HomeMy WebLinkAboutNC0034703_Compliance Evaluation Inspection_20160331 PAT MCCRORY
./ NIZ,
DONALD R. VAN IDR VAART.
Water Re otirces S. JAY ZIMMERMAN
GN'lIRONMLNi iL.OUAL:I v
March 31, 2016
RECEIVED/NCDE61/DWR
Mr. Eric Nianouris, Maintenance Director
Rowan-Salisbury Schools APR 0 7 1
1000 North Long Street
Salisbury, NC 28144 Water Quality
Permitting Section
Subject: Compliance Evaluation Inspection
Knollwood Elementary School WWTP
NPDES Permit No. NC0034703
Rowan County
Dear Mr. Nianouris:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on March 29, 2016 by Ori Tuvia. Timothy Pharr, Steve Germen, Dena
Myers and Jerry Rodgers cooperation during the site visit was much appreciated. Please advise
the staff involved with this NPDES Permit by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Sincerely,
_____J..
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, DEQ
Cc: NPDES Unit
Rowan County Health Department
MRO Files
Mooresville Regional Office
Location:610 East Center Ave.,Suite 301 Mooresville,NC 28115
Phone:(704)663-1699\Fax:(704)663-6040\Customer Service:1-877-623-6748
United States Environmental Protection Agency
Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 I I I 2 IS I 3 I NC0034703 111 12 I 16/03/29 117 18 ‘[...j,- 19 L!j 201 I
21111111 1 1 1 1 1 1 1 1 [ 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11111111111 r6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ---------Reserved--------
67 11.0 1 7014 J 1 71 I,. I 72 I N I 731 I 174 751 1 1 1 1 1 1 1 l80
LSection B:Facility Data I
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 09:20AM 16/03/29 14/07/01
Knollwood Elementary School
3075 Shue Rd Exit Time/Date Permit Expiration Date
10:20AM 16/03/29 19/06/30
Salisbury NC 28144
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Dena C Myers/ORC/704-872-4697/
Jerry L Rogers/ORC/704-872-4697/
Timothy D Pharr//704-639-3016/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
J.H.Bivens,515 N Clay St Salisbury NC 28144/Maintenance Director/704-639-3016/
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
A Permit II Flow Measurement II Operations&Maintenance; • Records/Reports
• Self-Monitoring Program • Sludge Handling Disposal II Facility Site Review II Effluent/Receiving Waters
U Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ori A Tuvia MRO WQ//704-663-1699/
_ ;r,..
.__.;; .3R 1 /J
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Andrew Pitner(A, O GW/1704 663-1699 Ext.21 ;G 3 .33` ( ,
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC0034703 111 121 16/03/29 117 18
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0034703 Owner-Facility: Knollwood Elementary School
Inspection Date: 03/29/2016 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ E ❑
application?
Is the facility as described in the permit? • 000
#Are there any special conditions for the permit? ❑ E ❑ ❑
Is access to the plant site restricted to the general public? • 000
Is the inspector granted access to all areas for inspection? U 000
Comment: The subiect permit expires on 6/30/2019.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? U 000
Is all required information readily available,complete and current? • 000
Are all records maintained for 3 years(lab. reg. required 5 years)? • 000
Are analytical results consistent with data reported on DMRs? II ❑ ❑ ❑
Is the chain-of-custody complete? U ❑ 0 0
Dates,times and location of sampling U
Name of individual performing the sampling
Results of analysis and calibration U
Dates of analysis
Name of person performing analyses
Transported COCs U
Are DMRs complete:do they include all permit parameters? • ❑ ❑ 0
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ I ❑
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator 00 • 0
on each shift?
Is the ORC visitation log available and current? • 000
Is the ORC certified at grade equal to or higher than the facility classification? • 000
Is the backup operator certified at one grade less or greater than the facility classification? • ❑ ❑ ❑
Is a copy of the current NPDES permit available on site? U ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? 00 • 0
Comment: The records were reviewed during the inspection were organized and well maintained.
DMR's, COC's, ORC logs and calibration logs were reviewed for the period of June 2013-
December 2015.
Laboratory Yes No NA NE
Page# 3
Permit: NC0034703 Owner-Facility: Knollwood Elementary School
Inspection Date: 03/29/2016 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • 000
Are all other parameters(excluding field parameters)performed by a certified lab? • 000
#Is the facility using a contract lab? • 000
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 000
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? 001110
Incubator(BOD)set to 20.0 degrees Celsius+/- 1.0 degrees? ❑ ❑ E ❑
Comment: Sampling is performed by Statesville Analytical (Lab Certification#440).
