Loading...
HomeMy WebLinkAboutNC0029602_Compliance Evaluation Inspection_20160322 PAT MCCRORY ". Governor DONALD R. VAN DER VAART Secretary Water Resources ENVIRONMENTAL QUALITY S. JAY ZIMMERMAN March 22, 2016 Director Yadkin County Board of Education Attn: Dr. Todd Martin, Superintendent RECEIVEDCDEOIDWR 121 Washington Street Yadkinville, NC 27055 MAR 2 4 2016 Water,Quatity SUBJECT: Compliance Evaluation Inspections Permitting Section Yadkin County Board of Education Wastewater Treatment Plants " Yadkin County Dear Dr. Martin: I Ron Boone of the Winston Salem Regional Office (WSRO) of the North Carolina Division of Water Resources (DWR or the Division) conducted compliance evaluation inspections at the following facilities on March 15, 2016: Facility Name NPDES Permit# u Courtney Elementary School NC0029599 - East Bend Elementary School NCO029611 Forbush Elementary School NCO029602 j! Forbush High School NCO071773 Starmount High School NCO070459 The assistance and cooperation of Mitch Long, Operator in Responsible Charge '(ORC), was greatly appreciated. Inspection reports are attached for your records and the inspection findings are summarized below. The following table shows important details about each plant: Latitude& Relceiving Stream Facility Name Plant Type Longitude Receiving Stream Classification Courtney Sand Filter 36.067886, Harmon Creek WS-IV Elementary School 80.602172 i East Bend 36.213194, Elementary School Sand Filter 80.509137 Logan Creek C Forbush Activated Sludge 36.125681, Logan Creek WS-IV Elementary School 80.498595 Forbush High Activated Sludge 36.142803, Forbush Creek WS-IV School 80.559088 Starmount High Activated Sludge 36.182031, South Deep Creek WS-III School 80.769535 State of North Carolina I Environmental Quality I Water Resources 450 West Hanes Nfill Road,Suite 300 1 Winston-Salem,North Carolina 27105 336 776 9800 - - u SITE REVIEWS Mr. Boone reviewed the plants with Mr. Long. For the most part, all plants were in good condition and well maintained.The effluents were clear and there was no foam at the discharge points.The deficiencies that Mr. Boone did note are detailed below, 1. Several alarms at the plants did not function when tested. The school board needs to test all alarms and make sure they are operational. DOCUMENTATION REVIEWS There were no problems noted with Mr. Long's documentation for all five plants. Mr. Long had all the required documentation and it meets requirements. There were no other discrepancies noted. Please keep up the good work in ensuring the plants are properly operated and maintained and meeting all the terms and conditions of the permits. Please remember that in accordance with NC General Statute 143-215.6A, violations of the permit are subject to enforcement actions not to exceed $25,000 per day, per violation. If you have any questions regarding the inspection or this letter, please do not hesitate to contact Mr. Boone or me at 336-776-9800. Thank you for your cooperation in this matter. Sincerely, Sherri V. Knight, P.E. Regional Supervisor Water Quality Regional Operations Division of Water Resources Attachments: 1. BIMS Inspection Reports (x5—one for each plant) CC: Central Files CNPDES`llnit WSRCFISNAP-Files Yadkin County Board of Education Attn: Mitchell Long, Operator in Responsible Charge 121 Washington Street Yadkinville, NC 27055 United States Environmental Protection Agency Form Approved EPA Washington,.D C 20460 OMB No.2040-0057 ' Water Compliance Inspection Report Approval expires 8-31-98 Section A National Data System Coding(i.e,PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 I 3 I N00029599 I11 12 16/03/15 17 18 L j 19 L Gj 4 201 211111 1 1 1 1 1 1 II 1 1I I I I I I I I I I I I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA -------------------Reserved------------- 67 70 71 I I 72 I N I 731 I 174 75 80 Section B Facility Data LJ I I I Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09 OOAM 16/03/15 14/01/01 Courtney Elementary School WWTP 2529 Courtney-Huntsville Exit Time/Date Permit Expiration Date Yadkinville NC 27055 10 OOAM 16/03/15 18/12/31 Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Mitchell Thomas Long/ORC/336-469-2711/ Name,Address of Responsible Official/Title/Phone and Fax Number Contacted Mark Matthews,121 Washington StY.adkinville NC 270557725//336-699-4481/ No Section C:Areas Evaluated