HomeMy WebLinkAboutNC0085812_Compliance Inspection 2016_20160303 PAT MCCRORY
Governor
N
a
DONALD R. VAN DER VAART
Secretary
Water Resources
ENVIRONMENTAL QUALITY S. JAY ZIMMERMAN
Director
March 3, 2016
RECEIVED/NCDEQ/DWR
Mr. Richard D. McMillian, P.E. MAR 1 0 2016
Water &Wastewater Division Director
500 North Main Street, Suite 600 Water Quality
Monroe, North Carolina 28112-4730 Permitting Section
SUBJECT: Compliance Evaluation Inspection
Grassy Branch WWTP
NPDES Permit NC0085812
Union County, NC
Dear Mr. McMillian:
On March 3, 2016, Roberto Scheller of this Office conducted an inspection at the subject
facility. This inspection was conducted as a Compliance Evaluation Inspection (CEI) to
insure compliance with permit requirements and conditions. At the time of inspection
facility appeared to be very well maintained and operated. It was noted that the subject
facility experiences high flows due to inflow and infiltration. An inspection of the
collection system was conducted by this Office on February 23, 2016 and will be
addressed under separate cover. We wish to thank you and operating staff for your
assistance regarding the inspection. A copy of this inspection will be forwarded to the
facility's Operator-in-Responsible-Charge (ORC).
The enclosed report should be self-explanatory; however, should you have any
questions, please do not hesitate to contact myself of Roberto Scheller at (704) 235-
2204 or roberto.scheller@ncdenr.gov.
Sincerely,
ed;'
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: Inspection Report
cc: Danny L. Smith — ORC— Charlotte Water
Dawn Padgett— Operations Manager—Charlotte Water
Wastewater Branch
MSC 1617 — Central files basement
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office'610 East Center Avenue,Suite 3011 Mooresville,North Carolina 28115
704 663 1699
United States Environmental Protection Agency Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 h 2 L 3 I NC0085812 111 12 I 16/03/03 117 18 19 LI I 201
2111 ( 111111111111111111111111111111111111111 p6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA -------------------Reserved------------
67 1 I 70 711 I 72 Lai 731 1 174 75I 1 1 1 1 1 1 180
LJ Section B:Facility Data 1
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 10:02AM 16/03/03 13/12/01
Grassy Branch WWTP
Exit Time/Date Permit Expiration Date
Old Fish Rd
11:52AM 16/03/03 18/10/31
Monroe NC 28111
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
Ill
Danny L Smith/ORC//
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Edward Goscicki,500 N Main St-Ste 500 Monroe NC 281124730/Public Works
Director/704-296-4212/7042964232 No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
5 Flow Measurement 5 Operations&Maintenance • Records/Reports II Self-Monitoring Program
Facility Site Review • Effluent/Receiving Waters
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
bertooScheller MRO WQ//252-946-6481/ `/ �, //
Y c!V FO
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W.Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3 Rev 9-94)Previous editions are obsolete. �l(,
Attsr-e 721441— 112-Q
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC0085612 111 121 16/03/03 I 17 18 ILI
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0085812 Owner-Facility: Grassy Branch WVViP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • 0 0 0
Is all required information readily available,complete and current? • 0 0 0
Are all records maintained for 3 years(lab. reg. required 5 years)? • 0 0 0
Are analytical results consistent with data reported on DMRs? • 0 0 0
Is the chain-of-custody complete? • 0 0 0
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs •
Are DMRs complete:do they include all permit parameters? • 0 0 0
Has the facility submitted its annual compliance report to users and DWQ? • 0 0 0
(If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator 0 0 • ❑
on each shift?
Is the ORC visitation log available and current? • ❑ 0 0
Is the ORC certified at grade equal to or higher than the facility classification? • 0 0 0
Is the backup operator certified at one grade less or greater than the facility classification? • 0 0 0
Is a copy of the current NPDES permit available on site? • 0 0 ❑
Facility has copy of previous year's Annual Report on file for review? 0 0 0 •
Comment:
Operations& Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? U ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • 0 0 0
Solids, pH,DO, Sludge Judge,and other that are applicable?
