HomeMy WebLinkAboutNC0066397_Compliance Evaluation Inspection_20160407 PAT MCCRORY
Governor
DONALD R. VAN DER VAART
Secretary
Water Resources S. JAY ZIMMERMAN
ENVIRONMENTAL QUALITY
Director
April 7, 2016
aPR 19 ,
Mr. Steve Boheler, Superintendent
Cleveland County Schools
866 Poplar Springs Church Road
Shelby,NC 28152
Subject: Compliance Evaluation Inspection
Casar Elementary School WWTP
NPDES Permit No.NC0066397
Cleveland County
Dear Mr. Boheler:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at
the subject facility on April 5, 2016 by Ori Tuvia. The cooperation of Timothy Lancaster during the
site visit was much appreciated. Please advise the staff involved with this NPDES Permit by
forwarding a copy of the enclosed report.
The main areas of concern that were observed during the inspection:
1. ORC visitation logs have not been maintained.
2. A copy of the NPDES permit must be on-site.
The report should be self-explanatory; however, should you have any questions concerning this
report, please do not hesitate to contact Ori Tuvia at(704) 235-2190, or at ori.tuvia@ncdenr.gov.
Sincerely,
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources,DEQ
cc: NPDES (Charles Weaver)
MRO Files
Mooresville Regional Office
Location:610 East Center Ave.,Suite 301 Mooresville.NC 28115
Phone:(704)663-1699\Fax:(704)663-6040\Customer Service:1-877-623-6748
Internet:www.ncwaterquality.org
United States Environmental Protection Agency Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 (ti i 2 LI 3 I N00066397 111 12 I 16/04/05 117 18 I,,I 19 ( G I 201_1
211 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I 1 1 1 1 1 1 1 1 1 i l l l l I 1 1 1 1 1 1 1 I I 166
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA —Reserved --
6711 0 I 7014 I 71 IN I 72 I N I 731 1 174 7511 1 1 1 1 1 1 180
Section B:Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number)
09:45AM 16/04/05 13/12/01
Casar Elementary School WWTP
436 School House Rd Exit Time/Date Permit Expiration Date
Casar NC 28020 10:45AM 16/04/05 18/08/31
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Timothy Reid Lancaster//704-487-9087/
Timothy Reid Lancaster/ORC/704-487-9087/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Steve Boheler,866 Poplar Springs Church Rd Shelby NC
28152//704-487-9087/7044876943 No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
• Permit II Flow Measurement 111 Operations&Maintenance II Records/Reports
• Self-Monitoring Program II Sludge Handling Disposal U Facility Site Review NI Effluent/Receiving Waters
II Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
On A Tuvia MRO WQ//704-663-1699/
Li/91 / 6
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W.Corey Basinger MRO WQ//704-235-2194/
EPA Fo 3560-3(Rev 9-94)PFevious editions are obsolete.
a4/.1--t/f7-- — tve- - Di-(4)g -- /`-9 .. � ''0_'_,-- 7,.)fe
Page# 1
NPDES yr/mo/day Inspection Type 1
31
NC0066397 111 121 16/04/05 I 17 18 is i
.
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0066397 Owner-Facility: Cesar Elementary School WWTP
Inspection Date: 04/05/2016 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0 0 II 0
application?
Is the facility as described in the permit? • 0 0 0
#Are there any special conditions for the permit? 0 • 0 0
Is access to the plant site restricted to the general public? • 0 0 0
Is the inspector granted access to all areas for inspection? • 0 0 0
Comment: Subject permit expires on 8/31/2018.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? 0 II 0 0
Is all required information readily available,complete and current? • 0 0 0
Are all records maintained for 3 years(lab.reg. required 5 years)? • 0 ❑ El
Are analytical results consistent with data reported on DMRs? • 0 0 0
Is the chain-of-custody complete? • 0 0 0
Dates,times and location of sampling
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis U
Name of person performing analyses •
Transported COCs •
Are DMRs complete:do they include all permit parameters? • El 0 0
Has the facility submitted its annual compliance report to users and DWQ? • El 0 0
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator 0 0 II El
on each shift?