During Inspection(Check only those areas evaluated) Permit ® Flow Measurement Operations&Maintenance ® Records/Reports Self-Monitoring,Program ■ Facility Site Review Effluent/Receiving Waters Laboratory Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Signature/(s))of Inspector(s) Agency/Office/Phone and Fax Numbers Date Ron Boone / WSRO WQ//336-776-9690/ Signature o�f Management Q A Reviewer / Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3(Rev 9-94)Previous editions are obsolete Page# 1 NPDES yr/mo/day Inspection Type 1 31 NCO029599 I11 12 16/03/15 17 18 JCJ Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) Please refer to the attached inspection summary letter. Page# 2 B Permit: NCO029599 Owner-Facility: Courtney Elementary School WVTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation F Operations& Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑ Does the facility analyze process control parameters,for ex MLSS, MCRT, Settleable ® ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: None Permit Yes No NA NE (if the present permit expires in 6 months or less) Has the permittee submitted a new ❑ ❑ ® ❑ application? Is the facility as described In the permit? ® ❑ ❑ ❑ #Are there any special conditions for the permit? ❑ ® ❑ ❑ Is access to the plant site restricted to the general public? ® ❑ ❑ ❑ Is the Inspector granted access to all areas for Inspection? ® ❑ ❑ ❑ Comment: None ' Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? i ❑ ❑ ❑ Is all required Information readily available, complete and current? ■ ❑ ❑ ❑ Are all records maintained for 3 years(lab. reg required 5 years)? ® ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ® ❑ ❑ ❑ Is the chain-of-custody complete? M ❑ ❑ ❑ Dates, times and location of sampling Name of Individual performing the sampling r Results of analysis and calibration Dates of analysis Name of person performing analyses S Transported COCs ■ Are DMRs complete:do they Include all permit parameters? M ❑ ❑ ❑ Has the facility submitted Its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ „M ❑ ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 p❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Page# 3 Permit: NC0029599 Owner-Facility: Courtney Elementary School WWTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: None Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ■ ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ® ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ M ❑ Comment: None Flow Measurement- Effluent Yes No NA NE #Is flow meter used for reporting? ■ ❑ ❑ ❑ Is flow meter calibrated annually? ❑ ❑ ❑ Is the flow meter operational? ® ❑ ❑ ❑ (If units are separated)Does the chart recorder match the flow meter? ❑ ❑ ® ❑ Comment: Facility uses water meter to measure flow. Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? ® ❑ ❑ ❑ Are UV bulbs clean? _ ■ ❑ ❑ ❑ Is UV intensity adequate? i ❑ ❑ ❑ Is transmittance at or above designed level? ® ❑ ❑ ❑ Is there a backup system on site? 0 ❑ ❑ ❑ Is effluent clear and free of solids? ❑ ❑ ❑ Comment: None Septic Tank Yes No NA NE (If pumps are used)Is an audible and visual alarm operational? ❑ 0 ❑ ❑ Is septic tank pumped on a schedule? M ❑ ❑ ❑ Are pumps or syphons operating properly? ❑ ❑ 0 ❑ Are high and low water alarms operating properly? ❑ ❑ M ❑ Comment: Tank has no alarms. Sand Filters (Low rate) Yes No NA NE Page# 4 Permit: NCO029599 Owner-Facility: Courtney Elementary School WWTP Inspection Date: 03/15/2016- Inspection Type: Compliance Evaluation Sand Filters (Low rate) Yes No rNA NE t (If pumps are used)Is an audible and visible alarm Present and operational? ® ❑k ❑ ❑ Is the distribution box level and watertight? ❑ ❑ ❑ ■ Is sand filter free of ponding? M ❑ ❑ ❑ Is the sand filter effluent re-circulated at a valid ratio? ■ ❑ ❑ ❑ #Is the sand filter surface free of algae or excessive vegetation? ■ ❑ ❑ ❑ #Is the sand filter effluent re-circulated at a valid ratio?