FACT SHEET FOR WASTELOAD ALLOCATION
Request #
Duke Power--Belews Lake --pipe 001
NC0024406Q
Domestic - 100% ,nO"
Existing
Renewal
West Belews CreekBelews Lake
C
03-02-01
RECEIVED
t4.C. Dept of EMR,
j " t 0 6 1992
6799 Winstr, z- a1Et
OX
Regional if
Stokes Stream Characteristic:
Winston-Salem Regional Office USGS # Lake
Rosanne Barona Date:
3/9/92 Drainage Area (mi2):
B18SE Summer 7Q10 (cfs):
Winter 7Q10 (cfs):
Average Flow (cfs):
30Q2 (cfs):
IWC (%):
Wasteload Allocation Summary
(approach taken, correspondence with region, EPA, etc.)
Once through and auxiliary cooling water discharge. Chlorine not allowed (permit language).
WSRO recommends continued thermal monitoring.
"i�Z-
Recommended by: wrJ Date: �
Reviewed by p01/' r7 D
Instream Assessment: Date: a'
Regional Supervisor: Date: !a5b"1 i
Permits & Engineering: Date: 2
RETURN TO TECHNICAL SERVICES BY: J U L 5 0 1992
1 Cl
W
r � �
2
CONVENTIONAL PARAMETERS
Existing Limits:
Wasteflow (MGD): monitor
Recommended Limits:
WQ or EL
Wasteflow (MGD): monitor
Chloe ji()& vF `/Lu once ,,'-hrDLc5 A- d- Cwt / a�� Cc�l, r� r Sha/l iso
Limits Changes Due To: Parameters Affected
Change in 7Q10 data
Change in stream classification
Relocation of discharge
Change in wasteflow
Other (onsite toxicity study, interaction, etc.)
Instream data
New regulations/standards/procedures
New facility information
Parameter(s) are water quality limited. For some parameters, the available load capacity of
the immediate receiving water will be consumed. This may affect future water quality based
effluent limitations for additional dischargers within this portion of the watershed
OR
X No parameters are water quality limited, but this discharge may affect future allocations.
INSTREAM MONITORING REQUIREMENTS
Upstream Location: Southern Railway crossing of Belews Creek and East Belews Creek
Downstream Location: at Dam
Parameters: Temperature
Special instream monitoring locations or monitoring frequencies: Temperature at the Dam recorder
shall not exceed 89.6 ° F during a discharge. Daily Max. limits on temperature are 35 ° C (95 ° F).
Daily monitoring April through October, weekly monitoring November through March.
MISCELLANEOUS INFORMATION & SPECIAL CONDITIONS
Adequacy of Existing; Treatment
Has the facility demo strated the ability to meet the proposed new limits with existing treatment
facilities? Yes No
If no, which parameters cannot be met?
Would a "phasing in" of the new limits be appropriate? Yes No
If yes, please provide a schedule (and basis for that schedule) with the regional
office recommendations:
If no, why. not?
Special Instructions or Condition
Chlorination of the once through and auxiliary cooling water shall not be allowed at this facility. Should
Duke Poser wish to chlorinate its once through cooling water, a permit modification must be requested a
received prior to commencing chlorination.
Wasteload sent to EPA? (Major) (Y or N)
(If yes, then attach schematic, toxics spreadsheet, copy of model, or, if not modeled, then old
assumptions that were made, and description of how it fits into basinwide plan)
Additional Information attached? (Y or N) If yes, explain with attachments.