Loading...
HomeMy WebLinkAboutNC0075027_NOV2016PC053 Site Visit_20160219 Permit: NCO075027 Owner-Facility: C8 ins Way Mobile Home Park Inspection Date: 02/10/2016 Inspection Type: Compliance Evaluation Disinfection-Tablet Yes No NA NE Is the level of chlorine residual acceptable? ❑ ❑ ❑ M Is the contact chamber free of growth, or sludge buildup? ® ❑ ❑ ❑ Is there chlorine residual prior to de-chlorination? ❑ ❑ ❑ ■ Comment: None Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ® ❑ ❑ Is sample collected below all treatment units? ® ❑ ❑ ❑ Is proper volume collected? ® ❑ ❑ ❑ Is the tubing clean? ® ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees ❑ ® ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit(frequency,sampling type ® ❑ ❑ ❑ representative)? Comment: Sampler case is broken and sampler cannot maintain proper temperature for samples. This needs to be fixed as soone as possible. If the owner decides to purchase a new sampler then he/she should purchase one that has the capability of flow proportional sampling,which is required by the permit, but is currently waived by the Division by letter Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit(frequency, sampling type, and ® ❑ ❑ ❑ sampling location)? Comment None Page# 7