HomeMy WebLinkAboutNC0030597_Compliance Evaluation Inspection_20160413 PAT MCCRORY
' (ic>vcmv
DONALD R. VAN DER VAART
WaterRessurces« S. JAY ZIMMERMAN
CNVIR0NMLN-f AL QUALITY
April 13, 2016 RECEIVEDUDENWR
Dr. Mary Eales, Superintendent APR 19 2016
Union County Public Schools Water Quality
201 Venus Street Permitting Section
Monroe, NC 28112
Subject: Compliance Evaluation Inspection
New Salem WWTP
NPDES Permit No. NCO030597
Union County
Dear Dr. Eales:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on April 11, 2016 by Ori Tuvia. Keith Benton cooperation during the site
visit was much appreciated. Please advise the staff involved with this NPDES Permit by
forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Sincerely,
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, DEQ
Cc: NPDES Unit
Union County Health Department
MRO Files
Mooresville Regional Office
Location:610 East Center Ave.,Suite 301 Mooresville,NC 28115
Phone:(704)663-1699\Fax:(704)663-6040\Customer Service:1-877-623-6748
United States Environmental Protechon Agency Form Approved.
EPA Washington,D.0 20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN i 2 15 1 3 I NCO030597 I11 12 16/04/11 17 18 [,j 19 I I I 201 I
211111 I I I I I III I I I I I I I I I I I I 1 l l l i i l i i l iii l l l i l f6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved------
67 10 701a 1 71 [ti1 72 1 NJ 73 1 I74 75 80
L_I Section B:Facility Data LJ L_J_J
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 09:40AM 16/04/11 14/11/01
New Salem Elementary School
Exit Time/Date Permit Expiration Date
6106 NC Hwy 205
10:30AM 16/04/11 19/01/31
Marshville NC 28103
Name(s)of Onsite Representative(s)lTitles(s)/Phone and Fax Number(s) Other Facility Data
Brandon Keith Benton//704-361-5267!
Brandon Keith Benton/ORC/704-361-5267/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Donald S Hughes,201 Venus St Monroe NC 28112//704-296-316017042963163
No
Section C Areas Evaluated During Inspection(Check only those areas evaluated)
® Permit ® Flow Measurement ® Operations&Maintenance ® Records/Reports
Self-Monitoring Program ® Sludge Handling Disposal ® Facility Site Review ® Effluent/Receiving Waters
■ Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ori A Tuvia MRO WQ//704-663-1699/
Signature of Managemen Q Reviewer Agency/Office/Phone and Fax Numbers Date
Andrew Pitner RO GW//704-663-1699 Ext.21
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NCO030597 I11 12I 16/04111 117 18 ICI
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Page# 2
y: New Salem
Permit: NC0030597 Owner-Facilit Elementary School
Inspection Date: 04/11/2016 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ® ❑
application?
Is the facility as described in the permit? M ❑ ❑ ❑
#Are there any special conditions for the permit? ❑ ® ❑ ❑
Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? ! ❑ ❑ ❑
Comment: The subject permit is effective from 10/3/14- 1/31/19:Keith Benton,the on-site
representative indicated that the facility will install a new treatment system.The new system
is in the final stages of the design stage, once the design is complete the permitee will be
looking to get a non-discharge permit.Assuming the permit will be approved the new non
discharge treatment will be installed during this coming school's summer break. Discharge
for the new system will be land applied by spray irrigation, rendering the NPDES permit
unnecessary.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? ® ❑ ❑ ❑
Is all required information readily available,complete and current? ® ❑ ❑ ❑
Are all records maintained for 3 years(lab.reg.required 5 years)? ® ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? ® ❑ ❑ ❑
Is the chain-of-custody complete? ® ❑ ❑ ❑
Dates,times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CDCs
Are MRS complete:do they include all permit parameters? ® ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ■ ❑
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator ❑ ❑ ® ❑
on each shift?
