HomeMy WebLinkAboutNC0063321_Fact Shee_20170630FACT SHEET
EXPEDITED - PERMIT RENEWAL
NCO063321 — Class 2
Basic Information for Expedited Permit Renewals
1<4
Permit Writer/Date
Joe R. Corporon L.G. / NPDES / 30Jun2017
Permit Number - Class
NCO063321 — WWTP Class 2
Flow
0.200 MGD
Owner
Tuckaseigee Water and Sewer Authority ( SA)
Facility Name
Cashiers #3 WWTP
Type of Waste
100 % domestic
Basin Name/Sub-basin number
Savannah River Basin / 03-13-01
Receiving Stream
Chattooga River [segment 3]
Stream Classification in Permit
B; Trout; ORW [no changes fromprevious]
Does permit need Daily Max NH3 limits?
No need - has DM & MA [summer and winter
Does permit need TRC limits/language?
Has limit 22 g/L (revised the TRC footnote for renewal)
Does permit have WET -testing?
No [replaced w/ Ammonia limits
Does permit have Special Conditions?
Yes — collection -system additions require MOD (see A. (2).
Does permit have instream monitoring?
YES — DO, Temp, Fecal
Is the stream impaired (on 303(d) list)?
No
Any obvious compliance concerns?
No
Any permit MODS since lastpermit?
No
Requests for Renewal
Received March 16, 2017
Current expiration date
Au st 31, 2017
New expiration date
August 31, 2022
Comments received on Draft Permit?
Permit History -- Flow is 100% domestic. Permittee monitors Ammonia w/ limits (summer and winter) in lieu
of WET -testing. No changes recommended.
Staff Report — No RRO Staff Report to date Emailed draft docs to Landon Davidson (ARO) for review and
comment (03Ju12017).
Data Review /Compliance Review -- reviewed BIMS effluent data from Jan2012 through Apr2017 (see Flow
Summary) Compliance generally good; BOD5, TSS, and Ammonia (NH3 as N) show no values above permit
limits, except Region issued NOVs in February and April of 2016 for BODS and Fecal (no penalties assessed),
and again NOVs for October 2016 proceeding to CPAs for BODS and TSS; none since.
Flow Summarbby Year
Year
Average
n
Minimum
Maximum
2012
0.073
366
002
0.190
2013
0.074
365
002
0.276
2014
0.076
365
0.023
0214,
2015
0 080
364
0.018
0.242
2016
0.072
366
0.018
0200
2017
0.057
150
0.021
0125
Renewal — no changes from the previous renewal (2012) except to update text, facility description and map;
added eDMR text; revised the TRC footnote for renewal.
Receiving Stream — reminded Permittee in the cover letter of ORW Classification.