(Approximately 3 to 1) ® ❑ ❑ ❑ Comment- None Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? ® ❑ ❑ ❑ Are all other parameters(excluding field parameters)performed by a certified lab? N ❑ ❑ ❑ #Is the facility using a contract lab? ® ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees ❑ ❑ ❑ Celsius)? Incubator(Fecal Coliform)set to 44 5 degrees Celsius+/-0.2 degrees? ❑ 0 ❑ ■ Incubator(BOD)set to 20 0 degrees Celsius+/-1 0 degrees? ❑ ❑ ❑ ■ P Comment- None Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ e Eld Is sample collected below all treatment units? i El ❑ ❑ Is proper volume collected? S ❑ ❑ ❑ Is the tubing clean? ■ ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit(frequency, sampling type ® '❑ ❑ ❑ representative)? Comment. None Page# 5 I United States Environmental Protection Agency II Form Approved EPA Washington,D C 20460 OMB No 2040"0057 Water Compliance Inspection Report Approval expires 8-31-98 i Section A•National Data System Coding(i.e.,PCS) @ Transaction Code NPDES yr/mo/day Inspection Type Inspector a Fac Type 1 2 15 I 3 I NCO029611 111 12 16/03/15 17 18 19 1 G 20 LJ 211111 1 1 1 1 1 1 II 11 I I I I I I I I I I I I I I I I I I I I I II 11 I I 1166 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA --------------Reserved------------- 671 70 IJ 71 I I 72 L N J I I 731 I 174 75III 80 Section B Facility Data L_ Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 11 15AM 16/03/15 14/01/01 East Bend Elementary School WWTP NC Hwy 67 E Exit Time/Date Permit Expiration Date 12 15P 16/03/15 18/12/31 East Bend NC 27018 Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data /// Mitchell Thomas Long/ORC/336-469-2711/ Name,Address of Responsible Official/Title/Phone and Fax Number Contacted Mark Matthews,121 Washington StYadkinville NC 270557725//336-699-4481/ No Section C Areas Evaluated During Inspection(Check only those areas evaluated) Permit ® Flow Measurement Operations&Maintenance Records/Reports Self-Monitoring Program ■ Facility Site Review Effluent/Receiving Waters Laboratory Section D-Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date Ron Boon ll WSRO WQH336-776-9690/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3(Rev 9-94)Previous editions are obsolete Page# 1 NPDES yr/mo/day Inspection Type 1 31 NCO029611 111 12 16/03/15 17 1.81 C I Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) Please refer to the attached inspection summary letter. Page# 2 Permit: NCO029611 Owner-Facility: East Bend Elementary School WVVrP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ 1 ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: None Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ #Are there any special conditions for the permit? ❑ 0 ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for Inspection? 0 ❑ ❑ ❑ Comment: None Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years(lab reg required 5 years)? ® ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain-of-custody completes 0 ❑ ❑ ❑ Dates, times and location of sampling Name of Individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are MRS complete: do they Include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility Is= or>5 MGD permitted flow)Do they operate 24/7 with a certified operator ❑ 0 ❑ ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Page# 3 Permit: NC0029611 Owner-Facility: East Bend Elementary School WVVTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ■ ❑ Comment: None Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? i ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ® ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ® ❑ Comment. None Flow Measurement- Effluent Yes No NA NE #Is flow meter used for reporting? ® ❑ ❑ ❑ Is flow meter calibrated annually? ❑ ❑ ❑ Is the flow meter operational? ® ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ ® ❑ Comment: Facility uses water meter for flow measurement. Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? ® ❑ ❑ ❑ Are UV bulbs clean? ® ❑ ❑ ❑ Is UV Intensity adequate? ■ ❑ ❑ ❑ Is transmittance at or above designed level? M ❑ ❑ ❑ Is there a backup system on site? ® ❑ ❑ ❑ Is effluent clear and free of solids? ® ❑ ❑ ❑ Comment. None Septic Tank Yes No NA NE (If pumps are used) Is an audible and visual alarm operational? ❑ ❑ M ❑ Is septic tank pumped on a schedule? 0 ❑ ❑ ❑ Are pumps or syphons operating properly? ❑ ❑ i ❑ Are high and low water alarms operating properly? ❑ ❑ 0 ❑ Comment: Tanks use dosing siphons. Sand Filters (Low rate) Yes No NA NE Page# 4 Permit: NCO029611 Owner-Facility: East Bend Elementary School WWl"P Inspection Date: 03/15/2016 Inspection.Type: Compliance Evaluation Sand Filters (Low rate) Yes No NA NE (If pumps are used) Is an audible and visible alarm Present and operatlonal'� ❑ ❑ ❑ Is the distribution box level and watertight? ❑ ❑ ❑ N Is sand filter free of ponding? i ❑ ❑ ❑ Is the sand filter effluent re-circulated at a valid ratio? 