HomeMy WebLinkAboutNC0065412_Compliance Evaluation Inspection_20170728I
batter es{7urces
EE lliFt NMIN7AL QUALITY
July 28, 2017
James Radford
PO Box 2533
Christiansburg, VA 24068
Subject: Compliance Evaluation Inspection Report
NPDES Permit NC0065412
Pleasant Ridge WWTP, Rockingham County
Dear Mr. Radford:
ROY COOPER
ailvEmor
MICHAEL S. REOAN
u91#0P fttiirV
JAY ZIMMERMAN
Dkertor
On July 17, 2017, Paul DiMatteo of the Division of Water Resources ("Division"), Winston-Salem Regional Office
conducted a Compliance Evaluation Inspection of the above referenced wastewater treatment system. Paul Smith,
Operator in Responsible Charge (ORC), was present for the inspection. An inspection summary follows and an inspection
report is attached for your records.
Site Review
1. Permit
The current permit became effective on July 1, 2016 and expires on April 30, 2021. A copy of the current
permit was not available for review — one should be kept for inspection. Permitted components include an
aeration basin, clarifier, and chlorine disinfection.
2. Facility Site Review
The facility was as described in the permit.
3 Operation and Maintenance
The high-water alarm in the influent tank was not operational. The facility appeared to otherwise be well
maintained. The operator or a properly designated backup visits the site as required. Visitation logs were
current and available during the inspection.
Please have the high-water alarm repaired by the next inspection.
4. Flow Measurement
Flow is measured using a V -notch weir. The weir did not appear to be obstructed.
5 Effluent/Receiving Waters
The outfall could not be accessed during the inspection. A cleared path to the outfall is not maintained.
State of North Carolina I Environmental Quality I Water Resources
ecn TV— u_- l.f.11 A.,.,.7 q, m snn W' 777n5
Documentation Review
I;
6. Records/Reports
Discharge Monitoring Reports (DMRs) and lab data are maintained according to the permit. DMRs include all
permit parameters. Copies of DMRs, operator visitation logs, lab reports and Chain -of -Custody forms were
available for review during the inspection.
7. Self -Monitoring Program
A review of DMRs from May, 2016 through May, 2017 showed the following violations, which have been
addressed in previous correspondence from this office:
PARAMETER
VIOLATION DATE
VIOLATION ACTION
Nitrogen, Total - Concentration
03/31/2017
Proceed to NOD
Phosphorus, Total (as P) - Concentration
03/31/2017
Proceed to NOD
Phosphorus, Total (as P) - Concentration
06/30/2016
Proceed to NOD
Coliform, Fecal MF, MFC Broth, 44.5 C
07/19/2016
Proceed to NOV
Solids, Total Suspended - Concentration
11/30/2016
Proceed to NOD
A comparison of submitted DMR data and field records showed no errors or concerns.
Laboratory
Field parameters are measured by the ORC under certification # 5169 (Smith Industries). All effluent samples
are taken from the aerobic digester. All other parameters are measured by Pace Analytical under
certification # 633. Chain -of -custody forms were complete and available for all parameters measured off
site. Records for parameters measured on-site were complete.
9. Sludge Handling Disposal
Sludge is removed from the plant as needed.
We appreciate your efforts in effectively operating and maintaining this treatment system. No additional
response to this report is required. If you should have any questions, please do not hesitate to contact Paul DiMatteo at
(336) 776-9691 or our office at (336) 776-9800.
Sincerely,
ft,/Sherri V. Knight, P.E., Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Enclosures — Inspection Report and Summary
CC: Paul Smith — by email 11
WQS Winston-Salem Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
Central Files
I
State of North Carolina I Environmental Quality I Water Resources
450 West Hanes Mill Road, Suite 300, Winston-Salem, NC 27105
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires B-31-98
Section A National Data System Coding (I e, PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 E 2 15 I 3 I NCO065412 111 12 17/07/17 17 18 I r• I 19 I G 20I I
21111111 111111111 11 1 11 1111 1 1 11111 1111111 11 11166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA -Reserved--
671 701 I 71 I I 72 I N I 731 I 174 75 80
LJ l_J I I 1
Section B FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09 20AM 17/07/17
16/07/01
Pleasant Ridge
Pleasant
109 Southfork Dr
Time/Date
Permit Expiration Date
Reidsville NC 27320
10 20AM 17/07/17
21/04/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
Paul Matthew Smith/ORC/336-932-9347/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Paul Smith,109 Southfork Dr Reidsville NC 27320//336-932-9347/
No
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit N Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D. Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Paul DiMatteo WSRO WQ//336-776-9691/
7/2,7)'w'7
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
C- -
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete
Page#
NPDES yr/mo/day Inspection Type (Cont.)
31 NCO065412 I11 12 17/07/17 17 18 i c I
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Site Review
1. Permit
The current permit became effective on July 1, 2016 and expires on April 30, 2021 A copy of the
current permit was not available for review — one should be kept for inspection. Permitted components
include an aeration basin, clarifier, and chlorine disinfection.
2. Facility Site Review
The facility was as described in the permit.
3. Operation and Maintenance
The high-water alarm in the influent tank was not operational. The facility appeared to otherwise be well
maintained. The operator or a properly designated backup visits the site as required. Visitation logs
were current and available during the inspection.
4. Flow Measurement
Flow is measured using a V -notch weir. The weir did not appear to be obstructed.
5. Effluent/Receiving Waters
The outfall could not be accessed during the inspection. A cleared path to the outfall is not maintained.
Documentation Review
6. Records/Reports
Discharge Monitoring Reports (DMRs) and lab data are maintained according to the permit. DMRs
include all permit parameters. Copies of DMRs, operator visitation logs, lab reports and
Chain -of -Custody forms were available for review during the inspection.
