HomeMy WebLinkAbout20071353 Ver 2_Staff Comments_2008060507-1353 Avon Forest SD AML comments June 5, 2008 For the level spreader at the back of Lot 7, the filter strip is too steep to allow for diffuse flow. Please either relocate the level spreader to a location where the filter strip slope is appropriate for level spreaders or provide a BMP that removes a minimum of 85 percent TSS and 30 percent TN from the stormwater generated by this drainage area. For each proposed BMP, please provide a completed BMP Supplement Form, with all the required items. The BMP Supplement Forms are available at: http://l12o.eni-.state.nc.us/su/bmp forms.htm. Please include both the Design Summary and the Required Items Checklist along with all the required items listed therein. 2. Appropriate diffuse flow measures have not been provided for the following discharge points: FES-13. the v-ditch between lots 31 and 32, and the road drainage from Cloverleaf Court that is directed to FES-3, FES-5 and FES-6. Per the requirements of the Neuse Riparian Buffer Rule, all stormwater drainage from this site must be discharged through a correctly designed level spreader. Level spreader design requirements are set forth in Chapter 8 of the North Carolina Stormwater BMP Manual, available at: http://h2o.enr.state.nc.us/su/'bmp forms.htm. Please provide one complete Level Spreader Supplement Form for each proposed level spreader.