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical ❑ •
Are the bars adequately screening debris? • 0 0 0
Is the screen free of excessive debris? • ❑ 0 0
Page# 3
Permit: NC0085812 Owner-Facility: Grassy Branch WWTP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Bar Screens Yes No NA NE
Is disposal of screening in compliance? • ❑ 0 0
Is the unit in good condition? • ❑ 0 0
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated? • 0 0 0
Is the basin free of bypass lines or structures to the natural environment? • ❑ 0 0
Is the basin free of excessive grease? • 0 0 0
Are all pumps present? • ❑ 0 0
Are all pumps operable? • 0 0 0
Are float controls operable? • 0 0 0
Are audible and visual alarms operable? • 0 0 0
#Is basin size/volume adequate? • 0 0 0
Comment: This facility is having issues with I&I.
Aeration Basins Yes No NA NE
Mode of operation Ext.Air
Type of aeration system Diffused
Is the basin free of dead spots? • 0 0 0
Are surface aerators and mixers operational? • 0 0 ❑
Are the diffusers operational? • 0 0 0
Is the foam the proper color for the treatment process? • 0 0 0
Does the foam cover less than 25%of the basin's surface? • 0 0 0
Is the DO level acceptable? • 0 0 0
Is the DO level acceptable?(1.0 to 3.0 mg/I) • 0 0 0
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ 0 0
Is the site free of excessive buildup of solids in center well of circular clarifier? • ❑ 0 0
Are weirs level? • 0 0 0
Is the site free of weir blockage? • ❑ 0 0
Is the site free of evidence of short-circuiting? • 0 ❑ ❑
Page# 4
Permit: NC0085812 Owner-Facility: Grassy Branch VWVTP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is scum removal adequate? • 000
Is the site free of excessive floating sludge? • ❑ ❑ ❑
Is the drive unit operational? • 000
Is the return rate acceptable(low turbulence)? • 000
Is the overflow clear of excessive solids/pin floc? • ❑ ❑ ❑
Is the sludge blanket level acceptable?(Approximately 1/4 of the sidewall depth) • 000
Comment:
Disinfection - UV Yes No NA NE
Are extra UV bulbs available on site? • ❑ ❑ ❑
Are UV bulbs clean? • 000
Is UV intensity adequate? ❑ ❑ ❑ •
Is transmittance at or above designed level? 00D •
Is there a backup system on site? • ❑ ❑ ❑
Is effluent clear and free of solids? • 000
Comment: UV was noted as being cleaned weekly.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ • ❑
Is sample collected below all treatment units? • DOD
Is proper volume collected? • 000
Is the tubing clean? • ❑ ❑ ❑
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Is the facility sampling performed as required by the permit(frequency, sampling type • 000
representative)?
Comment:
Flow Measurement-Influent Yes No NA NE
#Is flow meter used for reporting? • 000
Is flow meter calibrated annually? • 000
Is the flow meter operational? • 000
(If units are separated) Does the chart recorder match the flow meter? • 000
Comment:
Page# 5
Permit: NC0085812 Owner-Facility: Grassy Branch WWTP
Inspection Date: 03/03/2016 Inspection Type: Compliance Evaluation
Flow Measurement- Influent Yes No NA NE
Standby Power Yes No NA NE
Is automatically activated standby power available? • 0 0 0
Is the generator tested by interrupting primary power source? • 0 0 0
Is the generator tested under load? • 0 0 0
Was generator tested&operational during the inspection? 0 0 0 II
Do the generator(s)have adequate capacity to operate the entire wastewater site? • 0 0 0
Is there an emergency agreement with a fuel vendor for extended run on back-up power? • 0 0 0
Is the generator fuel level monitored? • 0 0 0
Comment:
Page# 6