HomeMy WebLinkAboutNC0020338_Compliance Evaluation Inspection_20160316 •
PAT MCCRORY
DONALD R. VAN DER VAART
=:2 R?sources
..t ';RONMaNTAL QUALITY S. JAY ZIMMERMAN
March 16, 2016
Town of Yadkinville
Attn: Perry Lee Williams, Town Manager
213 Van Buren Street ZECEIVEDINCDEQIDWP
Yadkinville, NC 27055-0816
21
Subject: Compliance Evaluation Inspection
NC0020338, Yadkinville Wastewater Treatment Plant Permitting Water g:SecPermittingSectio,,
Town of Yadkinville
Yadkin County
Dear Mr. Williams: •
1. Ron Boone of the Winston-Salem Regional Office of the NC Division of Water Resources (DWR or the
Division) conducted a compliance evaluation inspection (CEI) at the subject facility on March 3, 2016.
The assistance and cooperation of Grant Trivette, ORC, was greatly appreciated. An inspection report
is attached for your records and the inspection findings are summarized below.
General
2. The facility is located at 1620 Fred Hinshaw Road, in Yadkinville, Yadkin County, North Carolina. The
facility is authorized to discharge treated wastewater from the treatment works through outfall 001 to
North Deep Creek, which is currently classified as Class WS-IV waters and is located in the Yadkin Pee-
Dee River basin. The wastewater treatment system consists of a mechanical bar screen, dual grit
removal facilities, an influent pump station, an equalization basin, a flow splitter box, aeration basins, an
oxidation ditch, secondary clarification, chlorine contact chamber utilizing gas chlorination, gas
dechlorination, aerobic sludge digestion, sludge drying beds, and standby power.
Documentation & Monitoring Review
3. All required records were readily available, complete, and current. DMRs for 2014 and 2015 were
reviewed and no discrepancies were noted. Lab results, chains of custody, plant operation and
maintenance logs, and operator visitation logs, were also reviewed and no problems were noted.
Site Review
4. The plant was very clean and well maintained. Mr Trivette and his operations staff appear to be doing an
outstanding job of operating and maintaining the facility.
State of North Carolina Environmental Quality Water Resources
450 West Hanes Mill Road.Suite 300 I Winston-Salem,North Carolina 27105
336'76 9800
. -
I
5. Please encourage your operators to continue their efforts in complying with all permit conditions. Should
you have any questions, please feel free to contact Mr. Boone or me at(336) 776-9800.
Sincerely,
Sherri V. Knight, P.E.
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments:
1. BIMS Inspection Report
CC: SWP—WSRO
Central Files
NPDES Unit
Town of Yadkinville
Attn: Grant Trivette, Operator in Responsible Charge
1620 Fred Hinshaw Road
Yadkinville, NC 27055
United States Environmental Protection Agency Form Approved.
EPA Washington,D C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1E 2 I5 I 3 I NC0020338 111 12 I 16/03/03 117 18 19 G 201 I
211111 11 ) 11 111 1 [ I I l I I I I I I I I I 1 I 1 I 1 1 I I I II 1 1 [ 1 1 166
Inspection Work Days Facility Self-Monitoring Evaluation Rating 01 GA Reserved------------
671 1 701 I 71 72 U 731 1 174 751 I I 1 1 L 1 180
Section B:Facility Data LJ 1 l
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 10:00AM 16/03/03 14/08/01
Yadkinville WWTP
Exit Time/Date Permit Expiration Date
1620 Fred Hinshaw Rd
11:00AM 16/03/03 18/11/30
Yadkinville NC 27055
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Grant Franklin Trivette/ORC/336-679-2184/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Grant F Trivette:1620 Fred Hinshaw Rd Yadkinville NC 27055/ORC/336-679-2184/
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
• Permit • Flow Measurement • Operations&Maintenance • Records/Reports
• Self-Monitoring Program II Sludge Handling Disposal • Facility Site Review • Effluent/Receiving Waters
II Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
•
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone t WSRO WQ//336-776-9690/
e.• //
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
ut` ,r f
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC0020338 I11 121 16/03/03 117 18
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
•
Page# 2
V
Permit: NC0020338 Owner-Facility: Yadkinville VNMT
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Operations&Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • 0 0 0
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • 0 0 0
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ 0 U 0
application?
