May 25, 2016
RECEIVED/NCDEQ/DVVR
Ms. Jacqueline A. Jarrell, P.E., Superintendent
Environmental Management Division MAY 3 1 2016
Charlotte Mecklenburg Utilities Water Quality
4222 Westmont Drive
Charlotte, North Carolina 28217 Permitting Section
SUBJECT: Compliance Evaluation Inspection
McAlpine Creek WWTP
NPDES Permit NC0024970
Mecklenburg County, NC
Dear Ms. Jerrell:
On May 12, 2016, Roberto Scheller of this Office conducted an inspection at the subject
facility. This inspection was conducted as a Compliance Evaluation Inspection (CEI) to
insure compliance with permit requirements and conditions. Comments noted during the
subject inspection are listed under the comment section of the enclosed inspection
report. At the time of inspection the treatment facility appeared to be very well
maintained and operated. We wish to thank you and operating staff for your assistance
regarding this inspection.
The enclosed report should be self-explanatory; however, should you have any
questions, please do not hesitate to contact myself or Roberto Scheller at (704) 235-
2204 or roberto.scheller@ncdenr.gov.
Sincerely,
i ,
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: Inspection Report
cc: Sandy Neely, ORC, Charlotte Mecklenburg Utilities—McDowell Creek WWTP, 4901
Neck Road, Huntersville, NC 28078
Wastewater Branch
MSC 1617 —Central files basement
File
State of North Carolina I Environmental Quality 1 Water Resources I Water Quality Regional Operations
Mooresville Regional Office'610 East Center Avenue,Suite 3011 Mooresville,North Carolina 28115
704 663 1699
United states Environmental Probalon Agency Form Approved.
EPA wahinglm,D.C.20400 OMB Na 2040-0057
Water Compliance Inspection Report Appoval maims 8-31.95
Section A:National Data System Coding(i.e.,PCS)
Transection Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 El 2 3 I NC0024970 111 121 16/05/12 117 18I ( 19I c I 201 I
21111111 1111111 11 11 1 11 1111 1 1 11111 1111111 11 11 r
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 DA Roomed-
67
ees ved
671 1 70 LJ I. L
I 71 I I 72 I I I 731 1 174 751 11 I 1 1 1 180
Section B:FacilityData
L_1
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Pent Effective Date
POTW rine and NPDES permit Number) 10:05AM 18/05/12 14/013/01
McAlpine Creek WNW
12701 Lancaster Hwy Exit Time/Date Permit Expiration Date
Pineveb NC 23134 02:10PM 1&05/12 . 1e/02/2s
Name(s)of Omits Repreaentatve(s)/ritles(s)/Phone and Fax Numbers) Other Fealty Data
ll!
Sandy Kim Neely/ORC/704-542-0736/
Name,Address of Responsible OtI lfTlB&Phone and Fax Number
Contacted
Jacqueline A Janell,4222 Westmont Dr Charlotte NC
282171030//704-338-4480/7043385081 No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
• Permit • Flow Measurement • Operations&Maidenance II Records/Reports
• Self-Monitoring Program • Sludge Handling Disposal • Facility Site Review • Effluent/Receiving Waters
III Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and chectdists as necessary)
(See attachment summary)
Names)end Signature(s)of Inepeclor(s) Agency/Office/Phone and Fax Numbers Date
Roberto Scheller MRO WO//252-948-8481/
4 - �
Signature of Management O A Reviewer Agency/Me/Phone and Fax Numbers Date
W. Corey Basinger MRO WQ/1704-235-2194/ .t
EPA Fon 9680-3pPçnsarnobsolete. -
.�]., y r� any 4
Paget 1
NPDES yr/mo/day Inepecton Type 1
31 NC0024970 111 121 18105/12 117 18 Lie.
Section D:Summary of Finding/Comments(Math additional sheets of narrative and dleddists as necessary)
page# 2
Permit NC0024970 'Darner-Facility: McAlpine Creek wwTP
Inspection tate: 05/12/2019 Inspection Type: Compience Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new • 0 0 0
application?
Is the facility as described in the permit? • 0 0 0
#Are there any special conditions for the permit? ■ 0 0 0
Is access to the plant site restricted to the general public? • 0 0 0
Is the inspector granted access to all areas for inspection? • 0 0 0
Comment: The subject permit expired on 02/31/2016. permit under review.
Influent Sampling Yea No NA NE
#Is composite sampling flow proportional? • 0 0 0
Is sample collected above side streams? • ❑ 0 0
Is proper volume collected? • 0 0 0
Is the tubing dean/ . • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 8.0 degrees • 0 0 0
Celsius)?