0 ❑ ❑ ❑ #Is the sand filter surface free of algae or excessive vegetations 0 ❑ ❑ ❑ #Is the sand filter effluent re-circulated at a valid ratio?(Approximately 3 to 1) ■ ❑ ❑ ❑ Comment: None Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? M ❑ ❑ ❑ Are all other parameters(excluding field parameters)performed by a certified lab? 0 ❑ ❑ ❑ #Is the facility using a contract lab? ® ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees ❑ ❑ ❑ Celsius)? Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0 2 degrees? ❑ ❑ ❑ Incubator(BOD)set to 20 0 degrees Celsius+/-1 0 degrees? ❑ ❑ ❑ Comment: None Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units M ❑ ❑ ❑ Is proper volume collected? ® ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees ❑ ❑ ❑ N Celsius)? Is the facility sampling performed as required by the permit(frequency, sampling type ❑ ❑ ❑ 0 representative)? Comment: None Page# 5 United States Environmental Protection Agency Form Approved EPA Washington,D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A:National Data System Coding(i.e.,PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 [5j 3 I NO0029602 111 12 16/03/15 17 18[, 19 G j 201 I 211111' 11111111111111111111111111111111111111 f6 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA --------------------Reserved------------ 67 70 IJ 71 L.J 72 NJ 73L � 174 75 80 Section B:Facility Data LL1J Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 12 30PM 16/03/15 14/01/01 Forbush Elementary School WWTP Exit Time/Date Permit Expiration Date 1400 Bloomtown Rd 01 30P 16/03/15 18/12/31 East Bend NC 27018 Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Mitchell Thomas Long/ORC/336-469-2711/ Name,Address of Responsible Official/Title/Phone and Fax Number Contacted Mark Matthews,121 Washington StYadkinville NC 270557725//336-699-4481/ No Section C-Areas Evaluated During Inspection(Check only those areas evaluated) Permit ® Flow Measurement ® Operations&Maintenance Records/Reports Self-Monitoring Program E Sludge Handling Disposal ® Facility Site Review ® Effluent/Receiving Waters Laboratory Section D-Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date Ron Boone WSRO WQ//336-776-9690/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3(Rev 9-94)Previous editions are obsolete Page# NPDES yr/mo/day Inspection Type 1 31 NCO029602 I11 12 16/03/15 17 18 [,,j l Section D-Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) Please refer to the attached inspection summary letter Page# 2 t Permit: NCO029602 Owner-Facility: Forbush Elementary School VW TP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Operations &Maintenance Yes No'NA NE Is the plant generally clean with acceptable housekeeping? ® ❑ ❑ ❑ Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable M ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: None Permit Yes No NA NE (If the present permit expires In 6 months or less) Has the permittee submitted a new ❑ ❑ ® ❑ application? Is the facility as described In the permit? ® ❑ ❑ ❑ #Are there any special conditions for the permit? ❑ ® ❑ ❑ Is access to the plant site restricted to the general public? e ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? M ❑ ❑ ❑ Comment: None Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ® ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years(lab. reg required 5 years)? ® ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ® ❑ ❑ ❑ Is the chain-of-custody complete? ® ❑ ❑ ❑ Dates,times and location of sampling Name of Individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete do they Include all permit parameters? ■ ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ M ❑ (If the facility Is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ■ ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? M ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ! ❑ ❑ ❑ Page# 3 Permit: NC0029602 Owner-Facility: Forbush Elementary School WVVTP Inspection Date: 0311512016 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ® ❑ Comment: None Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ® ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ® ❑ Comment None Flow Measurement- Effluent Yes No NA NE #Is flow meter used for reporting? ® ❑ ❑ ❑ Is