Is the facility as described in the permit? • 0 0 0
#Are there any special conditions for the permit? 0 • 0 0
Is access to the plant site restricted to the general public'? • 0 0 0
Is the inspector granted access to all areas for inspection? U 0 0 0
Comment: None
Record Keeping Yes_No NA NE
Are records kept and maintained as required by the permit? • 0 0 0
Is all required information readily available, complete and current? • 0 0 0
Are all records maintained for 3 years(lab. reg. required 5 years)? • 0 0 0
Are analytical results consistent with data reported on DMRs? U 0 0 0
Is the chain-of-custody complete? • 0 0 0
Dates,times and location of sampling
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs •
Are DMRs complete:do they include all permit parameters? • 0 0 0
Has the facility submitted its annual compliance report to users and DWQ? • 0 0 0
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator 0 I 0 0
on each shift?
Is the ORC visitation log available and current? • 0 0 0
Is the ORC certified at grade equal to or higher than the facility classification'? • 0 0 0
Is the backup operator certified at one grade less or greater than the facility classification'? • 0 0 0
Is a copy of the current NPDES permit available on site? • 0 0 0
Page# 3
I
Permit: NC0020338 Owner-Facility: Yadkinville WWTP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? • 000
Comment: None
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? • 000
Are the receiving water free of foam other than trace amounts and other debris? • 000
If effluent (diffuser pipes are required) are they operating properly? 00110
Comment: None
Flow Measurement-Effluent Yes No NA NE
#Is flow meter used for reporting? I ❑ ❑ ❑
Is flow meter calibrated annually? • •❑ ❑ ❑
Is the flow meter operational? • ❑ ❑ ❑
(If units are separated) Does the chart recorder match the flow meter? • ❑ ❑ ❑
Comment: None
Aerobic Digester Yes No NA NE
Is the capacity adequate? • ❑ ❑ ❑
Is the mixing adequate? • ❑ ❑ ❑
Is the site free of excessive foaming in the tank? • ❑ ❑ ❑
#Is the odor acceptable? • 000
#Is tankage available for properly waste sludge? • ❑ ❑ ❑
Comment: None
Pump Station - Effluent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Are all pumps present? I EDO
Are all pumps operable? • 000
Are float controls operable? U ❑ ❑ ❑
Is SCADA telemetry available and operational? • 000
Is audible and visual alarm available and operational? 111000
Comment: None
Page# 4
i T
Permit: NC0020338 Owner-Facility: Yadkinville VWVf P
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Pump Station -Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures'? • ❑ 0 0
Is the wet well free of excessive grease? • 0 0 0
Are all pumps present? U 0 0 0
Are all pumps operable? • 0 0 0
Are float controls operable? • 0 0 0
Is SCADA telemetry available and operational? • 0 0 0
Is audible and visual alarm available and operational'? • 0 0 0
Comment: None
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical ❑
Are the bars adequately screening debris? • 0 0 0
Is the screen free of excessive debris? • 0 0 0
Is disposal of screening in compliance? • 0 0 0
Is the unit in good condition? • 0 0 0
Comment: None
Grit Removal Yes No NA NE
Type of grit removal
a.Manual •
b.Mechanical ❑
Is the grit free of excessive organic matter'? • 0 0 0
Is the grit free of excessive odor? • 0 0 0
#Is disposal of grit in compliance'? • 0 0 0
Comment: None
Equalization Basins Yes No NA NE
Is the basin aerated? • 0 0 0
Is the basin free of bypass lines or structures to the natural environment? U 0 0 0
Is the basin free of excessive grease? • 0 0 0
Are all pumps present? • 0 0 0
Page# 5
Permit: NC0020338 Owner-Facility: Yadkinville WWTP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Equalization Basins Yes No NA NE
Are all pumps operable? I ❑ 00
Are float controls operable? I ❑ ❑ ❑
Are audible and visual alarms operable'? • ❑ ❑ 0
#Is basin size/volume adequate? • 000
Comment: None
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • 000
Is the site free of excessive buildup of solids in center well of circular clarifier? U ❑ ❑ ❑