Is the ORC visitation log available and current? • 0 0 0
Is the ORC certified at grade equal to or higher than the facility classification? • 0 0 ❑
Is the backup operator certified at one grade less or greater than the facility classification? • 0 0 ❑
Is a copy of the current NPDES permit available on site? 0 • ❑ El
Facility has copy of previous year's Annual Report on file for review? ❑ 0 I 0
Comment: DMR's, COC and calibration logs were reviewed for the months 8/2013- 10/2015. ORC has
indicated that he has not been maintaining ORC loos and will start doing so. Permit was not
on site.
Laboratory Yes No NA NE
Page# 3
Permit: NC0066397 Owner-Facility: Casar Elementary School WWTP
Inspection Date: 04/05/2016 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • ❑ 0 0
Are all other parameters(excluding field parameters)performed by a certified lab? • 0 0 0
#Is the facility using a contract lab? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? 0 0 MI 0
Incubator(BOD)set to 20.0 degrees Celsius+l-1.0 degrees? 0 0 • 0
Comment: PH is measured in house. Pace Labs performs and analyzes all other sampling required by
the sublect permit.
Septic Tank Yes No NA NE
(If pumps are used)Is an audible and visual alarm operational? 0 0 U 0
Is septic tank pumped on a schedule? • 0 0 0
Are pumps or syphons operating properly? • 0 0 0
Are high and low water alarms operating properly? • 0 0 0
Comment: The septic tank is pumped out annually over the summer by Wesson Septic Tank Service.
Last pumped on 6/15/2015.
Sand Filters (Low rate) Yes No NA NE
(If pumps are used)Is an audible and visible alarm Present and operational? • ❑ 0 0
Is the distribution box level and watertight? • 0 0 0
Is sand filter free of ponding? • 0 0 0
Is the sand filter effluent re-circulated at a valid ratio? • 0 0 0
#Is the sand filter surface free of algae or excessive vegetation? U 0 0 0
#Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1) • 0 0 0
Comment:
Disinfection -UV Yes No NA NE
Are extra UV bulbs available on site? 0 0 0 •
Are UV bulbs clean? • ❑ 0 0
Is UV intensity adequate? • 0 0 0
Is transmittance at or above designed level? 0 0 0 IN
Is there a backup system on site? 0 0 0 II
Is effluent clear and free of solids? • 0 0 0
Page# 4
Permit: NC0066397 Owner-Facility: Casar Elementary School w'TP
Inspection Date: 04/05/2016 Inspection Type: Compliance Evaluation
Disinfection -UV Yes No NA NE
Comment:
Flow Measurement-Effluent Yes No NA NE
#Is flow meter used for reporting? • ❑ 0 0
Is flow meter calibrated annually? • 0 0 0
Is the flow meter operational? • 0 0 0
(If units are separated)Does the chart recorder match the flow meter? U 0 0 0
Comment: New flow meter was installed on September 2015. Flow meter was calibrated on 10/20/2015
by Kenneth Nash. Prior to September 2015 the facility was using potable water meter for
estimating effluent flow.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? 0 0 • 0
Is sample collected below all treatment units? • 0 0 0
Is proper volume collected? • 0 0 0
Is the tubing clean? 0 0 • 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type • ❑ 0 0
representative)?
Comment: The permit requires effluent grab samples.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? • 0 0 0
Are the receiving water free of foam other than trace amounts and other debris? • 0 0 0
If effluent (diffuser pipes are required) are they operating properly? 0 0 • 0
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • 0 0 0
Does the facility analyze process control parameters,for ex: MLSS, MCRT, Settleable • 0 0 0
Solids,pH, DO,Sludge Judge,and other that are applicable?
Comment: The facility appeared well maintained and operated at the time of the inspection. ORC must
maintain ORC logs.
Page# 5