HomeMy WebLinkAboutNC0069841_Compliance Evaluation Inspection_20170313`J
Water Resources
Environmental Quality
March 13, 2017
Mr. Edward Goscicki, PE
Union County Department of Public Works
500 North Main Street, Suite 600
Monroe, NC 28112
SUBJECT: Compliance Evaluation Inspection
Crooked Creek WWTP
NPDES Permit NCO069841
Union County, NC
Dear Mr. Goscicki:
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. JAY ZIMMERMAN
Director
RECEiVEDINMENWR
rvli R 21 2017
yValtet Quality
Pefmi,do'igSection
On March 8, 2017, Roberto Scheller of this Office conducted a compliance inspection at the
subject facility. This inspection was conducted as a Compliance Evaluation Inspection (CEI) to
insure compliance with permit requirements and conditions. At the time of inspection facility
appeared to be well maintained and operated. We wish to thank you and the operating staff for
assistance regarding this inspection.
The enclosed report should be self-explanatory; however, should you have any questions, please
do not hesitate to contact myself or Roberto Scheller at (704) 235-2204 or
roberto.scheller@ncdenr.gov.
Sincerely,
W. Corey Basinger, Regional Supervisor
Water Quality Regional. Operations Section
Division of Water Resources, NCDEQ
Enclosed
cc: , Danny L. Smith, ORC, Crooked Creek WWTP #2, 4015 Sardis Church Road, Monroe,
NC 28110
Wastewater Branch
File
Compares'----
State
ompares- --
State of North Carolina I Environmental Quality
1611 Mail Service Center I Raleigh, North Carolina 27699-1611
919-707-9000
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO069841 I11 12 17/03/08 17 18 I S I 19 I G I 201
21111111 11111111111 111 1111 1 111111 1-111111 II I 1166
Inspection Work Days Facility Self -Monitoring Evaluation Rating 81 QA -----Reserved--
I I 72 � r, i 731 I 174 751 I I I I I I 180
671 70 71 J
LJ L-1 I I
Section B: FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
01:05PM 17/03/08
09/10/01
Crooked Creek WWTP #2
Exit Time/Date
Permit Expiration Date
4015 Sardis Church Rd
03:32PM 17/03/08
14/01/31
Monroe NC 28110
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
Danny L Smith/ORC// `
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Edward Goscicki,500 N Main St -Ste 500 Monroe NC 281124730/Public Works
No
Director/704-296-4212/7042964232
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Roberto Scheller MRO WQ//252-946-6481/
w�•-'✓_'. C` �.�' _ �i � �J cel>��
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Ie isili NL 0—Q
Page#
NPDES ' yr/mo/day Inspection Type
31 NCO069841 I11 12 17/03/08 17 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: N00069841 Owner -Facility: Crooked Creek WWrP #2
Inspection Date: 03/08/2017 Inspection Type: Compliance Evaluation
Yes No NA NE
-Kee
Are records kept and maintained as required by the permit?
M
❑
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
M
❑
❑
❑
application?
M
❑
❑
❑
Is the facility as described in the permit?
M
❑
E-10
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Facility operating under conditions of expired permit.
Record pinq
Yes No NA NE
-Kee
Are records kept and maintained as required by the permit?
M
❑
❑
❑
Is all required information readily available, complete and current?
M
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
M
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
M
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CDCs
Are DMRs complete: do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
M
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
0
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
M
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑ .
Is the backup operator certified at one grade less or greater than the facility classification?
M
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
0
❑
❑
❑
Comment: Records are orderly and well maintained.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑
Page# 3
Permit: NCO069841
Inspection Date: 03/08/2017
Owner - Facility: Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
Y
Operations & Maintenance Yes No NA NE
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: 30 Settleable Solids test was conducted MLSS settled slowly with clear supernatant.
Microscopic exam of MLSS indicates sludge in an older range.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab? -
M
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
M
❑
❑
❑
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees?
❑
❑
N
❑
Comment: Laboratory analyses are performed bV Charlotte Water's Laboratory
Services Certification
#192 Field analyses performed under field certification #5658. ETT Laboratory conducts
toxicity.
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
N
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
M
❑
❑
❑
Is the tubing clean?
N
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
M
❑
❑
❑
Celsius)?
M
❑
❑
❑
Is sampling performed according to the permit?
N
❑
❑
❑
Comment: At time of inspection influent sampler was 0 degrees Celsius.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
N
❑
❑
❑
Is the screen free of excessive debris?
M
❑
❑
❑
Is disposal of screening in compliance?
M
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Page# 4
J
Permit: NCO069841 Owner -Facility: Crooked CreekWWrP #2
Inspection Date: 03/08/2017 Inspection Type: Compliance Evaluation
Bar Screens Yes No NA NE
Comment: Facility has manual bar screen to bypass mechanical bar screen.
Oxidation Ditches
Yes No NA NE
Are the aerators operational?
M
❑
❑
❑
Are the aerators free of excessive solids build up?
M
❑
❑
❑
# Is the foam the proper color for the treatment process?
M
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
J
Is the DO level acceptable?
❑
❑
M
❑
Are settleometer results acceptable (> 30 minutes)?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
0
❑
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
❑
0
❑
❑
Comment: Facilitv is holding sludge in aeration basin due to warm winter and high sludge production
30 minute settelometer settled out to about 900ml/I.
❑
❑
❑
■
❑
Pumps -RAS -WAS
Yes No NA NE
Are pumps in place?
M
❑
❑
❑
Are pumps operational?
®
❑
❑
❑
Are there adequate spare parts and supplies on site?
❑
❑
❑
M
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
❑
■
❑
❑
■
❑
❑
❑
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
M
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Page# 5
Permit: NCO069841
Inspection Date: 03/08/2017
Owner -Facility; Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
j
r
Secondary Clarifier Yes No NA NE
Comment: Effluent from clarifiers was clear with few suspended solids. It was noted during inspection
that weirs on secondary clarifiers did not appear level and shoud be adjusted next
maintenance period.
Filtration (High Rate Tertiary)
Yes No NA NE
Type of operation:
Down flow
❑
❑
Is the filter media present?
M ❑
❑
❑
Is the filter surface free of clogging?
M ❑
❑
❑
Is the filter free of growth?
W ❑
❑
❑
Is the air scour operational?
❑
❑
❑
Is the scouring acceptable?
❑ ❑
❑
M
Is the clear well free of excessive solids and filter media?
0 ❑
❑
❑
Comment: At time of inspection filters appeared to be operating properly.
Disinfection - UV
Yes No NA NE
Are extra UV bulbs available on site?
❑
❑
❑
N
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
0
❑
❑
❑
Is transmittance at or above designed level?
❑
❑
❑
0
Is there a backup system on site?
M
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment: Effluent was clear with no visible suspended solids.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
❑
Is sample collected below all treatment units?
N
❑
❑
❑
Is proper volume collected?
M
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: At time of inspection effluent sampler was noted at 2 degrees Celsius.
Page# 6