HomeMy WebLinkAboutNC0071463_Compliance Evaluation Inspection_20170525Water Resources
ENVIRONMENTAL QUALITY
May 25, 2017
Mr. Ken Fenton
Center Point Terminal Company, LLC
8235 Forsyth Blvd., Suite 400
Clayton, MO 63105
SUBJECT: Compliance Evaluation Inspection
Center Point Company - Greensboro Terminal
NPDES Permit No. NCO071463
Guilford County
Dear Mr. Fenton:
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. JAY ZIMMERMAN
Director
REGEl1(E01NCDEQ1DWR
MAY 3 1,:2017
water Q a tion
permitting
On May 24, 2017, Min Xiao of this office met with Rusty Evans and John Willard to perform a
Compliance Evaluation Inspection on the stormwater discharge from the Center Point Company
Terminal located at 6900 West Market Street in Greensboro, NC. The inspection findings are
detailed below and an inspection checklist is attached.
I. Permit
The permit became effective January 1, 2017, and will expire at midnight on August 31, 2021. A
current permit is kept on-site.
II. Self -Monitoring Program
The DMRs for Center Point were reviewed from March 2016 to February 2017. The facility was
only found to be noncompliant with the Turbidity limit in January 2017. In regards to the permit
monitoring requirements, it was noted that all sampling was performed per the frequencies
specified in the permit. Only flow is measured on-site, other parameters are tested by R & A Labs.
III. Facilih- Site Review
The Center Point Terminal stormwater management system consists of the following:
• stormwater from the truck loading -rack drain area flows to a 1,000 -gallon underground
pump tank located beside the office building. The tank has floats which automatically
controls pumping to the oil/water separator before flowing into the lower retention basin.
• diked secondary containment area for the AST's with two retention basins. The upper basin
flows by gravity via a manual valve to the lower retention basin. Accumulated stormwater
in the lower basin is pumped via a single pump through the oil/water separator located in
the maintenance building prior to being discharged. The upper basin holds 60-70% of the
stormwater of this facility.
State of North Carolina I Environmental Quality I Water Resources
450 West Hanes Mill Road, Suite 300, Winston-Salem, NC 27105
Phone: 336-776-98001 Intemet: www.nodenr.gov
IV. Flow Measurement
The permit requires episodic flow monitoring. Effluent flow from the lower retention basin is
calculated using the run time of the effluent pump. This discharge is controlled manually by
opening a valve and activating the pump. Records are kept documenting the effluent release date,
pump run time and discharge volume (12,000 GPH). The stormwater flow from the loading -rack
area has been routed to the lower retention basin after oil -water separation. This allows the loading -
rack drain stormwater flow to be recorded and sampled.
V. Records/Reports
A review of the facility files showed that all records were being maintained according to the permit.
After comparing the data of January 2017 DMR with the lab sheets from R & A Labs, the
paperwork issue noted during the inspection was the MTBE parameter should be "< 10 ug/L"
instead of "< 0.001 ug/L", and for Naphthalene, the result should be "< 0.001 mg/L". Other
parameters were transcribed correctly.
VI. Effluent/Receiving Waters
The system discharges into the storm drain that runs along West Market Street. The effluent
eventually reaches a tributary of Horsepen Creek, class "WS -III; NSW" waters of the Cape Fear
River Basin.
Should you have any questions concerning this report, please contact Min Xiao or me at (336)
776-9800.
Sincerely,
'Sherri V. Knight, PE
Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources
cc: Rusty Evans (revans@worldpointlp.com)
Central Files
NPDES Unit
WSRO
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code. NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N I 2 15 1 3 NO0071463 — 11 12 17/05/24 17 18 Li 19' G I 20 LJ
1
—1
211
1—V I I 1 1 1 1 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 1 1 1 1 1 r6
— Reserved -----
Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---Reserved —
67 70L 71 72 _ 73 L1J74 751 I I I I I I 180
67
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:10AM 17/05/24
17/01/01
Greensboro Terminal
6900 W Market St
Exit Time/Date
Permit Expiration Date
Greensboro NC 27409
11:03AM 17/05/24
21/08/31
Name(s) of Onsite Representative(s)fritles(s)/Phone and Fax Number(s)
Other Facility Data
///
John Michael Willard/ORC/336-854-8556/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Rusty Evans,6900 W Market St Greensboro NC 27409/Terminal
Manager/336-854-85561 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Records/Reports Self -Monitoring Program
Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Min Xiao WSRO WQ//336769800/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
aS/o r
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO071463 �11 12 17/05/24 17 18 ICII
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit NCO071463 Owner - Facility: Greensboro Terminal
Inspection Date: 05/24/2017 Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Yes No NA NE
❑ ❑ ■ ❑
Is access to the plant site restricted to the general public? ❑
Is the inspector granted access to all areas for inspection? ❑
Comment: The permit became effective January 1, 2017, and will expire at midnight on August 31.
2021. A current permit is kept on-site.
The Center Point Terminal stormwater management system consists of the followin
-stormwater from the truck loading -rack drain area flows to a 1,000 -gallon underground
pump tank located beside the office building. The tank has floats which automatically
controls pumping to the oiltwater separator before flowing into the lower retention basin.
-diked seconda containment area for the AST's with two retention basins. The upper basin
flows by gravity via a manual valve to the lower retention basin. Accumulated stormwater in
the lower basin is pumped via a single pump through the oil/water separator located in the
maintenance building prior to beina discharaed. The upper basin holds 60-70% of the
stormwater of this facilit
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
❑
■
❑
❑
Is flow meter calibrated annually?
❑
❑
M
❑
Is the flow meter operational?
❑
❑
■
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
M
❑
Comment: Effluent flow from the lower retention basin is calculated using the run time of the effluent
Dump. This discharge is controlled manually by opening a valve and activating
the pump. .
Records are kept documenting the effluent release date. pump run time and discharge
volume (-12000 GPH).
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
®
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
M
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The system discharges into the storm drain that runs along West Market Street. The effluent
eventually reaches a tributary of Horsepen Creek, class "WS -III: NSW" waters of the Cape
Fear River Basin.
Page# 3