Is sampling performed according to the permit? • 0 0 0
Comment: At time of inspection influent sampler was noted at 1.3 degree C.
•
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • 0 0 0
Is sample collected below all treatment units? ■ 0 0 0
Is proper volume collected? • 0 0 0
Is the tubing clean? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type • 0 0 ❑
representative)?
Comment: At time of inspection effluent sampler noted at 1.2 degrees C.
Upstream/Downstream Sampling Yos No NA NE
Is the facility sampling performed as required by the permit(frequency,sampling type,and • 0 0 0
sampling location)?
Comment:
Operations&Maintenance Yea No NA NE
Page# 3
Parrett NC0024970 Owner-Facility: McAlpine Creek WNW
Inspection Data: 05/122018 inspection Type: Compliance Evaluation
Operations& Maintenance Yes No NA NE
Is the plant generally dean with acceptable housekeeping? • 0 0 0
Does the facility analyze process control parameters,for ex:MLSS, MCRT,Settleable • 0 0 ❑
Solids, pH,DO, Sludge Judge,and other that are applicable?
Comment: First 5 mins. of 30 min. settability test noted activated sludge settled out quickly to about
45%with clear column of liquid above and visible suspended soilds. ORC noted solids in
MLSS is being brought down from higher levels for winter operation.
Equalization Basins Yes No NA NE
Is the basin aerated? • 0 0 0
Is the basin free of bypass lines or structures to the natural environment? • 0 0 0
Is the basin free of excessive grease? • 0 0 0
Are all pumps present? • 0 0 ❑
Are all pumps operable? • 0 0 0
Are float controls operable? ■ 0 0 0
Are audible and visual alarms operable? 0 0 • 0
#Is basin sizeNolume adequate? • 0 0 0
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual 0
b.Mechanical •
Are the bars adequately screening debris? • 0 0 0
Is the screen free of excessive debris? U 0 0 0
Is disposal of screening in compliance? • 0 0 0
Is the unit in good condition? • 0 0 0
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual 0
b.Mechanical •
Is the grit free of excessive organic matter? • 0 0 0
Is the grit free of excessive odor? • 0 0 0
Page# 4
Permit NC0024970 Owner-Facility: McJlpine Creek WHIP
Inspection Date: 05/12/2019 Inspection type: Compliance Evaluation
Grit Removal - Yes No NA NFe
#Is disposal of grit in compliance? • 0 ❑ 0
Comment:
Primary Clarifier Yes No NA NE
Is the clarifier free of blade and odorous wastewater? 0 0 0 IN
Is the site free of excessive buildup of solids in center well of circular clarifier? 0 0 0 II
Are weirs level? 0 0 0 •
Is the site free of weir blockage? 0 0 0 •
Is the site free of evidence of short-circuiting? 0 0 ❑ •
Is scum removal adequate? 0 0 0 IN
Is the site free of excessive floating sludge? 0 0 ❑ U
Is the drive unit operational? 0 0 0 •
Is the sludge blanket level acceptable? 0 0 0 U
Is the sludge blanket level acceptable?(Approximately Ye of the sidemall depth) 0 0 0 IN
Comment: Primary Gaffers are covered for odor control and not easly acessable.
Aeration Basins Yes No NA NE
Mode of operation Ext Air
Type of aeration system Diffused
Is the basin free of dead spots? • 0 0 0
Are surface aerators and mixers operational? 0 0 • 0
Are the diffusers operational? • 0 0 0
Is the foam the proper color for the treatment process? • 0 0 0
Does the foam cover less than 25%of the basin's surface? U 0 0 0
Is the DO level acceptable? • 0 0 0
Is the DO level acceptable?(1.0 to 3.0 mgA) • 0 0 0
Comment: Facility is in process of replacing diffusers.
Nutrient Removal Yes No NA NE
#Is total nitrogen removal required? 0 0 • 0
#Is total phosphorous removal required? • 0 0 0
Type Chemical
#Is chemical feed required to sustain process? • 0 0 0
Page# 5
WrrrYt NC0024970 Owner-Facility: McAlpns Creek W WTP
Inspection Date: 05/1V2016 Inspection Type: Compliance Evaluation
Nutrient Removal Yes No NA NE
Is nutrient removal process operating properly/? • 0 0 0
Comment: Phosphorus is chemically reduced/removed by use of ferric chloride and by use of
anaerobic zones in aeration basins.