flow meter calibrated annually? ® ❑ ❑ ❑ Is the flow meter operational? ® ❑ ❑ ❑ (If units are separated)Does the chart recorder match the flow meter? ® ❑ ❑ ❑ Comment. None Aerobic Digester Yes No NA NE Is the capacity adequate? ® ❑ ❑ ❑ Is the mixing adequate? ® ❑ ❑ ❑ Is the site free of excessive foaming in the tank? ® ❑ ❑ ❑ #Is the odor acceptable? ® ❑ ❑ ❑ #Is tankage available for properly waste sludge? ® ❑ ❑ ❑ Comment. None Bar Screens Yes No NA NE Type of bar screen a.Manual b.Mechanical ❑ Are the bars adequately screening debris? ■ ❑ ❑ ❑ Is the screen free of excessive debris? i ❑ ❑ ❑ Is disposal of screening In compliance? M ❑ ❑ ❑ Is the unit in good condition? ■ ❑ ❑ ❑ Comment: None Page# 4 Permit: NCO029602 Owner-Facility: Forbush Elementary School WWfP r Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Equalization Basins Yes No .`NA NE Is the basin aerated? 0 ❑ ❑ ❑ Is the basin free of bypass lines or structures to the natural environment? E ❑ ❑ ❑ Is the basin free of excessive grease? N ❑ ❑ ❑ Are all pumps present? E ❑ ❑ ❑ Are all pumps operable? ■ ❑ ❑ ❑ Are float controls operable? ® ❑ ❑ ❑ Are audible and visual alarms operable? S ❑ ❑ ❑ #Is basin size/volume adequate? N ❑ ❑ ❑ Comment. None Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? ® ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ ® ❑ Are weirs level? ® ❑ ❑ ❑ Is the site free of weir blockage? ® ❑ ❑ ❑ Is the site free of evidence of short-circuiting? ® ❑ ❑ ❑ Is scum removal adequate? ■ ❑ ❑ ❑ Is the site free of excessive floating sludge? ■ ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ ® ❑ Is the return rate acceptable(low turbulence)? ® ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? ® ❑ ❑ ❑ Is the sludge blanket level acceptable?(Approximately'/.of the sldewall depth) ❑ ❑ ❑ ■ Comment: None Aeration Basins Yes No NA NE Mode of operation Ext Air Type of aeration system Diffused Is the basin free of dead spots? e ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ N ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? i ❑ ❑ ❑ Does the foam cover less than 25%of the basin's surface? ■ ❑ ❑ ❑ Is the DO level acceptable? ■ ❑ ❑ ❑ Page# 5 Permit: NCO029602 Owner-Facility: Forbush Elementary School WWTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Aeration Basins Yes No NA NE Is the DO level acceptable?(1.0 to 3 0 mg/1) 0 ❑ ❑ ❑ Comment: None Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? 0 ❑ ❑ ❑ Are UV bulbs clean? 0 ❑ ❑ ❑ Is UV intensity adequate? 0 ❑ ❑ ❑ Is transmittance at or above designed level? 0 ❑ ❑ ❑ Is there a backup system on site? 0 ❑ ❑ ❑ Is effluent clear and free of solids? 0 ❑ ❑ ❑ Comment- None Pumps-RAS-WAS Yes No NA NE Are pumps in place? 0 ❑ ❑ ❑ Are pumps operational? 0 ❑ ❑ ❑ Are there adequate spare parts and supplies on site? 0 ❑ ❑ ❑ Comment: None Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters)performed by a certified lab? 0 ❑ ❑ ❑ #Is the facility using a contract lab? 0 ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees ❑ ❑ ❑ 0 Celsius)? Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? ❑ ❑ ❑ 0 Incubator(BOD)set to 20 0 degrees Celsius+/-1.0 degrees? ❑ ❑ ❑ 0 Comment: None Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ Page# 6 Permit: NCO029602 Owner-Facility: Forbush Elementary School WWTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Effluent Sampling Yes No NA NE #Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees ❑ ❑ ❑ ■ Celsius)? Is the facility sampling performed as required by the permit(frequency, sampling type ® ❑ ❑ ❑ representative)? Comment. None Page# 7 United States Environmental Protection Agency Form Approved EPA - .-- Washington,D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 4 Section A National Data System Coding(i.e.,PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN12 15 I 3 I NC0071773 I11 12 16/03/15 17 18 19 Li 201 I 211 1- 1 1 1 1 1 1 1 1 11 1 1 1 1 1 1 1 1 I I I I I I I I I I I I I I I I I I I I tLf6 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ------------------Reserved------------ 67 70 I I 71 I I 72 ,, ] 731 I 174 75 80 LJ Section B. Facility Data LJ I I I Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also Include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 01 45PM 16/03/15 14/02/01 Forbush High School WWTP Exit Time/Date permit Expiration Date 1525 Fallon Rd 02'45PM 16/03/15 18/12/31 , East Bend NC 27018 Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Mitchell Thomas Long/ORC/336-469-2711/ Name,Address of Responsible Official/Title/Phone and Fax Number Contacted Mark Matthews,121 Washington St Yadkinville NC 270557725//336-699-4481/ No Section C:Areas Evaluated During Inspection(Check only those areas evaluated) Permit 0 Flow Measurement - ® Operations&Maintenance ® Records/Reports Self-Monitoring Program i Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D-Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date Ron Boone 1! WSRO WQH336-776-9690/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3(Rev 9-94)Previous editions are obsolete Page# NPDES yr/mo/day Inspection Type 1 31 NP0071773 I11 12 16/03/15 17 18 Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) Please refer to the attached inspection summary letter 0 Page# 2 Permit: NCO071773 Owner-Facility: Forbush High School VW TP Inspection Date: 03/15/2016 - Inspection Type: Compliance Evaluation a R a Operations& Maintenance Yes No 'NA NE e Is the plant generally clean with acceptable housekeeping? ❑` ❑ ❑ Does the facility analyze process control parameters, for ex- MLSS, MCRT, Settleable 0 ❑' ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: None Permit Yes No NA NE (If the present permit expires in 6 months or less) Has the permittee submitted anew ❑ ❑ 0 ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ #Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: None Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years(lab reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain-of-custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling 0 Name of individual performing the sampling 0 Results of analysis and calibration 0 Dates of analysis 0 Name of person performing analyses 0 Transported COCs 0 Are DMRs complete do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ 0 ❑ ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Page# 3 Permit: NC0071773 Owner-Facility: Forbush High School WNIrP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ® ❑ Comment: None Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ® ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: None Flow Measurement- Effluent Yes No NA NE #Is flow meter used for reporting? ® ❑ ❑ ❑ Is flow meter calibrated annually? ® ❑ ❑ ❑ Is the flow meter operational? ® ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ® ❑ ❑ ❑ Comment. None. Aerobic Digester Yes No NA NE Is the capacity adequate? ® ❑ ❑ ❑ Is the mixing adequate? ® ❑ ❑ ❑ Is the site free of excessive foaming In the tank? ® ❑ ❑ ❑ #Is the odor acceptable? ® ❑ ❑ ❑ #Is tankage available for properly waste sludge? ® ❑ ❑ ❑ Comment: None Bar Screens Yes No NA NE Type of bar screen a Manual b Mechanical ❑ Are the bars adequately screening debris? ® ❑ ❑ ❑ Is the screen free of excessive debris? N ❑ ❑ ❑ Is disposal of screening In compliance? 0 ❑ ❑ ❑ Is the unit in good condition? N ❑ ❑ ❑ Comment: None Page# 4 Permit: NC0071773 Owner-Facility. Forbush High School WNNTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation It V Equalization Basins Yes No iNA NE Is the basin aerated? ® 01 ❑ ❑ Is the basin free of bypass lines or structures to the natural environment? ■ ❑ ❑ ❑ Is the basin free of excessive grease? N ❑ ❑ ❑ Are all pumps present? i ❑ ❑ ❑ Are all pumps operable? ® ❑ ❑ ❑ Are float controls operable? ■ ❑ ❑ ❑ Are audible and visual alarms operable? E ❑ ❑ ❑ #Is basin size/volume adequate? ® ❑ ❑ ❑ Comment: None Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? ® ❑ ❑ ❑ Is the site free of excessive buildup of solids In center well of circular clarifier? ❑ ❑ ® ❑ Are weirs level? ® ❑ ❑ ❑ Is the site free of weir blockage? ® ❑ ❑ ❑ Is the site free of evidence of short-circuiting? A ❑ ❑ ❑ Is scum removal adequate? N ❑ ❑ ❑ Is the site free of excessive floating sludge? ® ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ E ❑ Is the return rate acceptable(low turbulence)? ® ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? ® ❑ ❑ ❑ Is the sludge blanket level acceptable?