Equalization Basins Yes No NA NE
Is the basin aerated? • 000
Is the basin free of bypass lines or structures to the natural environment? • 0 ❑ ❑
Is the basin free of excessive grease? • ❑ ❑ 0
Are all pumps present? • 000
Are all pumps operable? • 0 ❑ ❑
Are float controls operable? ❑ ❑ ❑ U
Are audible and visual alarms operable? 000 •
#Is basin size/volume adequate? • 000
Comment: The equalization basin is equipped with influent screening system. Both pump were
operational.
Aeration Basins Yes No NA NE
Mode of operation Ext.Air
Type of aeration system Fixed
Is the basin free of dead spots? • 0 0 0
Are surface aerators and mixers operational? ❑ ❑ E ❑
Are the diffusers operational? • 000
Is the foam the proper color for the treatment process? • 000
Does the foam cover less than 25%of the basin's surface? • 000
Is the DO level acceptable? ❑ ❑ ❑ U
Is the DO level acceptable?(1.0 to 3.0 mg/I) 001110
Comment: Both blower/motor units were operational.
Secondary Clarifier Yes No NA NE
Page# 4
Permit: NC0034703 Owner-Facility: Knollwood Elementary School
Inspection Date: 03/29/2016 Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • 0 ❑ 0
Is the site free of excessive buildup of solids in center well of circular clarifier? 0 0 II 0
Are weirs level? • ❑ 0 0
Is the site free of weir blockage? • ❑ ❑ 0
Is the site free of evidence of short-circuiting? • 0 0 0
Is scum removal adequate? • ❑ 0 0
Is the site free of excessive floating sludge? • ❑ 0 0
Is the drive unit operational? 0 0 • 0
Is the return rate acceptable(low turbulence)? • 0 0 0
Is the overflow clear of excessive solids/pin floc? • ❑ ❑ 0
Is the sludge blanket level acceptable?(Approximately 1/4 of the sidewall depth) U 0 ❑ 0
Comment:
Sand Filters (Low rate) Yes No NA NE
(If pumps are used)Is an audible and visible alarm Present and operational? 00110
Is the distribution box level and watertight? U 0 ❑ 0
Is sand filter free of ponding? • ❑ ❑ 0
Is the sand filter effluent re-circulated at a valid ratio? 0 0 II ❑
#Is the sand filter surface free of algae or excessive vegetation? • 0 ❑ ❑
#Is the sand filter effluent re-circulated at a valid ratio?(Approximately 3 to 1) 0 0 • 0
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ 0
Are the tablets the proper size and type? • ❑ 0 0
Number of tubes in use? 3
Is the level of chlorine residual acceptable? • ❑ 0 0
Is the contact chamber free of growth,or sludge buildup? • ❑ 0 0
Is there chlorine residual prior to de-chlorination? • ❑ ❑ 0
Comment:
De-chlorination Yes No NA NE
Type of system? Tablet
Page# 5
Permit: NC0034703 Owner-Facility: Knollwood Elementary School
Inspection Date: 03/29/2016 Inspection Type: Compliance Evaluation
De-chlorination Yes No NA NE
Is the feed ratio proportional to chlorine amount(1 to 1)? 0 0 • 0
Is storage appropriate for cylinders? 0 U 0 0
#Is de-chlorination substance stored away from chlorine containers? • 0 0 0
Are the tablets the proper size and type? • 0 0 0
Comment: The chlorination and dechlorination containers (with secured lids)are both stored in the
same building.
Are tablet de-chlorinators operational? • 0 0 0
Number of tubes in use? 2
Comment: Proper dechlorination tablets were used.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? 0 0 IN 0
Is sample collected below all treatment units? • 0 0 0
Is proper volume collected? • 0 0 0
Is the tubing clean? 0 0 0 •
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type • 0 0 0
representative)?
Comment: The permit requires effluent grab samples.
Flow Measurement - Effluent Yes No NA NE
#Is flow meter used for reporting? 0 0 II 0
Is flow meter calibrated annually? 0 0 U ❑
Is the flow meter operational? 0 0 U ❑
(If units are separated)Does the chart recorder match the flow meter? 0 0 U 0
Comment: The flow meter on site is not working. Flow is estimated using the bucket and stopwatch
method.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • 0 0 0
Does the facility analyze process control parameters,for ex: MLSS,MCRT, Settleable • 0 0 0
Solids, pH, DO, Sludge Judge,and other that are applicable?
Comment: The facility appeared to be well maintained and adequately treating the wastewater.
Page# 6