HomeMy WebLinkAboutNC0081256_Compliance Evaluation Inspection_20170316Water Resources
ENVIRONMENTAL QUALITY
March 16, 2017
Mr. Wendell Pickett
Water Treatment Superintendent
City of High Point
P.O. Box 230
High Point, NC 27261
SUBJECT: Compliance Evaluation Inspection
Frank L. Ward Water Filtration Plant.— City of High Point
NPDES Permit No. NCO081256
Guilford County
Dear Mr. Pickett:
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. JAY ZIMMERMAN
Director
RECEIVE®INCOEQIRR
MAR 2 8 2011
WatarQuality
Permitting Sactl®n
On March 16, 2017, Min Xiao of this office met with you and City of High Pointe staff to perform a
Compliance Evaluation Inspection on the NPDES wastewater discharge from the Ward Water Filtration
Plant (WFP). The treatment facility was found to be compliant with the NPDES permit. The inspection
findings are detailed below and an inspection checklist is attached.
I. Permit
The NPDES permit was reissued February 1, 2017, and will expire on August 31, 2021.
II. Self -Monitoring Program
The monthly discharge monitoring reports (DMR's) were reviewed for the period January 2016 through
December 2016. The facility was found to be in compliance with the NPDES effluent limits for the above.
period. In regards to the permit monitoring requirements, it was noted that all sampling was performed per
the frequencies specified in the permit.
M. Flow Measurement
The NPDES permit contains two outfalls. Outfall #002 (north lagoon) is the primary discharge point. Flow
at this outfall is measured using a Siemens ultrasonic meter for the purpose of continuous measurement.
The ultrasonic meter is calibrated semiannually, and was last calibrated on August 17, 2016 by City of High
Point staff. Outfall #001 (south lagoon) discharges if solids are being removed from the north lagoon, or if
outfall #002 couldn't be used for discharging due to accidental problems. Flow at this outfall is estimated
by measuring water height in a parshall flume. An ultrasonic meter has been scheduled to install for outfall
#001.
IV. Sludge Handling and Disposal
Solids from the settling ponds are periodically removed every three or more years 'by dewatering with
portable centrifuges. The last removal event occurred in June and July 2015. The dewatered sludge is
disposed of at the City of High Point landfill.
State of Noah Carolina I Environmental Quality I Water Resources
450 West Hanes Mill Road, Suite 300, Winston-Salem, NC 27105
Phone: 336-776-98001 Intemet: www.ncdenr.gov
Page 2
March 16, 2017
V. Operations and Maintenance
The facility was competently operated and maintained. Both of the plant and laboratory are very clean and
organized. No problems or concerns were noted.
VI. Facility Site Review
The wastewater comes from water processing and filter backwash. The wastewater treatment components
consist of the following: two 10 MG settling basins (operated in series), tablet dechlorinator unit (sodium
sulfite) and effluent flow measurement. The system discharges daily through outfall #002.
VII. Records/Reports
A review of the facility files .found the operators records to be complete and maintained according to the
permit. A comparison of the July and November 2016 DMR with the corresponding operator records and
laboratory results for Flow, TSS, NH3-N, TN, TP and Fluoride showed that all field measurements were
transcribed onto the DMR correctly.
VIII. Effluent/Receiving Waters
The system discharges into an unnamed tributary to Richland Creek, class "WS -IV *" waters in the Cape
Fear River Basin. The effluent was clear on the day of the inspection.
Our office appreciates your efforts to comply with the NPDES permit. Should you have any questions
concerning this report, please contact Min Xiao or me at (336) 776-9800.
Sincerely,
R"rkherri V. Knight, PE
Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources
cc: Wendell Pickett (Wendell.pickett@highpointnc.gov)
Central Files
NPDES Unit
WSRO
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
App rovalexpires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
17 18 I S I 191 s I 201 I
1 [� 2 15 1 3 I NCO081256 I11 12 17/03/16j Li
211 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1' 1 -1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 t66
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---Reserved--
67 70 I 71 Ll72 1 N 1 73 11 I74 75 80
LJ I—J LL_I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
11:10AM 17/03/16
17/02/01
Frank L. Ward WTP
121 N Pendleton St
Exit Time/Date
Permit Expiration Date
High Point NC 27260
12:34PM 17/03/16
21/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Robert Wendell Pickett/ORC/336-883-3410/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Melanie Bruton,5875 Riverdale Dr Jamestown NC 27282//336-883-3517/3368833624
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance E Records/Reports
Self -Monitoring Program Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Min Xiao WSRO WQ//336769800/
V1\V'V /Q -1c,17
A'�j
Signature of ManagementQ A Reviewer Agency/Office/Phone and Fax Numbers Date 017
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
31 NCO081256 I11 ,121 17/03/16 17 18 ' c
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO081256 Owner - Facility: Frank L. Ward WTP
Inspection Date: 03/16/2017 Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is accessto the plant -site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Yes No NA NE
❑ ❑ ■ ❑
M ❑ ❑ ❑
❑ ❑ M ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The Dermit was reissued February 1, 2017, and will expire on. August 31, 2021. No violations
were found for the review period January 2016 through December 2016. A review of the July
and November 2016 DMR revealed that the data were transcribed correctly from ORC's
records and lab's test results.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 0
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The plant and lab are very clean and organized.
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting? .
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
❑
M
Comment: The flow meter_ is calibrated_ semiannually. Last calibration date was August 17, 2016.
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ M ❑
Is storage appropriate for cylinders? ❑ ❑ 0 ❑
# Is de -chlorination substance stored away from'chlorine containers? ❑ ❑ 0 ❑
Comment:
Are the tablets the proper size and type? M ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 6
Page# 3
Permit: NCO081256
Inspection Date: 03/16/2017
De -chlorination
Owner - Facility: Frank L. Ward WTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: Outfall #002 has 8 dechlorination tubes in total. while 6 of them were in use. Outfall #001
has a single dechlorination tube in the manhole Oust before the outfall. The dechlorination
tubes are checked daily to ensure adequate tablets (sodium sulfite).
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ❑
Comment: The effluent was observed to be clear.
Page# 4