HomeMy WebLinkAboutNC0005177_Compliance Evaluation Inspection_20170120Environmental
Quality
January 20; 2017
Mr. Rodney Willis, Environmental Engineer
FMC Corporation/Lithium Division
P.O Box 795
Bessemer, NC 28016
Dear Mr. Willis:
ROY COOPER
Governor
MICHAEL. S. RRGAN
Secretary
S. JAY ZIIV MERMAN
Director
JAN 3 12017
Water Quality,
Permitting Section
Subject: Compliance Evaluation Inspection
FMC Corporation/Lithium Division
NPDES Permit No. NC0005177
Gaston County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at
the subject facility on January 17, 2017, by Ori Tuvia. Your cooperation during the site visit was
much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a copy of
the enclosed repot.
If you any questions, please contact Ori Tuvia at (704) 235-2190, or via email at
ori.tuv iaa,ncdenr. ggov. ..
Cc: NPDES
MRO Files
Sincerely,
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, DEQ
Mooresville Regional Office
Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115
Phone: (704) 663-16991 Fax: (704) 663-60401 Customer Service; 1-877-623-6748
Internet: www.ncwaterqualitv.orq
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report_.
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 U 2 U 3 I. NC0005177 I11- 12 7101/18 117 18 [,j 19 I c I 201
2111111I IIIIIIIIII.11-IIIIIIIIIIIIIIIIIIIIIIII �6
Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA — Reserved -
67 1.0 70 Id I 71 72 L73I74 75 1 1 1 1 1 80
I� El
Section B: FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to.POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
12:OOAM 17/01/18
11/02/01
Lithium Division Plant
Exit Time/Date
Permit Expiration Date
NC Hwy 161
12:OOAM 17/01/18
15/08131
Bessemer City NC 28016
Name(s) of Onsite Representative(s)Ttles(s)/Phone and Fax Number(s)
Other Facility Data
111
Rodney Stough Willis/ORC/704-868-7630/
Name, Address of Responsible Official/Titie/Phone and Fax Number
Contacted
Joe Vasco,PO Box 795 Bessemer City NC 28016/Plant Manager/704-868-0856/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory ,
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ori A Tuvia MRO WQ//704-663-1699/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are -obsolete.
gC
p" MAO
Page#
C
NPDES yr/mo/day Inspection Type ' 1
31 NC0005177 111 121 17/01/18 117 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
. Permit: NC0005177 Owner -Facility: Lithium Division Plant
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
Inspection Date: 01/18/2017 Inspection Type: Compliance Evaluation
❑
Is all required information readily available, complete and current?
❑
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
-
application? - —
0•
❑
❑
❑
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection? "
0
❑
❑
❑
Comment: The subiect permit expired on 8/31/20.1.5. The facility has applied for renewal on 312/2015
and is operating under the expired permit until new permit will be issued. The facility has
submitted additional documentation (location-, receiving stream, monitoring results, etc.) to
the Division's Permitting Unit regarding the addition of a new discharge outfall. This outfall
collects the discharge from the toe drainage system of the final treatment pond for Outfall
001 this oufall could be added under the new permit.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
❑
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
❑
❑
Is the chain -of -custody complete?
0•
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they. include all permit parameters? ❑ ❑ ❑
Has the facility submitted. its annual compliance report to users and DWQ? ❑ ❑ M ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑
on each shift?
Is the,ORC visitation log available and current?
M
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
M
❑
❑
❑
Is the backup operator certified -at one grade less or greater than the facility classification?
M
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's�Annual Report on file for review?
❑
❑
0
❑
Page# 3
Permit: NC0005177 Owner- Facility: lithium Division Plant
Inspection Date: 01/18/2017 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed during the insDection were organized and well maintained. DMRs
COCs. Calibration logs and ORC lops were reviewed for the period March 2016 through
❑ ❑
0
November 2016. Incorrect date was found for toxicity sampling done in October. ORC will
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑ ❑
send an amended version.
❑
Comment: On-site field analyses (dissolved oxygen, DH, conductivity) are performed under the
Laboratory
Yes. No NA NE
Are field parameters performed by certified personnel or laboratory?
N ❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
M ❑
❑
❑
# Is the facility using a contract lab?
0 ❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
M ❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑ ❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑ ❑
N
❑
Comment: On-site field analyses (dissolved oxygen, DH, conductivity) are performed under the
Company's field laboratory certification #5023. Pace Analytical (BOD, TSS, chlorides, total
nitrogen, total phosphorus) and R&A Laboratories (toxicity) have been contracted have also
been 'contracted to provide analytical support.
The laboratory instrumentation used for field analyses appeared to be properly
calibrated/verified and documented.
Effluent Sampling
Yes No' NA NE
Is composite sampling flow proportional?
❑ ❑
❑
Is sample collected below all treatment units?
❑
❑
❑
Is proper volume collected?
0 ❑
❑
❑
Is the tubing clean?
❑ ❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑ ❑
0
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0 ❑
❑
❑
representative)?
Comment: The subject permit requires effluent grab'samples.
Operations & Maintenance
Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
M ❑
❑
❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
M ❑
❑
❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The.wastewater facility appeared to be properly operated and well maintained.
Process
control measurements are being properly documented and maintained on-site. All domestic
wastewater and a small percentage of the industrial wastewater are connected to the City of
Bessemer City's wastewater collection system.
Page#
4
Permit: NC0005177 Owner _ Facility: Lithium Division Plant
Inspection Date: 01/18/2017 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Chemical Feed Yes No NA NE
Is containment adequate? ❑ ❑ ❑
Is storage adequate? 0 ❑ ❑ ❑
Are backup pumps available? 0 ❑ ❑ ❑
Is the site free of excessive leaking? M ❑ ❑ ❑
Comment: Sulfuric acid is added to the influent to maintain appropriate PH levels. Influent PH levels are
monitored by an in-line monitoring system.
Flow Measurement - Effluent
Yes No NA NE
#' Is flow meter used for reporting?
N
❑
❑
❑
Is flow meter calibrated annually?
N
❑
❑
❑
Is the flow meter operational?
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?,
❑
❑
❑.
Comment: The flow meter for Outfall 001 is calibrated annually and was last calibrated on 11/28/2016
by the Company's personnel.
Effluent Pio e Yes No NA NE
Is right of way to the outfall properly maintained? ❑ ❑ 0 ❑
Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ N ❑
Comment: The effluents from Outfalls 001 and 004 were clear with no floatable solids or -foam. _ The
discharge from the toe drainage system (Outfall 001 pond) was also clear with no floatable
solids or foam. The receiving stream did not appear to be negatively impacted.
Page# 5