7 Self -Monitoring Program
A review of DMRs from May, 2016 through May, 2017 showed the following violations, which have been
addressed in previous correspondence from this office.
PARAMETER VIOLATION DATE VIOLATION ACTION
Nitrogen, Total - Concentration 03/31/2017 II Proceed to NOD
Phosphorus, Total (as P) - Concentration 03/31/2017 Proceed to NOD
Phosphorus, Total (as P) - Concentration 06/30/2016 Proceed to NOD
Coliform, Fecal MF, MFC Broth, 44.5 C 07/19/2016 Proceed to NOV
Solids, Total Suspended - Concentration 11/30/2016 Proceed to NOD
A comparison of submitted DMR data and field records showed no errors or concerns.
8. Laboratory
Field parameters are measured by the ORC under certification # 5169 (Smith Industries). All effluent
samples are taken from the aerobic digester. All other parameters are measured by Pace Analytical
under certification # 633. Chain -of -custody forms were complete and available for all parameters
measured off site. Records for parameters measured on-site were complete.
9. Sludge Handling Disposal
Sludge is removed from the plant as needed.
Page#
V
Permit- NCO065412 Owner - Facility Pleasant Ridge
Inspection Date: 07/17/2017 Inspection Type Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex- MLSS, MCRT, Settleable 0 ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment pH. Do, chlorine, settleable solids. Some new boards were set along the plant's walkways.
However, there are no railings on the outer perimeter of the walkways, which could present
a fall hazard.
Permit
Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted a new
❑
❑
M
❑
application?
0
❑
❑
❑
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
M
❑
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment.
Record Keepinq
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab reg required 5 years)?
M
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
❑
Is the chain -of -custody complete?
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CDCs
Are DMRs complete do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(if the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
N
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
M
❑
❑
❑
Page# 3
i
Permit: NC0065412 Owner - Facility. Pleasant Ridge
Inspection Date: 07/17/2017 Inspection Type, Compliance Evaluation
Record Keeping Yes No NA NE
Is a copy of the current NPDES permit available on site?
❑
0
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
❑
Comment: Copy of the current permit was 'not available during the inspection.
❑
Is the flow meter operational?
❑
❑
Effluent Pipe
I
Yes No NA NE
Is right of way to the outfall properly maintained? 1
❑
❑
❑
0
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
M
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
❑
0
Comment. A cleared path to the outfall is not maintained, and the wav is swampv and
overgrown.
❑
❑
❑
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
❑
❑
❑
❑
Is flow meter calibrated annually?
❑
❑
N
❑
Is the flow meter operational?
❑
❑
0
❑
I
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
N
❑
Comment: Flow is measured using a v -notch weir.
M
❑
❑
❑
Bar Screens
Yes No NA NE
Type of bar screen
❑
❑
N
❑
a.Manual
M
❑
❑
❑
b.Mechanical
❑
❑
❑
❑
Are the bars adequately screening debris?
M
❑
❑
❑
Is the screen free of excessive debris?
M
❑
❑
❑
Is disposal of screening in compliance?
M
❑
❑
❑
Is the unit in good condition?
M
❑
❑
❑
Comment:
Equalization Basins
Yes No NA NE
Is the basin aerated?
❑
❑
N
❑
Is the basin free of bypass Imes or structures to the natural environment?
❑
❑
❑
Is the basin free of excessive grease?
❑
❑
❑
Are all pumps present?N
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Page# 4
Permit. NCO065412
Owner - Facility Pleasant Ridge
Mode of operation
Ext. Air
❑
Inspection Date. 07/17/2017
Inspection Type Compliance Evaluation
Diffused
❑
Equalization Basins
Yes No NA NE
Are float controls operable?
E
❑
❑
❑
Are audible and visual alarms operable?
❑
N
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment: The alarms were not operational.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
❑
❑
Type of aeration system
Diffused
❑
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
0 ❑
❑
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
E ❑
❑
❑
Is the DO level acceptable?
❑ ❑
❑
0
Is the DO level acceptable?(1 0 to 3.0 mg/1)
❑ ❑
❑
N
Comment:
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
❑
Are weirs level?
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
E
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately 1/4 of the sidewall depth)
❑
❑
❑
E
Comment.
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? 0 ❑ ❑ ❑
Page# 5
Permit- NCO065412
Inspection Date- 07/17/2017
Disinfection -Tablet
Are the tablets the proper size and type?
Number of tubes In use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment: Tablets are added In the flume after the clarifier.
Owner - Facility. Pleasant Ridge
Inspection Type: Compliance Evaluation
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment -
Are the tablets the proper size and type?
Are tablet de-chlonnators operational?
Number of tubes in use?
Comment -
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
i
Incubator (Fecal Coliform) set to 44 5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20 0 degrees Celsius +/- 1!0 degrees?
Comment -
Yes No NA NE
M ❑ ❑ ❑
❑ ❑ ❑ M
■ ❑ ❑ ❑
❑ ❑ ❑ ■
Yes No NA NE
Tablet
❑
❑
❑
M
❑
❑
❑
❑
❑
❑
M
❑
❑
❑
■
❑
❑
❑
M
❑
❑
❑
2
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
❑ ❑ ❑ M
❑ ❑ ❑ ■
❑ ❑ ❑ ■
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Yes No NA NE
❑
❑
❑
Page# 6
1
a
permit- NCO065412 Owner - Facility Pleasant Ridge
Inspection Date 07/17/2017 Inspection Type Compliance Evaluation
Effluent Sampling
Yes No NA NE
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
❑
❑
❑
0
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
N
❑
❑
❑
representative)?
Comment Collected after dechlorination.
Page# 7