Loading...
HomeMy WebLinkAboutNC0060259_Compliance Evaluation Inspection_201708075pA Water resources VIRONKRNTAL QUALITY August 7, 2017 Mr. James Radford NC Land Lease LLC PO Box 2533 Christiansburg, VA 24068 Ploy COOPER Cry 0worr MICHAEL S. 8i EGAN soc efory S. JAY ZIMI ERMAN Dimdar RECEIVED/NCDE0/0WR AUG 0 9 2017 Water Quality Permitting Section Subject: Compliance Evaluation Inspection Report NPDES Permit NCO060259 Willow Oak Mobile Home Park WWTP, Rockingham County Dear Mr. Radford: On July 17, 2017, Paul DiMatteo of the Division of Water Resources ("Division"), Winston-Salem Regional Office conducted a Compliance Evaluation Inspection of the above referenced wastewater treatment system. Paul Smith, Operator in Responsible Charge (ORC), was present for the inspection. An inspection summary follows and an inspection report is attached for your records. Site Review 1. Permit The current permit became effective on July 1, 2016 and expires on April 30, 2021. A copy of the current permit was not available for review — one should be kept for inspection. Permitted components include a bar screen, facultative lagoons and alum feed tanks. 2. Facility Site Review The facility was as described in the permit. Flow is low compared to the permitted amount (permitted for 22,000 gpd; average reported flow over the last 2 years is about 150 gpd). 3. Operation and Maintenance The operator or a properly designated backup visits the site as required. Visitation logs were current and available during the inspection. The 4th chamber of the alum feed system was observed to be leaking on the lagoon -facing side. A follow-up visit was conducted on July 31 to verify that the leak had been plugged, but the ORC mentioned additional maintenance may be needed. State of North Carolina 1 Environmental Quality I Water Resources dan m t w-- &NI Rnad Nuite 40n Wmetnn-.Salem. NC 27105 A.. 4. Flow Measurement The permit requires instantaneous flow measurement influent or effluent. Flow is measured at the influent. 5. Effluent/Receiving Waters The effluent is discharged into Little Troublesome Creek. The outfall was not accessible during the inspection due to the lack of a path and swampy ground. Documentation Review 6. Records/Reports Discharge Monitoring Reports (DMRs) and lab data are maintained according to the permit. DMRs include all permit parameters. Copies of DMRs, operator visitation logs, lab reports and Chain -of - Custody forms were available for review during the inspection. 7. Self -Monitoring Program A review of DMRs from May, 2016 through May, 2017 showed no violations. A comparison of submitted DMR data with bench sheets did reveal one minor error on the August, 2016 DMR. Mr. Smith said he would more carefully check that the data has been transferred correctly before submittal. 8. Laboratory Field parameters are measured by the ORC under certification # 5169 (Smith Industries). All effluent samples are taken from the aerobic digester. All other parameters are measured by Pace Analytical under certification # 633. Chain -of -custody forms were complete and available for all parameters measured off site. Records for parameters measured on-site were complete. 9. Sludge Handling Disposal Sludge is removed from the plant as needed. If you should have any questions, please do not hesitate to contact Paul DiMatteo at (336) 776-9691 or our office at (336) 776-9800. Sincerely, Sherri V. Knight, P.E., Regional Supervisor Water Quality Regional Operations Section Winston-Salem Regional Office Division of Water Resources, NCDEQ Enclosures — Inspection Report and Summary CC: Paul Smith — by email WQS Winston-Salem Regional Office - Enforcement File NPDES Compliance/Enforcement Unit - Enforcement File Central Files State of North Carolina I Environmental Quality I Water Resources 450 West Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 United States Environmental Protection Agency Form Approved EPA Washington, D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires 6-31-96 Section A National Data System Coding (i e, PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 I 3 I NCO060259 I11 12 17/07/17 17 18 I S I 19 I c I 20 f 21111111111111111111111111111111111111111111 166 I --Reserved Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA -----Reserved 67 70 I 71 I I 72 I N I 731 I 174 75 80 LJ L J I I I Section B Faciility—Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES Dermit Number) 10 30AM 17/07/17 16/07/01 Willow Oaks Exit Time/Date Permit Expiration Date 109 Southfork Dr 11 30A 17/07/17 21/04/30 Reidsville NC 27320 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Paul Matthew Smith/ORC/336-932-9347/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Paul Smith,4309 Old Liberty PI Greensboro NC 27407//336-932-9347/ No Section C Areas Evaluated During Inspection (Check only those areas evaluated) Permit E Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program N Sludge Handling Disposal Facility Site Review Laboratory Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Paul DIM eo WSRO WQ!