HomeMy WebLinkAboutNC0089206_Compliance Evaluation Inspection_20160311 PAT MCCRORY
DONALD R. VAN DER VAART
Water Resources_ S. JAY ZIMMERMAN
LNYIRONMe1TAL OUA L. 'r
RECEIVED/NCDEQIDWR
March 11, 2016
Mr. Neil McElveen, P.E. MAR 1 5 2':E
Department Manager Water Quality
Terracon Permitting Section
2020 East Starita Road
Charlotte, NC 28206
Subject: Compliance Evaluation Inspection
Claire Sprayway
Ground water remediation
NPDES Permit No. NC0089206
Mecklenburg County
Dear Mr. McElveen:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on March 3, 2016 by Ori Tuvia and Ed Watson. Your cooperation during
the site visit was much appreciated. Please advise the staff involved with this NPDES Permit by
forwarding a copy of the enclosed report.
After further review of the Transit Time Flow Meter—Model TTFM 1.0, it was confirmed
that the flow meter does need to be calibrated yearly. Calibration can be done in-house but
must be completed annually.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Sincerely,
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, DEQ
Cc: NPDES (Derek Denard)
MRO Files
Mooresville Regional Office
Location:610 East Center Ave.,Suite 301 Mooresville.NC 28115
Phone:(704)663-1699\Fax:(704)663-6040\Customer Service:1-877-623-6748
United States Environmental Protection Agency
Form Approved.
E PA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 u 2 3 I N00089206 111 12 16/03/03 117 18 i,,i 19 i S i 201 I
211 I I I I I I I I I II I � I I I I I I I I I I I I I I I I I I I I II 1 1 1 1 1 166
Inspection Work Days Facility Self-Monitoring Evaluation Rating 81 QA — Reserved--
6711.o
eserved----
6711 o 1 70 Id I 71 tyIre JI 72 1 N 1 731
I 174 751 I I I I I I 180
LJ Section B:Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 09:15AM 16/03/03 16/03/01
Church Street remediation site
2100 N Church St Exit Time/Date Permit Expiration Date
Charlotte NC 28202 10:00AM 16/03/03 20/06/30
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
//1
Analee L Farrell/ORC/919-630-0421/
Neal McElveen/1704-594-8912/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Gary Myers,105 Boldt Ln Saint Clair MO 63077/1636-629-3400/6366290500
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
• Permit • Flow Measurement • Operations&Maintenance • Records/Reports
MI Self-Monitoring Program • Facility Site Review • Effluent/Receiving Waters MI Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Edward Watson MRO GW///
Ori A Tuvia MRO WQ//704-663-1699/ , /i 6
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W.Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete. d f �{4e .1t 24`
. D9 +4 ����
Page# 1
NPDES yr/mo/day Inspection Type (Cont.) 1
31
NC0089206 I11 121 16/03/03 117 18 [ j
Section D:Summary of Finding/Comments(Attach additional)sheets of narrative and checklists as necessary)
1 Notes by Ed Watson.
The ten(10)recovery wells are paired as an air sparge and pump system. The wells are connected to
the remediation trailer through a network of trenches. Influent water enters the remediation building and
is first directed through a series of bags filters. The size of the filters range between 50 to 100
microns. These bag filters collect the suspended solids out of the influent water. The water is then
sent to a four(4)tray air stripper which completes the removal of the chlorinated solves. Effluent water
is collected from a sampling port located after the stripper tower. There is a 1000 gallon holding tank
located out-side of the remediation building that is used to collect the extracted water while the system
is being serviced. Water can be sent to the system from this tank on an as called for basis. This
allows the system to continuously run during system maintenance. Effluent water is discharged into a
near site storm drain that discharges to an unnamed tributary of Little Sugar Creek.
The direction of groundwater flow across the site appears to the southeast. There are eighteen(18)
monitoring wells on site where water levels are regularly measured. A request was made to be
provided with the average depth to water across the site. Additional information requested during this
inspection includes the area of influence the remediation system and a copy of a recent manifest for
the disposal of the spend filter bags.
Page# 2
Permit: NC0089206 Owner-Facility: Church Street remediation site
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0 0 • 0
application?
Is the facility as described in the permit? • 0 0 0
#Are there any special conditions for the permit? 0 • 0 0
Is access to the plant site restricted to the general public? • 0 0 0
Is the inspector granted access to all areas for inspection? • 0 0 0
Comment: Permit was issued on 3/1/2016 effective until 6/30/2020.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • 0 0 0
Is all required information readily available,complete and current? • 0 0 0
Are all records maintained for 3 years(lab. reg. required 5 years)? • 0 0 0
Are analytical results consistent with data reported on DMRs? • 0 0 0
Is the chain-of-custody complete? • 0 0 0
Dates,times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs •
Are DMRs complete:do they include all permit parameters? • 0 0 0
Has the facility submitted its annual compliance report to users and DWQ? 0 0 • 0
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator 0 0 • 0
on each shift?
Is the ORC visitation log available and current? • 0 0 0
Is the ORC certified at grade equal to or higher than the facility classification? U 0 0 0
Is the backup operator certified at one grade less or greater than the facility classification? U 0 0 0
Is a copy of the current NPDES permit available on site? • 0 0 0
Facility has copy of previous year's Annual Report on file for review? 0 0 • 0
Comment: DMRs, COC and ORC logs were reviewed for the months of 3/2014- 11/2015.All records
were well maintained and organized.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • 0 0 0
Page# 3
Permit: NC0089206 Owner-Facility: Church Street remediation site
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Are all other parameters(excluding field parameters)performed by a certified lab? • 0 0 0
#Is the facility using a contract lab? • ❑ 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? 0 0 • 0
Incubator(BOD)set to 20.0 degrees Celsius+/-1.0 degrees? 0 0 II 0
Comment: Pace Lab is contracted to analyze samples.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ 0 • 0
Is sample collected below all treatment units? • 0 0 0
Is proper volume collected? • 0 0 0
Is the tubing clean? 0 0 0 U
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type • 0 0 0
representative)?
Comment: Pace Lab analyzes samples for:TSS,Trichloroethane, Dichloromethane, Dichloroethene,
Napthalene,Tetrachloroethene, 12 Dichloroethane, Trichloroethane, and Chronic toxicity.
Flow Measurement - Effluent Yes No NA NE
#Is flow meter used for reporting? • 0 0 0
Is flow meter calibrated annually? 0 IN 0 0
Is the flow meter operational? • 0 0 0
(If units are separated)Does the chart recorder match the flow meter? • 0 0 0
Comment: Electronic flow meter,Transit Time Flow Meter—Model TTFM 1.0, is used. Flow meter has
not been calibrated.Must be calibrated annually.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? 0 0 II 0
Are the receiving water free of foam other than trace amounts and other debris? • 000
If effluent (diffuser pipes are required) are they operating properly? 0 0 • 0
Comment: Discharges into storm drain.
Operations & Maintenance Yes No NA NE
Page# 4
Permit: NC0089206 Owner-Facility: Church Street remediation site
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? I 0 0 0
Does the facility analyze process control parameters,for ex:MLSS, MCRT, Settleable 0 0 I 0
Solids, pH, DO,Sludge Judge,and other that are applicable?
Comment: Ten recovery wells are connected to the remediation trailer through a network of trenches.
The water is then sent to a four tray air stripper.Area of influence of all ten recovery wells is
estimated to be 40,000 ft^2. Effluent water is discharged into a near site storm drain that
discharges to an unnamed tributary of Little Sugar Creek.
Page# 5