HomeMy WebLinkAboutCompliance Eval Inspection. Ri
NC ENR
North Carolina Department of Environment and Natural Resources
Pat McCrory
Governor
January 9, 2015
Ms. Gina Danison, Environmental Manager
Raleigh-Durham Airport Authority
P.O. Box 80001
RDU Airport, NC 27623
Subject: Compliance Evaluation Inspection
NPDES Permit No. NCO084514
Raleigh-Durham International Airport (RDU)
Wake County
Dear Ms. Danison:
Donald R. van der Vaart
Secretary
RECEIVED
JAN 14 l ;i
CENTRAL FILES
DWR SECTION
On December 16, 2014, Cheng Zhang of the Raleigh Regional Office conducted a compliance
evaluation inspection of the subject facility. Your assistance was appreciated as it facilitated the
inspection process. The inspection report is attached. The following observations were made:
The Raleigh-Durham International Airport is permitted to discharge stormwater runoff, treated
wastewater from oil/water separators, and used de-icing and anti -icing fluids from various areas to
Outfalls 001, 002, 003, 004, 007, and 016. The facility discharges into unnamed tributaries to Brier
Creek (Class C -NSW), Brier Creek Reservoir (Class C -NSW), Sycamore Creek (Class B -NSW), and
Haley Creek (Class C NSW), in the Neuse River basin.
1. The facility consists two sets of treatment units (each has an aeration basin, an aerobic sludge
digester, and a clarifier) in series, which share the influent splitter box, EQ basin, chlorine
disinfection, tertiary filters, clear well and mud well.
2. Current permit expired on February 28, 2013. A renewal application was received by the
Division on August 30, 2012, which is still in review by the Division.
3. The facility has developed and implemented a Stormwater Pollution Prevention Plan (SPPP), the
plan was reviewed/updated annually. Employee training records were reviewed and found
complete. Qualitative and analytical monitoring had been conducted as required by the permit.
4. Lab results, chain -of -custody forms, and DMRs were complete and current, kept in good order
and ready for review.
5. June 2014 DMR data were compared to lab bench sheets, no transcriptional errors were noted.
None Carolina
Naturallry
North Carolina Division of Water Resources 1628 Mail Service Center Raleigh, NC 27699-1628 Phone (919) 791-4200
Internet: www.ncwaterauality.org Location: 3800 Barrett Drive Raleigh, NC 27609 Fax (919) 788-7159
An Equal Opportunity/Affirmative Action Employer— 50% Recycled/10% Post Consumer Paper
Compliance Evaluation Inspection
Raleigh-Durham International Airport (RDU)
Permit No. NCO084514
6. The facility is certified to analyze the following field parameters: pH, temperature, and DO
(Field Certification # 5353), calibration/analysis records were checked and met the Division's
requirements.
7. All six outfalls was observed during the inspection, accesses to which were well maintained.
If you have any questions regarding the attached report or any of the findings, please contact Cheng
Zhang at: (919) 791-4200 (or email: cheng.zhang2ncdenr.gov).
S'. cer ly,
Danny Smith
Water Quality Regional Supervisor
Raleigh Regional Office
Attachments
Compliance Inspection Report
Cc: Central Files w/attachment
Raleigh Regional Office w/attachment
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A National Data System Coding (I e, PCS)
Transactton Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 I�, 2 IS I 3 I N00084514 111 12 14/12/16 17 18 Lij 191 G I 201 I
Lj
21111111 IIIIIIIIIII 1111111 1111111 IIIIII�IIII �S6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67 701 I 71 I I 72 1 ti 1 731 I 174 751 III I I I 180
L_I LJ i I I
Section B FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09 30AM 14/12/16
08/07/01
RDU International Airport-WWTP
Exit Time/Date
Permit Expiration Date
1600 Terminal Blvd Termin
Raleigh NC 27623
12 30PM 14/12/16
13/02/28
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name Address of Responsible Official/Title/Phone and Fax Number
Gina Danison,PO Box 80001 Raleigh NC 276 2 3 0 0 0 1//91 9-8 4 0-7741 /91 9 84 0 0 1 7 5 Contacted
No
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance Records/Reports Self -Monitoring Program
Facility Site Review Effluent/Receiving Waters � Laboratory � Storm Water
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Cheng Zhang RRO WQ//919-791-4200/
C'Le44 � � (/ 1) /� �s—
gnatu of Manageme A Revi er Agency/Office/Phoneand Fax Numbers Date
2: Z
EPA Form 3X5-3 (Rev 9-94) Previous editions are obsolete
Page#
NPDES yr/mo/day Inspection Type
31 NC0084514 I11 12 14/12/18 17 18 U
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The facility has developed and implemented a Stormwater Pollution Prevention Plan (SPPP)
Qualitative monitoring at all Outfalls were conducted semi-annually Plan has been reviewed annually
as required Employee training records were reviewed and found complete
Page#
rJ
Permit NCO084514
Inspection Date 12/16/2014
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Owner - Facility RDU International Airport-WWTP
Inspection Type Compliance Evaluation
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable
Sohds ppH -BO-Sludge-Judge,—arld-otherthat-are-apphcable9 --
Comment
Permit
(If the present permit expires in 6 months or less) Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the Inspector granted access to all areas for inspection?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Yes No NA NE
M ❑ ❑ ❑
E ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ 1:11:1
■ ❑ ❑ ❑
Comment Permit expired on February 28, 2013, renewal application was received by the Division on
August 30, 2012
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab reg required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
❑
❑
Is the chain -of -custody complete*
3
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete do they include all permit parameters
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
M
❑
❑
❑
(if the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
M
❑
on each shift
Is the ORC visitation log available and current?
❑
❑
M
❑
Is the ORC certified at grade equal to or higher than the facility classification'?
❑
❑
0
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
0
❑
Is a copy of the current NPDES permit available on site?
M
❑
❑
❑
Page#
3
Permit NCO084514
Inspection Date 12/16/2014
Record Keeping
Facility has copy of previous year's Annual Report on file for review?
Comment
Owner -Facility ROU Intemational Airport-MT13
Inspection Type Compliance Evaluation
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment Outfalls 001, 002, 003, 004, 007, and 016 were observed during the InsDectlon
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44 5 degrees Celsius+/- 0 2 degrees?
Incubator (BOD) set to 20 0 degrees Celsius +/-1 0 degrees?
Comment Field lab certification # 5253
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment
Yes No NA NE
■ ❑ ❑ ❑
Yes No NA NE
M ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
M ❑ ❑ ❑
M ❑ ❑ ❑
■ ❑ ❑ ❑
1:11:1 ■ ❑
Yes No NA NE
❑ ❑ M ❑
Page# 4