(Approximately'/.of the sldewall depth) ❑ ❑ ❑ i Comment None Aeration Basins Yes No NA NE Mode of operation Ext.Air Type of aeration system Diffused Is the basin free of dead spots? E ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ ■ ❑ Are the diffusers operational? ! ❑ ❑ ❑ Is the foam the proper color for the treatment process? E ,❑ ❑ ❑ Does the foam cover less than 25%of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? E ❑ ❑ ❑ Page# 5 Permit: NCO071773 Owner-Facility: Forbush High School WVVTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Aeration Basins Yes No NA NE Is the DO level acceptable?(1 0 to 3 0 mg/1) ® ❑ ❑ ❑ Comment: None Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? M ❑ ❑ ❑ Are UV bulbs clean? ® ❑ ❑ ❑ Is UV Intensity adequate? ® ❑ ❑ ❑ Is transmittance at or above designed level? i ❑ ❑ ❑ Is there a backup system on site? M ❑ ❑ ❑ Is effluent clear and free of solids? ® ❑ ❑ ❑ Comment- None Pumps-RASMAS Yes No NA NE Are pumps in place? ® ❑ ❑ ❑ Are pumps operational? M ❑ ❑ ❑ Are there adequate spare parts and supplies on site? ® ❑ ❑ ❑ Comment: None Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? ■ ❑ ❑ ❑ Are all other parameters(excluding field parameters)performed by a Certified lab? ❑ ❑ ❑ #Is the facility using a contract lab? ® ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees ❑ ❑ ❑ Celsius)? Incubator(Fecal Coliform)set to 44 5 degrees Celsius+/-0 2 degrees? ❑ ❑ ❑ Incubator(BOD)set to 20.0 degrees Celsius+/-1.0 degrees? ❑ ❑ ❑ M Comment: None Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? ■ ❑ ❑ ❑ Is the tubing clean? ❑ ❑ e ❑ Page# 6 Permit: NCO071773 Owner-Facility: Forbush High School WWTP Inspection Date: 03/15/2016 Inspection-Type: Compliance Evaluation Effluent Sampling Yes No NA NE #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees ❑ ❑ ❑ ■ Celsius)? Is the facility sampling performed as required by the permit(frequency,sampling type ® ❑ ❑ ❑ representative)? Comment: None r Page# 7 United States Environmental Protection Agency Form Approved EPA Washington,D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires8-31-98 Section A National Data System Coding(i e.,PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 , 1 2 IS I 3 I NC0070459 I11 12 16/03n5 17 18 LC j 19 ICI 201 I 211111 1 1 1 1 1 1 II 1 LI I I I I I I I I I I I I I I I I I I I I II I I I I I J6 Inspection Work Days Facility Self-Monitonng Evaluation Rating B1 QA ---------------Reserved-------------- 671 70 I I 71 L] 72 ti 73�74 75 80 LJ LJ Section 6-Facility Data Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 03 OOPM 16/03/15 14/01/01 Starmount High School WWTP Exit Time/Date Permit Expiration Date 2516 Longtown Rd 04.00PM 16/03/15 18(12131 Boonville NC 27011 Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Mitchell Thomas Long/ORC/336-469-2711/ Name,Address of Responsible Official/Title/Phone and Fax Number Contacted Mark Matthews,121 Washington St Yadkinville NC 270557725//336-699-4481/ No Section C-Areas Evaluated During Inspection(Check only those areas evaluated) ® Permit ® Flow Measurement Operations&Maintenance ® Records/Reports Self-Monitoring Program ® Sludge Handling Disposal ® Facility Site Review ■ Effluent/Receiving Waters Laboratory Section D.Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date Ron Boone WSRO WQ//336-776-9690/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3(Rev 9-94)Previous editions are obsolete Page# 1 NPDES yr/mo/day Inspection Type 1 31 NCO070459 I11 12 16/03/15 17 18 ICI Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) Please refer to the attached inspection summary letter. Page# 2 ' 1 i Permit: NCO070459 Owner-Facility: Starmount High School WWTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Operations$ Maintenance Yes No INA NE i Is the plant generally clean with acceptable housekeeping? 0 ❑,' ❑ ❑ Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable 0 El El 1:1Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: None Permit Yes No NA NE (If the present permit expires In 6 months or less) Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? ❑ ❑ ❑ ❑ #Are there any special conditions for the permit? ❑ ® ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ 0 Comment: None Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ® ❑ ❑ ❑ Is all required information readily available, complete and current? 0 0 ❑ ❑ Are all records maintained for 3 years(lab reg required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ Is the chain-of-custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete:do they Include all permit parameters? 0, ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑'I ❑ 0 ❑ (If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ 0 ❑ ❑ on each shift? r Is the ORC visitation log available and current? 0"r ❑ ❑ El Is the ORC certified at grade equal to or higher than the facility classification? 06 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Page# 3 Permit: NC0070459 Owner-Facility: Starmount High School WVVrP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ E ❑ Comment: None Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ® ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ® ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ® ❑ Comment: None Flow Measurement- Effluent Yes No NA NE #Is flow meter used for reporting? ® '❑ ❑ ❑ Is flow meter calibrated annually? ® ❑ ❑ ❑ Is the flow meter operational? ® ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ® ❑ ,❑ ❑ Comment: None Aerobic Digester Yes No NA NE Is the capacity adequate? ® ❑ ❑ ❑ Is the mixing adequate? i ❑ ❑ ❑ Is the site free of excessive foaming In the tank? ® ❑ ❑ ❑ #Is the odor acceptable? ® ❑ ❑ ❑ #Is tankage available for properly waste sludge? ® ❑ ❑ ❑ Comment. None Bar Screens Yes No NA NE Type of bar screen a Manual b.Mechanical ❑ Are the bars adequately screening debris? ® ❑ ❑ ❑ Is the screen free of excessive debris? ■ ❑ ❑ ❑ Is disposal of screening in compliance? N ❑ ❑ ❑ Is the unit in good condition? N ❑ ❑ ❑ Comment: None. Page# 4 h Permit: NCO070459 Owner-Facility: Starmount High School WMlrP Inspection Date: 03/15/2016 - Inspection Type: Compliance.Evaluation Equalization Basins Yes No NA NE Is the basin aerated? ❑ Is the basin free of bypass lines or structures to the natural environment? M ❑ ❑ ❑ Is the basin free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? ® ❑ ❑ ❑ Are all pumps operable? ■ ❑ ❑ ❑ Are float controls operable? E ❑ ❑ ❑ Are audible and visual alarms operable? .■ ❑ ❑ ❑ #Is basin size/volume adequate? ® ❑ ❑ ❑ Comment: None Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? E ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ ® ❑ Are weirs level? ® ❑ ❑ ❑ Is the site free of weir blockage? ❑ ❑ ❑ ❑ Is the site free of evidence of short-circuiting? -® ❑ ❑ ❑ Is scum removal adequate? ® •❑ ❑ ❑ Is the site free of excessive floating sludge? ! ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ ® ❑ Is the return rate acceptable(low turbulence)? N ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? N ❑ ❑ ❑ Is the sludge blanket level acceptable?(Approximately''/4 of the sidewall depth) ❑ ❑ ❑ 0 Comment: None - Aeration Basins Yes No NA NE Mode of operation Ext Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Are the diffusers operational? N ❑ ❑ ❑ Is the foam the proper color for the treatment process? N ❑ ❑ ❑ Does the foam cover less than 25%of the basin's surface? ■ ❑ ❑ ❑ Is the DO level acceptable? 0 ❑ ❑ ❑ Page# 5 Permit: NCO070459 Owner-Facility: Starmount High School VVWTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Aeration Basins Yes No NA NE Is the DO level acceptable?(1 0 to 3.0 mg/1) M ❑ ❑ ❑ Comment: None Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? M ❑ ❑ ❑ Are UV bulbs clean? ® ❑ ❑ ❑ Is UV intensity adequate? ® ❑ ❑ ❑ Is transmittance at or above designed level? ® ❑ ❑ ❑ Is there a backup system on site? ® ❑ ❑ ❑ Is effluent clear and free of solids? ® ❑ ❑ ❑ Comment: None Pumps-RAS-WAS Yes No NA NE Are pumps in place? ® ❑ ❑ ❑ Are pumps operational? ■ ❑ ❑ ❑ Are there adequate spare parts and supplies on site? ® ❑ ❑ ❑ Comment: None Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? ® ❑ ❑ ❑ Are all other parameters(excluding field parameters)performed by a certified lab? 0 ❑ ❑ ❑ #Is the facility using a contract lab? 0 ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees ❑ ❑ ❑ ■ Celsius)? - Incubator(Fecal Coliform)set to 44 5 degrees Celsius+/-0 2 degrees? ❑ ❑ ❑ M Incubator(BOD)set to 20 0 degrees Celsius+/-1.0 degrees? ❑ ❑ ❑ 0 Comment: None Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? M ❑ ❑ ❑ Is proper volume collected? M ❑ ❑ ❑ Is the tubing clean? ❑ ❑ N ❑ Page# 6 Permit: NCO070459 Owner-Facility: Starmount High School WWTP Inspection Date: 03/15/2016 Inspection Type: Compliance Evaluation Effluent Sampling Yes No NA NE !' #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees ❑ 0 ❑ 0 Celsius)? Is the facility sampling performed as required by the permit(frequency, sampling type ® ❑ ❑ ❑ representative)? Comment: None Page# 7