Is the ORC visitation log available and current? ® ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? M ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility classification? ■ ❑ ❑ ❑
Is a copy of the current NPDES permit available on site? ! ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ® ❑
Page# 3
Permit: NCO030597 Owner-Facility. New Salem Elementary School
Inspection Date: 04/11/2016 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: DMR's, COC and ORC visitation logs were reviewed for the months 9/2013-2/2016.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ® ❑ ❑ ❑
Are all other parameters(excluding field parameters)performed by a certified lab? ■ ❑ ❑ ❑
#Is the facility using a contract lab? ® ❑ ❑ ❑
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees ® ❑ ❑ ❑
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? ❑ ❑ ® ❑
Incubator(BOD)set to 20.0 degrees Celsius+/-1.0 degrees? ❑ ❑ ® ❑
Comment: K&W Laboratories(Certification#559) is contracted to sample and analyze samples as
required by the permit.
Septic Tank Yes No NA NE
(If pumps are used)Is an audible and visual alarm operational? ® ❑ ❑ ❑
Is septic tank pumped on a schedule? ® ❑ ❑ ❑
Are pumps or,syphons operating properly? ® ❑ ❑ ❑
Are high and low water alarms operating properly? ® ❑ ❑ ❑
Comment: The septic tank is pumped annually by L&L Environmental during the summer. The septic
tank high water alarm was examined during the inspection and was in working order.
Sand Filters (Low rate) Yes No NA NE
(If pumps are used)Is an audible and visible alarm Present and operational? ❑ ❑ ® ❑
Is the distribution box level and watertight? ® ❑ ❑ ❑
Is sand filter free of ponding? ■ ❑ ❑ ❑
Is the sand filter effluent re-circulated at a valid ratio? M ❑ ❑ ❑
#Is the sand filter surface free of algae or excessive vegetation? ® ❑ ❑ ❑
#Is the sand filter effluent re-circulated at a valid ratio?(Approximately 3 to 1) ❑ ❑ ❑ M
Comment: In previous inspections it was determined that the sprinkler heads in the filter beds need to
be lowered in order to prevent overspray.Alternatively,the facility has raised the walls
around the filter beds. It was observed that raising the walls have solved the oversprav
problem and there was no evidence of over application on the filter bed edges.
Disinfection - UV Yes No NA NE
Are extra UV bulbs available on site? ® ❑ ❑ ❑
Are UV bulbs clean? ® ❑ ❑ ❑
Page# 4
Permit- NCO030597 Owner-Facility: New Salem Elementary School
Inspection Date: 04/11/2016 Inspection Type: Compliance Evaluation
Disinfection -UV Yes No NA NE
Is UV intensity adequate? M ❑ ❑ ❑
Is transmittance at or above designed level? ® ❑ ❑ ❑
Is there a backup system on site? ® ❑ ❑ ❑
Is effluent clear and free of solids? M ❑ ❑ ❑
Comment:
Flow Measurement- Effluent Yes No NA NE
#Is flow meter used for reporting? ® ❑ ❑ ❑
Is flow meter calibrated annually? ® ❑ ❑ ❑
Is the flow meter operational? ® ❑ ❑ ❑
(If units are separated)Does the chart recorder match the flow meter? ❑ ❑ ® ❑
Comment: Flow meter is annually calibrated on March.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ ® ❑
Is sample collected below all treatment units? ® ❑ ❑ ❑
Is proper volume collected? S ❑ ❑ ❑
Is the tubing clean? ❑ ❑ ® ❑
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees ® ❑ ❑ ❑
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type ® ❑ ❑ ❑
representative)?
Comment: Grab sampling is required by the permit.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? ■ ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? M ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ M ❑
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? - 0 ❑ ❑ ❑
Does the facility analyze process control parameters,for ex:MLSS,MCRT,Settleable ® ❑ ❑ ❑
Solids, pH, DO,Sludge Judge,and other that are applicable?
Page# 5
Permit: NCO030597 Owner-Facility New Salem Elementary School
Inspection Date: 04/11/2016 Inspection Type. Compliance Evaluation
Operations & Maintenance Yes No NA NE
Comment:
Page# 6