact the USGS for a re-evaluation of 7Q10 flow before
requesting a permit modification At current 7Q10 flows, speculative summer ammonia limits would be
1 mg/L and 13 mg/L during the winter The addition of ammonia limits would require more frequent
monitoring than chronic toxicity and may require additional treatment to meet limits consistently
Page#
DocuSign Envelope ID D30FD396-2DF9-4C84-A21E-A20272E573F2
Permit NCO061123 Owner - Facddy The Mountain Retreat & Learning Center WWI
Inspection Date- 09/12/2017 Inspection Type Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable ❑ ❑ E ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment This facility consists of multiple septic tanks and two surface sand filters See summary for
additional details
Permit Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted a new 0 ❑ ❑ ❑
application?
Is the facility as described in the permit?
®
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment The wwtp is located a 1/4 of a mile down an access road The Mountain Retreat may wish
to install a fence around some of the treatment units to prevent potential public access A
fence may also help prevent wildlife from disturbing the sand filter and distribution lines.
Sand Filters (Low rate)
Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
❑
❑
0
❑
Is the distribution box level and watertight?
0
❑
❑
❑
Is sand filter free of ponding?
E
❑
❑
❑
Is the sand filter effluent re -circulated at a valid ratio?
❑
❑
❑
0
# Is the sand filter surface free of algae or excessive vegetation?
0
❑
❑
❑
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
❑
❑
❑
0
Comment Two surface sand filters Upper sand filter was not beinq used during the site visit Flow was
directed to lower sand filter Maintenance manager recently raked both sand filters
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? E ❑ ❑ ❑
Are the tablets the proper size and type? N ❑ ❑ ❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑ ❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑ E
Comment Staff are currently using Norweco tablets supplied by Environmental Inc
Page# 3
DocuSign Envelope ID D30FD396-2DF9-4C84-A21E-A20272E573F2
Permit NC0061123 Owner - Facility The Mountain Retreat & Learning Center WWI
Inspection Date- 09/12/2017 Inspection Type Compliance Evaluation
De -chlorination
Yes No NA NE
Type of system?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑ ❑
E
❑
Is storage appropriate for cylinders?
❑ ❑
N
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
E
❑
Comment
Are the tablets the proper size and type? N ❑ ❑ ❑
Are tablet de -chlorinators operational? N ❑ ❑ ❑
Number of tubes in use? 2
Comment Maintenance staff monitor tablets dL nng routine visits throughout the week