/336-776-9691/ �.0 1 Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete Page# NPDES yr/mo/day Inspection Type 31 NCO060259 I11 12 17/07/17 7 18 1C1 Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# Permit. NCO060259 Owner - Facility Willow Oaks Inspection Date 07/17/2017 Inspection Type Compliance Evaluation Operations $ Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑ Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment. The 4th chamber in the alum feed tank was leaking on the side facing the lagoon. During a follow-up site visit on July 31 2017 the leak appeared to have been patched but there was still standing water on the -ground near the lagoon -side of the tank. Permit Yes No NA NE (If the present permit expires in 6 months or less) Has the permittee submitted a new ❑ ❑ M ❑ application? 0 ❑ ❑ ❑ Is the facility as described in the permit? M ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses M Transported CDCs M Are DIViRs complete do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? M ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? N ❑ ❑ ❑ Page# 3 permit- NCO060259 Inspection Date: 07/17/2017 Record Keeping Owner - Facility. willow Oaks Inspection Type: Compliance Evaluation Yes No NA NE Is a copy of the current NPDES permit available on site? ❑ M ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: Copy of the current permit was no- available. There was one minor mistake noted on the August. 2016 DMR. Lab report for Nitrogen - Ammonia was 3.9 mg/I - DMR reported 3.0 mg/I. Mr. Smith said that he would be more careful and double check values before submitting. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ M ❑ Is flow meter calibrated annually? ❑ ❑ M ❑ Is the flow meter operational? ❑ ❑ M ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: Bar Screens Yes No NA NE Type of bar screen # Is a re -circulation line present? ❑ 0 a.Manual ❑ Is lagoon free of excessive floating materials? 0 ❑ b Mechanical ❑ # Are baffles between ponds or effluent baffles adjustable? ❑ ❑ Are the bars adequately screening debris? 0 ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screening in compliance? M ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment- In the lower left corner of the bar screen there appeared to be one vertical bar seament missing. This appeared to lead to channeling of debris and water in the chamber immediately prior to the bar screen. According to the ORC this is necessary to prevent the bar screen from clogging and overflowing. The plant is only required to be visited once per week. Lagoons Yes No NA NE Type of lagoons? Facultative # Number of lagoons in operation at time of visit? 2 Are lagoons operated in? Series # Is a re -circulation line present? ❑ 0 ❑ ❑ Is lagoon free of excessive floating materials? 0 ❑ ❑ ❑ # Are baffles between ponds or effluent baffles adjustable? ❑ ❑ ❑ 0 Are dike slopes clear of woody vegetation? M ❑ ❑ ❑ Page# 4 Permit: NC0060259 Inspection Date- 07/17/2017 Lagoons Are weeds controlled around the edge of the lagoon? Are dikes free of seepage? Are dikes free of erosion? Are dikes free of burrowing animals? Owner - Facility willow Oaks Inspection Type Compliance Evaluation # Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations? # If excessive algae is present, has barley straw been used to help control the growth? Is the lagoon surface free of weeds? Is the lagoon free of short circuiting? Yes No NA NE ■ ❑ ❑ ❑ M ❑ ❑ ❑ N ❑ ❑ ❑ M ❑ ❑ ❑ ❑ ❑ ❑ M ❑ ❑ ■ ❑ ❑ ■ 1:111 M ❑ ❑ ❑ Comment. Duckweed growing all throughout plant Reportedly this is common during the summertime. Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Number of tubes in use? Is the level of chlorine residual acceptable? ❑ ❑ ❑ 0 Is the contact chamber free of growth, or sludge buildup? ❑ M ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ 0 Comment The 5th (last) chamber of the alum feed tank is used as a chlorine contact chamber. Chlorine tablets are fed directly into the chamber. De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de-chlonnation substance stored away from chlorine containers? M ❑ ❑ ❑ Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? M ❑ ❑ ❑ Number of tubes in use? 4 Comment. Laboratory Yes No NA NE Page# 5 Permit NCO060259 Inspection Date- 07/17/2017 Owner - Facility: willow Oaks Inspection Type Compliance Evaluation Laboratory Are field parameters performed by certified personnel or laboratory? Are all other parameters(excluding field parameters) performed by a certified lab? # Is the facility using a contract lab? # Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0 2 degrees? Incubator (BOD) set to 20 0 degrees Celsius +/- 1 0 degrees? Yes No NA NE M ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ M ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ Comment: Mr. Smith reported that temperature was recorded using an infrared thermometer. Field lab rules state that Infrared cannot be used for temperature readings reported on the DMR. Mr Smith was informed of this requirement, and said that he would obtain and use a proper thermometer. Field parameters by Smith Industries, cert. # 5169: all others by Pace Analytical in Eden cert. # 633. Effluent Sampling Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kep: at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment- Taken after dechlorination. Yes No NA NE ❑ ❑ M ❑ M ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ■ M ❑ ❑ ❑ Page# 6