Are weirs level? U 000
Is the site free of weir blockage? • ❑ ❑ p
Is the site free of evidence of short-circuiting? • 000
Is scum removal adequate? • ODD
Is the site free of excessive floating sludge? • ❑ ❑ ❑
Is the drive unit operational? U ❑ ❑ ❑
Is the return rate acceptable(low turbulence)? • 000
Is the overflow clear of excessive solids/pin floc? • ❑ ❑ ❑
Is the sludge blanket level acceptable?(Approximately Y4 of the sidewall depth) ❑ ❑ ❑ U
Comment: None
Aeration Basins Yes No NA NE
Mode of operation Ext.Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ 0
Are surface aerators and mixers operational? • 0 0 0
Are the diffusers operational? • 000
Is the foam the proper color for the treatment process? U ❑ ❑ p
Does the foam cover less than 25%of the basin's surface? MOOD
Is the DO level acceptable? • 000
Is the DO level acceptable?(1.0 to 3.0 mg/I) U ❑ ❑ ❑
Comment: None
Disinfection-Gas Yes No NA NE
Page# 6
f
Permit: NC0020338 Owner-Facility: Yadkinville\MNTP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Disinfection-Gas Yes No NA NE
Are cylinders secured adequately? • 0 El 0
Are cylinders protected from direct sunlight? U ❑ 0 0
Is there adequate reserve supply of disinfectant? • 0 0 0
Is the level of chlorine residual acceptable? • ❑ ❑ ❑
Is the contact chamber free of growth, or sludge buildup? • ❑ El ❑
Is there chlorine residual prior to de-chlorination? • ❑ ❑ ❑
Does the Stationary Source have more than 2500 lbs of Chlorine(CAS No. 7782-50-5)? • 0 ❑ 0
If yes,then is there a Risk Management Plan on site? • ❑ ❑ 0
If yes,then what is the EPA twelve digit ID Number?(1000-= )
If yes,then when was the RMP last updated?
Comment: None
De-chlorination Yes No NA NE
Type of system ? Gas
Is the feed ratio proportional to chlorine amount(1 to 1)? • El ❑ ❑
Is storage appropriate for cylinders? • ❑ ❑ ❑
#Is de-chlorination substance stored away from chlorine containers? • ❑ ❑ 0
Are the tablets the proper size and type? ❑ ❑ • ❑
Comment: None
Are tablet de-chlorinators operational? 0 ❑ • 0
Number of tubes in use?
Comment: None
Standby Power Yes No NA NE
Is automatically activated standby power available? • ❑ ❑ ❑
Is the generator tested by interrupting primary power source? • ❑ ❑ El
Is the generator tested under load? • ❑ ❑ 0
Was generator tested&operational during the inspection? 0 ❑ ❑ MI
Do the generator(s) have adequate capacity to operate the entire wastewater site? • ❑ 0 0
Is there an emergency agreement with a fuel vendor for extended run on back-up power'? • 0 ❑ ❑
Is the generator fuel level monitored? U ❑ ❑ 0
Comment: None
Page# 7
Permit: NC0020338 Owner-Facility: Yadkinville VWVfP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Pumps-RAS-WAS Yes No NA NE
Are pumps in place? • ❑ 0 0
Are pumps operational? • ❑ 0 0
Are there adequate spare parts and supplies on site? • ❑ ❑ ❑
Comment: None
Laboratory •
Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • 0 0 0
Are all other parameters(excluding field parameters)performed by a certified lab? • ❑ ❑ ❑
#Is the facility using a contract lab? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 ❑
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? • 0 0 0
Incubator(BOD)set to 20.0 degrees Celsius+/- 1.0 degrees? • 0 0 0
Comment: None
Influent Sampling Yes No NA NE
#Is composite sampling flow proportional? • 0 0 ❑
Is sample collected above side streams? • ❑ 0 ❑
Is proper volume collected? II ❑ ❑ ❑
Is the tubing clean? • 0 ❑ ❑
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • ❑ 0 0
Celsius)?
Is sampling performed according to the permit? • 0 ❑ ❑
Comment: None
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ 0 ❑
Is sample collected below all treatment units? • ❑ ❑ p
Is proper volume collected? • ❑ ❑ ❑
Is the tubing clean? • 0 ❑ ❑
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • ❑ 0 ❑
Celsius)?
Is the facility sampling performed as required by the permit(frequency, sampling type II ❑ ❑ ❑
representative)?
Page# 8
4
Permit: NC0020338 Owner-Facility: Yadkinville WWTP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Comment: None
Page# 9