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • 0 0 0
Is the site free of excessive buildup of solids in center well of circular clarifier? • 0 0 0
Are weirs level? • ❑ 0 0
Is the site free of weir blockage? • 0 0 0
Is the site free of evidence of short-circuiting? • 0 0 0
Is scum removal adequate? • 0 0 0
Is the site free of excessive floating sludge? • 0 0 0
Is the drive unit operational? • ❑ 0 0
Is the return rate acceptable(low turbulence)? • 0 0 0
Is the overflow clear of excessive solids/pin floc? • 0 0 0
Is the sludge blanket level acceptable?(Approximately%of the sidewall depth) • 0 0 0
Comment:
Pumps-RAS-WAS Yes No NA NE
Are pumps in place? • ❑ 0 0
Are pumps operational? • 0 0 0
Are there adequate spare parts and supplies on site? • 0 0 0
Comment:
Chemical Feed Yes No NA NE
Is containment adequate? • 0 0 0
Is storage adequate? • ❑ 0 0
Are backup pumps available? • 0 0 0
Is the site free of excessive leaking? • 0 0 0
Comment:
Filtration (Rich Rate Tertiarvi Yes No NA NE
Type of operation:
Is the filter media present? • 0 0 0
Pages 6
Permit NC0024970 Owner-Facility: McAlpine Creek VNNTP
Wpeeaon Daft 05/12/2016 Inepectlon Typo; Compliance Evaluation
Filtration (High Rate Tertiarvl Yes No NA NFe
Is the filter surface free of dogging? • 0 ❑ 0
Is the filter free of growth? • 0 0 0
Is the air scour operational? • 0 0 0
Is the scouring acceptable? • 0 0 0
Is the dear well free of excessive solicit and fitter media? • 0 0 0
Comment
Disinfection-Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant? • 0 0 0
(Sodium Hypochlorite)Is pump feed system operational? • 0 0 0
Is bulk storage tank containment area adequate?(free of leaks/open drains) • 0 0 0
Is the level of chlorine residual acceptable? • 0 0 0
Is the contact chamber free of growth,or sludge buildup? • 0 0 0
Is there chlorine residual prior to de-chlorination? • 0 0 0
Comment:
Dechlorination Yes No NA NE
Type of system? Liquid
Is the feed ratio proportional to chlorine amount(1 to 1)? • 0 0 0
Is storage appropriate for cylinders? 0 0 • 0
#Is de-chlorination substance stored away from chlorine containers? 0 0 0 0
Comment:
Are the tablets the proper size and type? 0 0 II 0
Are tablet de-chlorinators operational? 0 0 ■ 0
Number of tubes in use?
Comment: Aqueous Sodium Biosulfite is used for dechlorination.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? • 0 0 0
Are the receiving water free of foam other than trace amounts and other debris? • 0 0 0
If effluent (diffuser pipes are required) are they operating properly? 0 0 • 0
Comment: Effluent was dear with no visible suspended solids. Foam was noted at discharge point but
disipated 75- 100 yards down stream.
Pagee 7
Permit NC0024970 Owner-Facility: McAlpine Creek WWrP
Inspection Dab: 05/12/2016 Inspection Type: Compliance Evelwtlon
Effluent Pipe Yes No NA NE
Anaerobic Digester Yea No NA NE
Type of operation: • Fixed cover ,
Is the capacity adequate? • 0 0 ❑
#Is gas stored on site? • 0 0 0
Is the digester(s)free of tilting covers? • 0 0 ❑
Is the gas burner operational? • ❑ 0 0
Is the digester heated? • 0 0 0
Is the temperature maintained constantly? • 0 0 0
Is tankage available for properly waste sludge? • ❑ 0 0
Comment: Facility has gravity belt thickners and centrifuges to dewater sludge. Dewatered sludge is
taken to landfill or land applied by Synagro under Permit No.WQ0000057.
Standby Power Yes No NA NE
Is automatically activated standby power available? • ❑ 0 0
Is the generator tested by interrupting primary power source? • 0 0 0
Is the generator tested under load? • 0 0 0
Was generator tested&operational during the inspection? 0 ❑ • 0
Do the generator(s)have adequate capacity to operate the entire wastewater site? • 0 0 0
Is there an emergency agreement with a fuel vendor for extended run on back-up power? • 0 0 0
Is the generator fuel level monitored? • ❑ ❑ 0
Comment: Facility has 6 standby generators that are tested monthly.
Page# 8