Loading...
HomeMy WebLinkAboutNC0081621_Compliance Evaluation Inspection_20170810Water Resources ENVIRONMENTAL QUALITY August 10, 2017 Mr Timothy Mauldin Waste Water Operations Manager Water & Sewer Authority of Cabarrus County Post Office Box 428 Concord, North Carolina 28086 SUBJECT Compliance Evaluation Inspection Muddy Creek WWTP NPDES Permit NC081621 Cabarrus County, NC Dear Mr Mauldin: ROY COOPER Govemor MICHAEL S. REGAN Secretary S JAY ZIMMERMAN Director On August 08, 2017, Roberto Scheller of this Office conducted an inspection at the subject facility This inspection was conducted as a Compliance Evaluation Inspection (CEI) to insure compliance with permit requirements and conditions At the time of inspection facility appeared to be very well maintained and operated, however, an issue with the influent sampler was noted during the subject Inspection Please check the influent sampler to ensure sampler is located above all side streams of wastewater, such as backwash water and/or supernatant from sludge dewatering being sent back to head of plant Such side streams would skew Influent analytical data and miss represent treatment plant loading and removal rates It was also noted that this facility experienced a plant upset that was reported to this Office on July 14, 2017 It is the recommendations of this Office that headworks be fitted with pH, DO and ORP probes to detect damaging Influents and divert to equalization basin before they reach treatment units We wish to thank you and the operating staff for assistance regarding this inspection The enclosed report should be self-explanatory, however, should you have any questions, please do not hesitate to contact myself of Roberto Scheller at (704) 235-2204 or roberto.scheller@ncdenr.gov. Sincerely, W Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations Mooresville Regional Office) 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115 704 663 1699 United States Environmental Protection Agency Form Approved EPA Washington, D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires B-31-98 Section A National Data System Coding (i e, PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 I 3 I NCO081621 I11 12 17/08/08 17 18 1,.1 19 L! -i 201 I 211111 1 1 1 1 1 111 I I I I I I I I I I I I 1 I I I I I I I I I 111 11 1 I Il66 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---Reserved--I 67 70 JLJ j 71 L] 72 L N C 731 I 174 751 I I I I I I 180 l� I I I Section B Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09 50AM 17/08/08 14/10/01 Muddy Creek WWTP Exit Time/Date Permit Expiration Date 14655 Hopewell Church Rd 12 23PM 17/08/08 18/10/31 Midland NC 26107 Name(s) of Onsite Representative(s)rritles(s)/Phone and Fax Number(s) Other Facility Data /// Kimberly Dawn HoIUORCl704-788-4164/ Name, Address of Responsible OfficiaUTitle/Phone and Fax Number Contacted Coleman M Keeler, PO Box 428 Concord NC 280260428/Executive No D i re cto r/7 0 4-7 86-1 7 8 3170 47 9 51 5 64 Section C Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program N Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date ,Robertj Scheller MRO WQ!/252-946-6481/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W Corey Basinger MRO WQ//704-235-2194/ EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete r■iAIF Page# I Permit NCO081621 Owner - Facility Muddy Creek WWTP Inspection Date 08/08/2017 Inspection Type Compliance Evaluation It Is Permit Yes No NA NE (If the present permit expires in 6 months or less) Has the permittee submitted anew ❑ ❑ E ❑ application? Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 Is the facility as described In the permit? N ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? M ❑ ❑ ❑ Is the Inspector granted access to all areas for inspection? N ❑ ❑ ❑ Comment The current permit became effective on October 1, 2014 and shall expire on midnight October 21 2018 Permit is for the Continued operation of a 0 15 MGD wastewater treatment system Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? E ❑ ❑ ❑ Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable 0 ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment Top stair leading up to equalization basin in not suported along back of stair tread It Is recommended that back edge of stair tread be supported to prevent metal fetuge and failure of step Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab reg required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? E ❑ ❑ ❑ Is the chain -of -custody complete? ❑ ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported CDCs Are DMRs complete do they include all permit parameters? E ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ E (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ N ❑ on each shift? Is the ORC visitation log available and current? * ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? E ❑ ❑ ❑ Page# 3 N 1 Permit. NCO081621 Inspection Date 08/08/2017 Bar Screens Is the unit in good condition? Owner -Facility Muddy Creek WWTP Inspection Type- Compliance Evaluation Yes No NA NE ■ ❑ ❑ ❑ Comment Mechanical barscreen was operating at time of Inspection It was noted that mechanical barscreen is fitted with a manual bypass Screenings drop down into a dumpster and are disposed in a sanitary landfill Equalization Basins Is the basin aerated? Is the basin free of bypass Imes or structures to the natural environment? Is the basin free of excessive grease? Are all pumps present? Are all pumps operable? Are float controls operable? Are audible and visual alarms operable? # Is basin size/volume adequate? Yes No NA NE N ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ N ❑ ❑ ❑ ■ ❑ ❑ ❑ E ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment Equalization basin pumps Into a dual train units where flow is divided among treatment tanks Aeration Basins Yes No NA NE Mode of operation Ext Air ❑ ❑ Type of aeration system Diffused N ❑ Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ E ❑ Are the diffusers operational? E ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? E ❑ ❑ ❑ Is the DO level acceptable? ❑ ❑ ❑ E Is the DO level acceptable?(1 0 to 3 0 mg/1) ❑ ❑ ❑ N Comment Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? N ❑ ❑ ❑ Are weirs level? 0 ❑ ❑ ❑ Is the site free of weir blockage? ❑ ❑ ❑ Is the site free of evidence of short-circuiting? N ❑ ❑ ❑ Page# 5 Permit NCO081621 Owner - Facility Muddy Creek WVTFP Inspection Date 08/08/2017 Inspection Type Compliance Evaluation Effluent Sampling Yes No NA NE # Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees M ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type M ❑ ❑ ❑ representative)? Comment Effluent sampler apeared to be operating properly, temperature was recorded at 3 degrees Celsius at time of Inspection Page# 7