HomeMy WebLinkAboutNC0089095_NOV2017PC0604_20170917T 0y, Comm
�r�ar
9. JAYZIMMERMAN
Certified Mail # 7004 0750 0000 2589 9774
Return Receipt Requested
September 11, 2017 '7
Aubrey L Deaver
A&D Water Service Inc
PO Box 1407
Pisgah Forest, NC 28768-1407 T a
cg! V
SUBJECT: NOTICE OF VIOLATION
Tracking Number: NOV-2017-PC-0604
Permit No. NCO089095 RECEIVED/NCDENWR
High Vista Falls WWTP
Henderson County SEP 2 5 2017
Dear Permittee: Watei Quality
Permitting Section
The North Carolina Division of Water Resources conducted an inspection of the High Vista Falls WWTP on
August 24, 2017. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0089095. A summary of the findings and
comments noted during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Sampling inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following violation(s) were noted during the inspection:
Inspection Area Description of Violation
Effluent Sampling The effluent sampling is not flow proportional as required by the permit.
In addition, the issues below must also be addressed:
Compliance Issue(s):
#3 Freshwater pump high water alarm was not functioning and must be repaired.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law.
State of North Carolina I Environmental Quality I Water Resources
2090 U S 70 Highway, Swannanoa, NC 28778
828-296-4500
To prevent further action, please respond in writing to this office within 15 days upon your receipt of this Notice
of Violation regarding your plans or measures to be taken to address the indicated violations and other identified
issues, if. -applicable.
If you should have any questions, please do not hesitate to contact Timothy Heim with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4500.
Sincerely,
a: Davidson, P.G., Regions OL—
Water Quality Regional Operations Section
A3heville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Vince Edwards, ORC (electronic copy)
WQS Asheville Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
G:\WR\WQ\Henderson\Wastewater\Minors\High Vista Falls 89095\NOV-2017-PC-0604.rtf
State of North Carolina I Environmental Quality I Water Resources
2090 U S 70 Highway, Swannanoa, NC 28778
828-296-4500
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
---Water Compliance Inspection Report -
Approval expires 8-31-98
Section A National Data System Coding (i e, PCS)
Transaction Code NPDES yr/mo/day Inspection Type
Inspector Fac Type
1 IN 2 15 1 3 I N00089095 I11 12 17/08/24 17 181-1
Lfj
19 L G I 20I I
21111111111111111111111111111111111111111111
t66
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA
Reserved -------
67 70 I I 71 I I 72 L LJN C 73 L I J74 75 80
L_I it
Section B FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09 30AM 17/08/24
15/11/01
High Vista Falls WWTP
Creasman Hill Rd
Exit Time/Date
Permit Expiration Date
Mills River NC 28759
12 0OPM 17/08/24
20/10/31
Name(s) of Onsite Representabve(s)/Tities(s)/Phone and Fax Number(s)
Other Facility Data
Vincent L Edwards/ORC/828-697-3077/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Patty Cariand,117 Kira Ln Hendersonville NC 2 87 3 9//8 2 8-8 9 0-4 8 1 0/
Yes
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & MaintenanC6 0 Self -Monitoring Program
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspectors) Agency/Office/Phone and Fax Numbers
Date
Beverly Price ARO WQ//828-2964500/
Timothy H Heim ARO WQ//828-296-4665/
IT) A,)I? 1?
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers
(-Date /
�/( S—/ %Z
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete
Page#
NPDES
yr/mo/day
31 Ncooasoss I11 12 17/08/24 17
Inspection Type (Cont)
- -- 18-U-- _- -
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim and Bev Price of the Asheville Regional Office performed a Compliance Evaluation
Inspection on August 24rd, 2017 Vince Edwards (ORC) assisted with the inspection and facility
review This inspection was a follow up to a previous inspection performed on July 21, 2016
During the July 21, 2016 inspection, the followiN items were noted
-The EQ basin float alarms were located inside the blower building, it is very difficult to see/hear them if
they are activated In a letter dated July 28, 2016, Mr Aubrey Deaver indicated that this would be
corrected by relocation of the alarms outside the building This had not occurred at the time of the 2017
inspection
-The composite effluent sampling was not flow proportional as required by the permit Mr Deaver was
directed to submit a request for time/constant volume sampling to the Regional Office for approval by
the Director to continue time/constant volume sampling This had not occurred at the time of the 2017
inspection, and this item continues to be non-compliant
During the August 24, 2017 Inspection, the following additional non-compliant items were noted
- #3 Freshwater pump high water alarm was not functioning
It is also suggested that the emergency backup generated be tested under load regularly, and sufficient
fuel be maintained in the tank to accommodate a multiday outage
Page#
Permit NCO089095
Inspection Date. 08/24/2017
Owner -Facility High Vista Falls WWrP
Inspection Type Compliance Evaluation
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment The effluent sampling Is not flow proportional as required by the permit
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
❑ ■ ❑ ❑
M ❑ ❑ ❑
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